Performa – SoP 002: Action taken report for safety measures complied for the accidents occurred
Sr Circle Location of Accident and details of the victim Date of occurrence Type of Accident Cause of Accident Findings of CEI / EI / AEI Remedies suggested by CEI /EI / AEI in various cases Whether the remedy suggested is complied Action taken to avoid recurrence of such Accident
1st half                  
1 RCC MOTAMAVA - SHRI. JAYESH NARANBHAI BAGDA  2.6.16 FHO Accident occurred to victim a labour of construction contractor Sh Ramjibhai while he was working on roof of newly constructed house of Sh Mukeshbhai Jirajbhai under 11 KV HT line, as per primary investigation no 11 kv line tripping observed   Report yet not received NA NA House Holder responcible 1
2 RCC NAVAGAM - SHRI. JAINUDIN IQBALMOHMMAD AALA 25.6.16 FHO From site visit it concluded that accident took place while victim was working on bonnet of truck which was parked under the 11 KV HT line and as soon as he stood up on truck bonnet come in induction zone of live wire and got electric shock and fell down from truck bonnet   and had injury on back side of head and met with fatal accident.  On investigation no tripping observed on 11 KV HT line side. 1 )clearance from GL 4.70 meter found  which ids to be  6.1 meter .thus ground clearance not maintained and 2) near by house clearance not maintained   eventhough  electric connection given ,  3 ) Guarding not provided  1 ) Dy Engineer  breach safety rtegulation 2010 ,  2 )  If Driver not park truck under HT line and victim not  stamnd  up on truck and work accident could br avoided   Yes , Under Groung Cable HT line provideed for 300 mtr . Under Ground cable provided  to maintain clearance  2
3 RCC KOTHARIYA- cow of owner SHRI. LAXMANBHAI VAJABHAI  SANIYA  29.6.16 FA accident occurred due to damage of insulation of service wire of single phase connection Co No 34513296925 of Mukeshbhai Khimjibhai at LT pole live conductor came in contact with guarding angle so leakage current was passing through guarding so as soon as cow come in vicinity of LT pole No 18/5792 (next pole ) and as it was raining got electric shock and met with fatal accident  Report yet not received NA NA SERVICE WIRE RECTIFIED  3
4 RCC KOTHARIYA- SHRI. BHAVESSHBHAI BACHYBHAI SONARAT  29.6.16 FHO accident occurred while victim climb on LT line pole having Pole to do some unauthorized work and he come in contact with live wire on pole and got electric shock and met with fatal accident Victim  breach  safety regulation  2010 - clause No 3  and  without havinh qualified person worked  of electric line  . During working not observed safety  gadgets by victim For this accident victim him self responcible   If  victim observed safety regulation  2010- clause no 3, and clause no 19  accident could be avoided . N A AS VICTIM HIM SELF  RESPONCIBLE . Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 4
5 RCC RAJKOT - cow of owner Shri. Hiteshbhai Momnbhai Toliya 24.8.16 FA There was rain on dtd. 24-8-2016, due to rain, main cable of  No. KOT/VRN/046/L001/DT 006 Fired and touch with radiator. Hence leakage current passes through body of transformer and due to common neutral of DT 006 & DT 008 leakage current passes through earth of DT 008. At that time cow was passing nearby distribution box of DT 008 and came in ontact with this box and got electrocute and met with fatal accident. Detail investigation report will be sent soon. Report yet not received NA NA Main calbe rectifed 5
6 RCC Kothariya Velnath - Shri. Haribhai Ramabhai Kuvariya 21.4.16 FHO About  the accident come to know  by D.E. Vavdi  urban S/dn on date 26-04-16 so immediately site visit done by him in present of  Electrical inspector .From site visit and statement of victim’s brother it concluded that accident occurred on date 21-04-2016 while victim was doing some work unauthorisedly on LT line pole . During that  he fell down from LT line pole and admitted to civil hospital  and met with fatal accident ,As per statement of police and victim’s elder brother victim had bums on his finger . P.M. report of victim is awaited.    Victim was doing some work unauthorized on LT line pole and met with fatal accident.  Victim is responsible for the accident (Breach of Safety Regulation 2010 no. 3) Yes Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 6
7 RRC NANA MAHIKA                    RAHUL OMKARBHAI CHAUHAN 21-4-2016 FHO Due to encroachment and new illegal construction near 11 KV Ag Line, the victim came in contact with live wire passing near the terrace and got electrocuted. The horizontal clearance between line and construction was 3 to 4 inch only. Hence it is clear negligence of owner of under construction room.  Report yet not received N.A N.A FIR LETTER WRITTEN TO POLICE DEPT. VIDE GDD/3507/22.4.16 1
8 RRC SURYA RAMPARA                    SURESHBHAI PARSHOTTAMBHAI PANSURIYA 30-4-2016 NFHO As reported by DE Kuvadava victim Sh. Sureshbhai Parshottambhai Pansuriya has carried out unauthorized work of fixing halogen light in marriage function at village Surya Rampara of Shri Babubhai Vaghjibhai Zala on dt. 30.04.2016 Time 15:55 PM (App). While victim was working above unauthorized work on existing PSC pole of 11 KV Jiyana JGY Feeder & to give connection for that in line (as per statement of eye witness) victim has got electric shock & fall down from pole, immediately victim refer at hospital Kuvadava & then refer at Government Hospital Rajkot for further treatment. Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 2
9 RRC JAM KANDORNA                    AJAYBHAI JAGDISHBHAI SHIYAL 2-5-2016 FHO As informed by police station Jamkandorna at 10:30 Am as per owner of Dharti travels Shri Dhirubhai’s statement, his driver (victim) waked up from sleeping at roof of bus parking under 11 KV line. He came in contact with live 11 KV wire and met with fatal accident. There are no any sparking spot found on 11 KV wire and no any TT recorded at 66 KV SS during time. Detail investigation follows   . Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 3
10 RRC MANEKVADA                    THE BUFFALO OF SHRI  DEVABHAI GANDUBHAI SARASIYA 4-5-2016 FA As per information received telephonically at approx. 11:30 A.M .As per physical observation found at site at the time of rojkam due to heavy wind top angle tilted and conductor touched to earthing G.I wire and leakage power passed through G.I wire and P.S.C pole. so these two numbers of she buffaloes came contact with GI earth wire and got electrocuted. Actual reason of accident will be submitted with detail investigation report which is under progress. Report yet not received N.A N.A This accident is suspected and detail investigation is under process 4
11 RRC MANEKVADA                    THE BUFFALO OF SHRI  DEVABHAI GANDUBHAI SARASIYA 4-5-2016 FA As per information received telephonically at approx. 11:30 A.M .As per physical observation found at site at the time of rojkam due to heavy wind top angle tilted and conductor touched to earthing G.I wire and leakage power passed through G.I wire and P.S.C pole. so these two numbers of she buffaloes came contact with GI earth wire and got electrocuted. Actual reason of accident will be submitted with detail investigation report which is under progress. Report yet not received N.A N.A This accident is suspected and detail investigation is under process 5
12 RRC SHAPAR VERAVAL                    ANILBHAI JIVRAMBHAI DHORECHA 7-5-2016 FHO As reported by DE Shapar Veraval on date 09.05.2016 Unitech Casting Industrial Consumer barring Consumer No. 81901-01965-1 load 100KW was came at office on 13:00 Hrs and personally inform to SDO Shapr (V)  about fatal accident occurred at his premises, as per PAR Submitted by SDO Shapar (V) the victim Sh. Anilbhai Jivrambhai Dhorecha came to the above address for carpentry work during night hours for measurement when he entered in the office at the first floor with 15 feet aluminum rod with his hand  Victim was trying to enter in the office along with this aluminum road he was cross the aluminum rod and it touched to the bare 11 KV live electric line of Royal Industrial feeder which is 9 feet away from accident place and victim got electric shock and died at site.  VICTIM HIMSELF IS REPONSIBLE FOR SAID ACCIDENT. N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 6
13 RRC VAVDI NO VIDO                    HARDIIPSINH KISHORSINH RANA 15-5-2016 FHO Due to looping of cable network wire was looped with the 11 kv Padavala JGY feeder At the same location the victim was came for the maintenance of dish cable wire network. When victim was cutting the cable network wire with the help of very inferior quality insulated player he was came in contact with the live electric wire through looped wire and got electrocuted.  Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 7
14 RRC KAHTLI                    NAVINCHANDRA LAXMANBHAI NINAMA    4-6-2016 NFHD A non fatal Electrical Accident has been occurred to the victim at village Khatali while the victim climbed the Transformer Centre (Hokdavadu) to attend the complain of loose neutral and power fluctuation. Before climbing the to T/C pole, the victim has dismantled the D.O. fuse, there after he climbed to the T/C but while touching the neutral, spark was occurred and felt electric shock and his uniform shirt started burning on the back side. He climbed down himself in this situation through help of villagers. Further investigation is in process  Report yet not received N.A N.A  Strict Instruction to give line
staff not to work without safety precausion & not to work without obeserving safety rules.
8
15 RRC VIRDA VAJDI                    MUKESHBHAI BABUBHAI MAKWANA 17-6-2016 FHO As reported by DE Ronki on date 17.06.2016 human fatal accident occur of shree Mukeshbhai Babubhai Makwana,  at transformer center of Sh. Arjanbhia Samatbhai Khimaniya 3ph connection, consumer no 89749-00410-8 of village: Virda vajdi. victim got electric shock while he was self-tiding of D.O. fuse element unauthorized and touched 11 KV side DO fuse of TC structure. Victim was climbed the DP structure for tiding the failed DO element with the help of Plier and got  electric shock.  VICTIM HIMSELF IS REPONSIBLE FOR SAID ACCIDENT. N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 9
16 RRC MOTA DADVA                    A COW OF SHRI BHIMBHAI LAGHARABHAI MEVADA 23-6-2016 FA As per site visit and eye witness Statements Due to rain and wind pressure end of  service wire’s terminal was touched with Nut-Bolt of  LT shackle Insulator So, current was passing though LT pole to  ground and spread around LT pole, that time  cow was passing near that LT pole and got electric shocked.  Report yet not received N.A N.A New Earthing & Service PilferProofing Done 10
17 RRC KOTHI                                 A COW OF VELABHAI CHANABHAI  23-6-2016 FA As per site visit and eye witness Statements Due to rain, leakage current was spread around transformer center that time cow was passing near that TC that time cow got electric shocked and fall on the ground. Report yet not received N.A N.A T/C Fencing Done. 11
18 RRC JIYANA                              FA 1 NO OF GOAT 2 NO OF BUFFALO BABY 
1) Goat Owner Name Shri. Raiya Natha Sarsiya
2) Buffalo Baby Owner Name Shri Bhopa Giga Sarasiya
3) Buffalo Baby Owner Name Shri Nagji Giga Sarasiya
29-6-2016 FA A Fatal accident occurred to animals 1 no. Goat and 2nos. Buffalo (baby) at Jiyana Village.  From investigation at site it is found that there is joint in service line of consumer name Sh. Giga Gandu Fangaliya, consumer no. 89664/00064/7. Due to wind & rain the joint portion of service line touches to the guy wire of Existing Lt line pole no. ,( FC/01/KHF/M/DT/10/178 ) which passes nearby it. At that time 3 nos. victim 1 no. goat and 2 nos. buffalo (baby) passes from that area and directly comes to contact with pole guy and got electric shock and died at same place. Report yet not received N.A N.A SERVICE WIRE REPLACED. 12
19 RRC JIYANA                              FA 1 NO OF GOAT 2 NO OF BUFFALO BABY 
1) Goat Owner Name Shri. Raiya Natha Sarsiya
2) Buffalo Baby Owner Name Shri Bhopa Giga Sarasiya
3) Buffalo Baby Owner Name Shri Nagji Giga Sarasiya
29-6-2016 FA A Fatal accident occurred to animals 1 no. Goat and 2nos. Buffalo (baby) at Jiyana Village.  From investigation at site it is found that there is joint in service line of consumer name Sh. Giga Gandu Fangaliya, consumer no. 89664/00064/7. Due to wind & rain the joint portion of service line touches to the guy wire of Existing Lt line pole no. ,( FC/01/KHF/M/DT/10/178 ) which passes nearby it. At that time 3 nos. victim 1 no. goat and 2 nos. buffalo (baby) passes from that area and directly comes to contact with pole guy and got electric shock and died at same place. Report yet not received N.A N.A SERVICE WIRE REPLACED. 13
20 RRC JIYANA                              FA 1 NO OF GOAT 2 NO OF BUFFALO BABY 
1) Goat Owner Name Shri. Raiya Natha Sarsiya
2) Buffalo Baby Owner Name Shri Bhopa Giga Sarasiya
3) Buffalo Baby Owner Name Shri Nagji Giga Sarasiya
29-6-2016 FA A Fatal accident occurred to animals 1 no. Goat and 2nos. Buffalo (baby) at Jiyana Village.  From investigation at site it is found that there is joint in service line of consumer name Sh. Giga Gandu Fangaliya, consumer no. 89664/00064/7. Due to wind & rain the joint portion of service line touches to the guy wire of Existing Lt line pole no. ,( FC/01/KHF/M/DT/10/178 ) which passes nearby it. At that time 3 nos. victim 1 no. goat and 2 nos. buffalo (baby) passes from that area and directly comes to contact with pole guy and got electric shock and died at same place. Report yet not received N.A N.A SERVICE WIRE REPLACED. 14
21 RRC VIRPUR                    AMRUTBHAI MADHABHAI VAGHELA 3-7-2016 NFHO We came to know from today”s news paper. Accident occurred due to illegal construction by OWNER Shri Subhashbhai Ratilala Joshi at Chitrakut Park, Virpur nearby 11 KV Virpur feeder. The victim was standing at first floor and lifting iron rod from ground floor to first floor. The Iron rod came into induction zone of 11 KV and get electric shock. Report yet not received N.A N.A 40MTR COATED CONDUCTOR PROVIDED VIDE  SR NO:- 8207638 AMT :- 1690 15
22 RRC PANCHVADA                      A COW OF SHRI KALUBHAI AMRABHAI DANGAR 10-7-2016 FA As per site visit and eye witness Statements a cow was grassing near transformer centre that time cow came in contact with earthing wire of transformer centre and got electric shocked and this accident occurred. Report yet not received N.A N.A Earthing of this TC is reactivated and arround the tc fencing work completed  16
23 RRC DHORAJI                             A COW OF SHRI SIDIK JUSABHAI MATAWA 13-7-2016 FA As per complain No 2233  Dt 13.07.16 received at Dhoraji Town Sdn’s Fault center. A fatal accident occurred to Cow of Shree Sidik Jusabbhai Matwa at Saraf Bajar, Dhoraji. From investigation at site it is found that the old service wire from Junction Box mounted on wall to consumer is damage and contact with GI wire which is hanging through wall, same wall is contact with BSNL round iron pole. Cow came in contact with BSNL pole and got electrocuted. Report yet not received N.A N.A REPLACEMENT OF DAMAGED SERVICE BY SUB DIVISION OFFCIE ON DT 25.07.16 17
24 RRC GONDAL                    MAHENDRABHAI BHANUBHAI NAGDIKIYA 13-7-2016 FHO It is came to know from Gondal police station that electrical fatal accident occured at Vora Kotda road, Panch Pirni dhar, Hudco Quarter No 102, Gondal the said victim, As per site verifcation, It is found that owner of house Shri Bhanubhai Bhikahbhai Nagdikiya has recently illegally constructed roof and sufficient clearance is not maintained between line and construction. Victim was talking on cell phone and accidently came in contact with 11 KV vijaynagar line and got electrocuted. Hence it is clear negligence on part of victim and owner of House. FIR against owner of house shall be lodged. Report yet not received N.A N.A LINE SHIFTED AT SAFE DISTANCE AT APPLICANT COST. WORK COMPLETED ON DT 18.07.16 .Rs 40000/00 paid and work carried out  under ND scheme 18
25 RRC MAHIKA                    DEVRAJBHAI CHHAGANBHAI JESANI 20-7-2016 FHO This Accident was occurred on date the 20.07.2016 at Mahika village in Pithad aai Society and information regarding this accident received on date.21.07.2016. from Gujarat Samachar news paper. As per site situation 11 kv line passes near the shop and victim was touched with 11 kv live line and this accident was occurred. During site visit construction of this shop was found illegally and also roof of this shop extended illegally on road side under 11 kv line. Further detail investigation under process. Report yet not received N.A N.A SDO HAS WROTE LETTER TO POLICE STATION REAGRDING ILLEGAL CONSTRUCTION VIDE:- TSD/EST/5586/28.07.16 19
26 RRC CHHATRASA                    A COW OF SHRI SAILENDRASINH VANRAJSINH SARVAIYA 28-7-2016 FA As per inform to Deputy Engineer Dhoraji Rural Sdn on dt 28.07.16 18:00pm by cow owner. A fatal accident occurred to Cow of Shree Sailendrasinh Vanrajsinh Sarvaiya at Chhatrasa under  Dhoraji Rural Sdn. From the site investigation it is found that wet soil at PSC pole of Sahkari Mandali walu village transformer center (DT12) due to rainy atmosphere. There is complete earthing at PSC pole so no leakage current is found.  One cow got electroculated any how and died near the LT line PSC pole. IT is also assume that death of cow may be happen due to shock of lightning stoke, detail report follows.
 This is for your kind information please.
ACCIDENT OCCURRED DUE TO POOR EFFECTIV EARTHING. N.A N.A Accident Might be Occurred Due To Lightning Stroke. 20
27 RRC GOMTA                           A BUFFALO OF SHRI AMRABHAI KALABHAI CHAVADIYA 21-6-2016 FA Heavy wind and rain was fallen on 21.06.2016 at/ near Gomta Village, at that time, there were herd of buffalo passing near hanuman temple where one LT pole is there. One of the phase wire of said LT line was release from LT shackle and lying on LT cross arm. Due to that the leakage current was passing through earthing GI wire, at the same time buffalo came in contact with the GI wire and got electric shocked and died. Report yet not received N.A N.A NECESSARY DEPARTMENTAL RESTRINGING & REBINDING WORK CARRIED OUT. 21
28 RRC CHIHALIYA                       A BUFFALO OF SHRI MUSABHAI KASAMBHAI NAREJA 1-8-2016 FA An information of fetal animal (Buffalo) received to Junior Engineer Dhoraji Rural Sdn on Dt. 01.08.16 time 05:00 PM by village. A fatal accident occurred to buffalo of shree Musabhai Kasambhai Nareja at village Chikhaliya under Dhoraji Rural Sdn from the site investigation it is found that wet soil near transformer centre due to heavy rain on dtd. 01.08.16 and leakage current is flow in transformer’s earthing wire at accident place. One buffalo was passing near that transformer centre and came in contact with earthing wire and buffalo electrocuted and died.  
 This is for your kind information please.
Report yet not received N.A N.A Earthing reactivation done 22
29 RRC AMBARDINESS
(BHYAVADAR)                    A BUFFALO OF SHRI PARBATBHAI GOGANBHAI KHAMBHALA
4-8-2016 FA Owner of buffalo has informed to Bhayavadar S/dn office regarding fetal of animal (buffalo) on dt 04.08.16. A fatal accident occurred to buffalo of Shree Parbatbhai Goganbhai Khambhala at  village Bhayavadar (Ambardinesh)under  Bhayavadar Sdn. From the site investigation it is found that  five number of PSC pole of 11kv Padavala ( AG) feeder is broken near pond of Bhayavadar (Ambardinesh)village due to heavy rain on dt 04.08.16 and 11kv Padavala (AG) feeder was triped on dt 04.08.16 time 17:55pm. At that time One Buffalo was passing near damage 11kv line and came in contact with conductor between pole no BHY/PAD/103 and BHY/PAD/104 and buffalo electroculated and died.
 This is for your kind information please.
Report yet not received N.A N.A DAMAGE POLES ERECTED 23
30 RRC MANDLIKPUR                    SHRI DHANSUKH GANDALAL BHDALIYA 8-8-2016 NFHD This accident occurred at 66kv Mandlikpur Ss compound in 11kv Fareni AG feeder on dt 08.08.16 under Dhoraji Rural Sdn. From the site investigation it is found that Victim knows that 11kv Bateshwar AG feeder was in PF from dt 08.08.16 time 4:00am due to cable fault at panel. So Victim took LC of 11kv Bateshwar AG feeder Vide LC No 6774 Dt 08.08.16 time 9:00am by SMS for Jumpering work. Victim has carried out Jumpering work in 11kv Bateshwar AG feeder and he came to 66kv Mandlikpur Ss at time 9:50am for remove of cable jumper at first DP of 11kv Bateshwar feeder. But by mistake victim climbed on DP of 11kv Fareni AG feeder. So Victim fall down from DP but in 11kv Fareni AG feeder have not any tripping in 66kv Madlikpur Ss  around time 10:05am. So Nonfatal injury occurred to Victim’s spinal and he admit to Jetpur Govt. Hospital for primary treatment and then admit to the Sterling Hospital at Rajkot.   
 This is for your kind information please.
VICTIM HIMSELF IS REPONSIBLE FOR SAID ACCIDENT. N.A N.A Daily In morning at time of work distribution all line staff taking safety oath and JE , DE give instruction to line staff to use safety gadget compulsory and carryout work in proper manner. 24
31 RRC JETPUR                         A BUFFALO OF SHRI RAYDEBHAI DEVANANADBHAI NAKRANI 9-8-2016 FA :       An electrical animal fatal accident occurred to buffalo of shri Raydebhai  Devanand bhai nakrani at jetpur, Nr. Bhadarkanthavistar Khirasara road . It happened when buffalo came in contact with live Lt line wire which was fell down on land due to broken snapping of conductor. Report yet not received N.A N.A Necessary instruction has been given to SDO to erect new pole between all long distance (Span /locations) under their jurisdiction to avoid such type of accident in future, & timely Maintenance of all feeders. 25
32 RRC UPLETA                          A BUFFALO OF SHRI PUNJA VIRA SHAMLA 29-8-2016 FA Complain No 107783 Dt 29.08.16 was registered  to Upleta Town S/dn office’s fault center regarding fetal of animal (buffalo) on dt 29.08.16. A fatal accident occurred to buffalo of Shree Punja Vira Shamla at  village Upleta under  Upleta Town Sdn. From the site investigation it is found that  Private fencing barbed wire bind with PSC pole of DT 18. Due to heavy rain, Soil is wet near transformer center of Mahalaxmi Plastic Valu TC (DT18), Vadala Road Upleta. The Buffalo was grazing the grass near the said TC. Due to leakage current in GI wire of earthing of said transformer, private fencing barbed wire was also live and buffalo came in contact with live private fencing wire and buffalo electroculated and died.
 This is for your kind information please.
Report yet not received N.A N.A Earthing reactivation done 26
33 RRC BEDLA                             A COW OF SHRI VALUBHAI HAKABHAI SATIYA 1-9-2016 FA As Per Eye witness statement( Cow owner)  when cow was grazing Near brocken LT wire That time cow was came in contact with Live LT wire and got electric shocked and this accident was occurred Report yet not received N.A N.A Necessary instruction has been given to SDO to erect new pole between all long distance (Span /locations) under their jurisdiction to avoid such type of accident in future, & timely Maintenance of all feeders. 27
34 RRC ADHYA                        SHRI RAJESHKUMAR LIMBABHAI SARVAIYA 3-9-2016 NFHD As Per The Statement of eye Witness Sh maheshbhia jivrajbhai dobariya ,  Sh R L SarvaiyaBhai Come To his Ag Land To  Attend LT  Power Complaint Of Conn No-34859/05000/0 ,He Went to direct TC Centre & Only Cut Off D O Fuse than climbed on the TC And Repair The TC  Ckt Cable .After That he Climbed On LT  pole and Found that Span is Loose, so he tried to pull LT Conductor For Stringing but as he pull the conductor, the conductor touched 11 KV Line Passes over the LT Line & got Electric Shocked ,and  as his both legs were crossed lock in LT Wire he faint on lt pole with head down to earth
 During primary investigation it is found that he had only cut off DO Fuse , no 11 KV LC Permit Taken From S/S ,Also No Local Earthing Line Short Done By Him ,also while working on lt pole he didn’t use the safety helmet as well as safety hand gloves , He had made complete violation of safety rules 
                                                                                                                 
Report yet not received N.A N.A Necessary instruction has been given to SDO to erect new pole between all long distance (Span /locations) under their jurisdiction to avoid such type of accident in future, & timely Maintenance of all feeders. 28
35 RRC RAMALIYA                    A BUFFALO OF SHRI POLABHAI KARSHANBHAI GHANGHAL 13-9-2016 FA As per Eye witness & owner statement, he is moving to his Ag farm with 5 cattle’s (i.e. 4 buffalos & 1 cow) at today morning aprr.7:45am. While moving to Ag land gada Marg from main road, the 1st buffalo moving ahead touched the11Kv Brocken wire hanging on tree & in which return power is flowing in it and got electric shocked and this fatal animal accident took place. Site visit his done by DE Sardhar, necessary Rojkam, Photography made on site. Report yet not received N.A N.A Deteriorated conductor replaced 29
36 RRC PADASAN                    NAGJIBHAI AMBABHAI VAGHASIYA 13-9-2016 FHO This accident was occurred on the date 13.09.2016. This accident occurred due to victim was came in contact with Brocken LT Wire but during site visited, DE Tramba has not convincing about this accident matter.  Further investigation is under process.  Report yet not received N.A N.A This accident is suspected and detail investigation is under process 30
37 RRC JAMVADI                        A BUFFALO OF SHRI NAKABHAI VAGHABHAI MNAKARANI 18-9-2016 FA Due to heavy rain and wind pressure on dtd 18.09.2016 at early morning conductor was broken at shackle point at Pole no JAM/TOR/065 at load side. The owner Shri Nakabhai Vaghabhai Nakarani was taking 20-25 buffalos for grazing. On the way, the buffalo come in contact with broken conductor of 11 kv Torranto JGY feeder and electrocuted. While inquire in 66 KV Jamwadi S/S the tripping was not observed after snapping of said conductor. Detail investigation is under process.

Report yet not received N.A N.A Necessary instruction has been given to SDO to erect new pole between all long distance (Span /locations) under their jurisdiction to avoid such type of accident in future, & timely Maintenance of all feeders. 31
38 RRC SARDHAR                    RAMESHBHAI LALJIBHAI DHANKECHA 30-8-2016 FHO The accident was informed by Sh.Dineshbhai at Sardhar fault office on dt:30.8.16. Also Press note published in local newspaper on dt:1.9.16. As per site visit, there is NO EYE WITNESS of this accident. As per statements, the victim was climbed on Tree situated in his Ag land to cut the tree branches which likely to touch 11KV line passing nearby it. In doing so, the cute tree branch touched the 11Kv line & got electric shock & fallen down from the tree. The press note published on local newspaper Dt: 1.9.16 in which the actual cause of death is not declared. So, actual cause of death could not find out at the time of accident & same matter was conveyed to EE, Jasdan, SE RRC & Elcect. Inspector by this office vide letter no: SDO/Sardhar/Accident/Confi/6013 Dt: 01.09.2016
• Remark :- The P.M. Note is received on dt:19.9.16 & as per the P.M. Note Victim got electric shock & died.
Report yet not received N.A N.A Necessary instruction has been given to SDO to erect new pole between all long distance (Span /locations) under their jurisdiction to avoid such type of accident in future, & timely Maintenance of all feeders. 32
39 RRC SATADA AG                    PRAVINBHAI LALABHAI DHOL 24-9-2016 NFHO As per investigation report by SDO Kuvadava, labors of Contractor was working for new SPA connection of Smt. Labhuben Devabhai Meghani at village: Satda Ta. & Dis. Rajkot on dtd. 24.09.201,6 time 15:00 hours approx. During stringing work of said SPA connection work victim Shri Pravinbhai Lalbhai Dhol was working on PSC pole No. GP 22 Dt. 15.06.2016. While during carried out stringing work, the PSC pole was broken from bottom victim and PSC pole both are fall down on the land and victim got mechanical injuries. lmmediately victim has referred at Government Hospital Rajkot for further treatment. Report yet not received N.A N.A This accdident done naturally but safety equipments used while doing work. 33
40 MRB 1 Buffalo of Gobarbhai Limbabhai Bambhava 22.04.2016 FA Due to wind ‘D’ clamp’s nut bolt broke or loosened, which led “V cross Arm” to tilt. One of the dog conductors of this tilted “V cross Arm” detached or broke loose off pin binding. The detached dog conductor then freely hung thereby reducing vertical clearance to about 4FT as average span length being about 60 to 70mtr. The victim animals passing below or near to this dog conductor came in contact & electrocuted.  Report yet not received NA NA "V cross arm replaced & DOG condutor rebound properly 1
41 MRB 1 Buffalo of Gobarbhai Limbabhai Bambhava 22.04.2016 FA Due to wind ‘D’ clamp’s nut bolt broke or loosened, which led “V cross Arm” to tilt. One of the dog conductors of this tilted “V cross Arm” detached or broke loose off pin binding. The detached dog conductor then freely hung thereby reducing vertical clearance to about 4FT as average span length being about 60 to 70mtr. The victim animals passing below or near to this dog conductor came in contact & electrocuted.  Report yet not received NA NA "V cross arm replaced & DOG condutor rebound properly 2
42 MRB 1 Buffalo of Gobarbhai Limbabhai Bambhava 22.04.2016 FA Due to wind ‘D’ clamp’s nut bolt broke or loosened, which led “V cross Arm” to tilt. One of the dog conductors of this tilted “V cross Arm” detached or broke loose off pin binding. The detached dog conductor then freely hung thereby reducing vertical clearance to about 4FT as average span length being about 60 to 70mtr. The victim animals passing below or near to this dog conductor came in contact & electrocuted.  Report yet not received NA NA "V cross arm replaced & DOG condutor rebound properly 3
43 MRB 1 CALF of Gobarbhai Limbabhai Bambhava 22.04.2016 FA Due to wind ‘D’ clamp’s nut bolt broke or loosened, which led “V cross Arm” to tilt. One of the dog conductors of this tilted “V cross Arm” detached or broke loose off pin binding. The detached dog conductor then freely hung thereby reducing vertical clearance to about 4FT as average span length being about 60 to 70mtr. The victim animals passing below or near to this dog conductor came in contact & electrocuted.  Report yet not received NA NA "V cross arm replaced & DOG condutor rebound properly 4
44 MRB Robin Babubhai Zala 11.06.2016 FHO A fatal accident occurred during cleaning muthoot finance hoarding board hang on outside wall of extended passage of first floor. Such board when clean by victim with the help of iron stick spunch cleaner at that time iron stick was accidently touched with live part of do fuse of nearby transformer centre and victim came in contact with leakage current and immediately victim was fall down on ground floor and met with an electrical and mechanical accident. Report yet not received NA NA By providing new fabricated angle on Transformer Centre now  horizontal clearance is 1.58 mtr AND also Accident awareness to village people and school students regarding safety awareness during field visit 5
45 MRB Rajubhai Labhubhai Langoja 17.06.2016 FHO The victim was dismantling 26ft long & 2ft wide iron frame hoarding at Ganesh TVS showroom, due to heavy wind flow the same hoarding goes unbalance & accidently came in contact with 11kv highway urban feeder which is passing nearby showroom and its horizontal clearance from the hoarding wall is 1.7mtr which is stipulated as per safety regulation.  Report yet not received NA NA Accident awareness to village people and school students regarding safety awareness during field visit AND alsosafety pamphlets distributed in all s.dn area 6
46 MRB Surendra Prembhai Darbar 18.06.2016 NFHO During starting of drilling of bore well when bore well vehicle mounting rod tilting by hydraulic key operated, one victim & another victim fixing drilling rod in mounting so when such mounting was came in contact with 11 kv live conductor than victim was came in contact with leakage current and met with an electrical accident. During such tilting mounting rod activity vehicle already stand beside 11kv line. Distance between ground and 11 kv line is 6.9mtr approx.   Report yet not received NA NA Accident awareness to village people and school students regarding safety awareness during field visit AND alsosafety pamphlets distributed in all s.dn area 7
47 MRB Sunil Biharbhai Darbar 18.06.2016 NFHO During starting of drilling of bore well when bore well vehicle mounting rod tilting by hydraulic key operated, one victim & another victim fixing drilling rod in mounting so when such mounting was came in contact with 11 kv live conductor than victim was came in contact with leakage current and met with an electrical accident. During such tilting mounting rod activity vehicle already stand beside 11kv line. Distance between ground and 11 kv line is 6.9mtr approx.   Report yet not received NA NA Accident awareness to village people and school students regarding safety awareness during field visit AND alsosafety pamphlets distributed in all s.dn area 8
48 MRB Sh. Khetabhai Mohanbhai Jambukiya 23.06.2016 FHO Unauthorisely the Victim was Binding the Jumper of 11 KV Bhaghvati AG Feeder.  He was climbing on PSC Pole with Approx. 1 Meter Aluminum wire and he was contact with  11 KV Jumper of Bhaghvati AG Fdr and Met with Fatal Accident. However, detailed investigation will soon follows. Report yet not received NA NA Accident awareness to village people and school students regarding safety awareness during field visit 9
49 MRB Sh. Satyamsinh Virpalsinh Thakur 25.06.2016 FHO Victim sitting on loaded truck & passing under 11 KV City-2 Feeder on soil filled road, Suddenly any how victim came in induction zone of 11 KV Line & met with accident. No tripping occurred in City-2 feeder & ground clearance is 16 feet & approx. truck height is 12.4 ft.  However, detailed investigation & analysis will soon follow. Report yet not received NA NA Accident awareness to village people and school students regarding safety awareness during field visit AND alsosafety pamphlets distributed in all s.dn area 10
50 MRB 1 Cow of Vela Bhai Butabhai Bharvad 14.07.2016 FA The victim Cow was passing by transformer center bearing leakage current into earthed terminal & around this transformer center the water was logged. The step potential thus created led to the fatal accident to the victim Cow. However, detail investigation will soon follows. This Transformer DP maintenance was carried out as on DT: 12.4.16 by erect New DP Structure due to old Transformer DP. Report yet not received NA NA This Transformer DP maintenance was carried out a by erect New DP Structure due to old Transformer DP. 11
51 MRB 1 Buffalo of Rameshbhai Mohanbhai 06.08.2016 FA From the LT line a service cable (droper) joint with service line of consumer through junction box. Live phase of this service cable joint accidently touch with metallic fabricated part of respective LT pole. Hence, leakage current passed through wetland around this LT pole. At that time Victim Buffalo passing near this LT pole, step potential created & victim buffalo electrocuted & met with fatal accident. Report yet not received NA NA A new service cable and new earthing provided at accident location 12
52 MRB 1 Buffalo oF Jivrajbhai Nanjibhai Surela 10.08.2016 FA At transformer center, coated conductor is utilized as a service cable, which is found deteriorated & passing through Pole hole, during rain the same is touched to Earthling wire  & leakage current passed through it.  At the same time buffalo passing near transformer center & attract towards transformer Centre due to step voltage and met with this fatal accident.  Report yet not received NA NA A new service cable of transformer and new earthing of transformer center provided 13
53 MRB Sh.Veljibhai Manubhai Solanki 19.09.2016 FHO      Victim was unauthorisely climb on DP structure of 11 KV gang switch for looking his cow. While victim was trying to see his cow, victim accidently touched with live part of 11 KV gang switch & came in contact with leakage current which is resultant into this fatal human accident. Report yet not received NA NA Accident awareness to village people and school students regarding safety awareness during field visit AND alsosafety pamphlets distributed in all s.dn area 14
54 PBR KESHOD- SHRI HARIBHAI MEGHABHAI JADAV 03.05.16 NFHO ACCIDENT OCCURED DUE TO VICTIM IS LABOUR OF CONSTRUCTION WORK OF NEW HOUSE. VICTIM WAS SPRINKLING WATER ON WALL FOR PROPOSED CONSTRUCTION WORK BY STANDING ON STAIRS. DURING WATER SPRINKLING ON NEW CONSTRUCTED WALL, SPRINKLING WATER CAME IN CONTACT WITH LIVE 11KV LINE. DUE TO THAT PVC PIPE BY WHICH VICTIM WAS SPRINKLING WATER WAS ELECTRODE AND VICTIM GOT ELECTRIC SHOCK AND FALL DOWN IN HOUSE. Report yet not received NA NA Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 1
55 PBR BOKHIRA AG AREA- ELEC.ASSI.  SHRI GIRISHBHAI LALJIBHAI BANAMIYA 04.05.16 NFHD As per preliminary investigation a non fatal Departmental (mechanical) accident of Shri Girishbhai Lalajibhai Bamaniya Electrical assistant. Under coastal s/Dn  accident occurred due to victim clamp on transformer centre at that time due to unbalanced he fall down and got mechanical injuries in back spine Further, Matter regarding cause of accident  is under investigation. Report yet not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line. 2
56 PBR BANTW-AKHODABHAI VALABHAI RATHOD 23.06.16 FHO LIVE LT LINE CONDUCTOR WAS SNAPPED ON VICTIM DURING PASSING STREET. VICTIM WAS CAME IN LIVE SANPPED CODUCTOR AND GOT ELECTROCUTED AT SITE.PRILIMINARY REASON OF SNAPPING OF CONDUCTOR IS 3-PH CABLE FAULT IN BSNL CON. IN HIS INTERNAL PRIMISES DAURING RAILFALL MATTER UNDER INVESTIGATION. Report yet not received NA NA ABC provided  3
57 PBR FATAL accident to -  ANIMAL  -  COW of CHANDUBHAI CHANABHAI MANGERA, at Village: PORBANDAR 25.06.16 FA As per site Investigation accident occurred due to 1 ph. Service wire fault, the fault current passed through girder pole, because of heavy rain hence water logging around the accident location, due to that Cow came in contact with fault current and electrocuted. Girder pole replaced by PSC Pole and reactivation of Pole earthing. Earthing reactivation done NA All earthing of poles are reactivated 4
58 PBR BALEJ -RAMNATH JETNATH DHARMNATHI 02.07.16 FHO On dated 02.07.2016 around at 05:30 AM, when victim Ramnath Jetnath Dharmnathi passing with bullock cart through the village road near Bhanasara area of Balej village , during this his Bullocks came in contact with Live conductor and also Nilgay was came in contact with this snapped conductor of 11kv Kadachh JGY feeder which snapped on ground and Feeder remain charged even though conductor snapped on ground also victim was contact with bullock and  electrocuted on the spot. SNAPPING OF CONDUCTORS-c) Due to short circuit Deteriorated conductor replaced NA Deteriorated conductor replaced 5
59 PBR FATAL accident to -  ANIMAL  -  BULLOCK of RAMNATH JETNATH DHARAMNATHI, at Village: BALEJ 02.07.16 FA On dated 02.07.2016 around at 05:30 AM, when victim Ramnath Jetnath Dharmnathi passing with bullock cart through the village road near Bhanasara area of Balej village , during this his Bullocks came in contact with Live conductor and also Nilgay was came in contact with this snapped conductor of 11kv Kadachh JGY feeder which snapped on ground and Feeder remain charged even though conductor snapped on ground also victim was contact with bullock and  electrocuted on the spot. SNAPPING OF CONDUCTORS-c) Due to short circuit Deteriorated conductor replaced NA Deteriorated conductor replaced 6
60 PBR FATAL accident to -  ANIMAL  -  BULLOCK of RAMNATH JETNATH DHARAMNATHI, at Village: BALEJ 02.07.16 FA On dated 02.07.2016 around at 05:30 AM, when victim Ramnath Jetnath Dharmnathi passing with bullock cart through the village road near Bhanasara area of Balej village , during this his Bullocks came in contact with Live conductor and also Nilgay was came in contact with this snapped conductor of 11kv Kadachh JGY feeder which snapped on ground and Feeder remain charged even though conductor snapped on ground also victim was contact with bullock and  electrocuted on the spot. SNAPPING OF CONDUCTORS-c) Due to short circuit Deteriorated conductor replaced NA Deteriorated conductor replaced 7
61 PBR FATAL accident to -  ANIMAL  -  BLUE BULL of NO OWNER, at Village: BALEJ 02.07.16 FA On dated 02.07.2016 around at 05:30 AM, when victim Ramnath Jetnath Dharmnathi passing with bullock cart through the village road near Bhanasara area of Balej village , during this his Bullocks came in contact with Live conductor and also Nilgay was came in contact with this snapped conductor of 11kv Kadachh JGY feeder which snapped on ground and Feeder remain charged even though conductor snapped on ground also victim was contact with bullock and  electrocuted on the spot. SNAPPING OF CONDUCTORS-c) Due to short circuit Deteriorated conductor replaced NA Deteriorated conductor replaced 8
62 PBR AGATRAI-JAYESH VINOD BHINDI(DIPARTMENTAL) 14.07.16 NFHD Preliminary Reason for the accident :-    The victim has taken hand trip and after that victim was rectifying the consumers fault on T.C. During this 66 KV SBO has charged the feeder and victim came in contact of induction zone of  11 kv jumper and got electric shock. Report yet not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line. 9
63 PBR RANIKPARA-   SHRI RANCHODBHAI SOMABHAI DABHI 24.08.16 FHO As per received information, the victim is mentally ill & early morning without informing anyone & without any reason, unauthorized manner climbed on transformer centre, in the process he came in contact with live part  of electricity, fall down from the transformer centre & met with non-fatal accident. This incident came in notice by telephone calls received from village at 12:30 dt 24-8-2016.Further investigation is in process.              Report yet not received NA NA Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly 10
64 PBR FATAL accident to -  ANIMAL  -  CAMEL OF SHANTIGIRI HAJARIGIRI MEGHNATHI, MADHAVPUR 10.09.16 FA On dated 10.09.2016 snapping of conductor of 11KV Gorsar JGY feeder occurred at Madhavpur. And snapped conductor touched the camel which was kept under this 11KV line by his owner near his hut and electrocute occurred. Further investigation is under progress. Report yet not received Deteriorated conductor replaced NA Deteriorated conductor replaced 11
65 PBR FATAL accident to -  ANIMAL  -  BULLOCK OF LAKHMAN KARSHAN BHATU, PASHWARI 25.09.16 FA      Due to pin insulator fault 11kv conductor snapped & bullock comes in contact with 11kv conductor and got electrocuted. Report yet not received Deteriorated conductor and pin insulator replaced NA Deteriorated conductor replaced 12
66 JMN Beraja-Shri Jalabhai Jethabhai Toyata 01.04.2016 FHO Victim was engaged with "dish cable" connection work on electric pole unauthorizly, came in contact with live conductor and got electric shock and died Report yet not received NA NA Safety sticker & safety pemphlets are distributed for public safety awareness 1
67 JMN Ghunada--Shri Vithalbhai Gordhanbhai Teraya 01.04.2016 FHO Victim was trying himself to put up/hang D.O. or to do any other work on TC structure and came in contact with live parts and may be electrocuted and died Report yet not received NA NA Safety sticker & safety pemphlets are distributed for public safety awareness 2
68 JMN Khilosh-Shri. Kamlesh Mukambhai Servani 24.04.2016 FHO Victim was climbed on electric pole anyhow and falldown on getting electric Report yet not received NA NA Safety sticker & safety pemphlets are distributed for public safety awareness 3
69 JMN Rupamora-Shri Ramabhai Raydebhai 26.04.2016 FHO Victim got electric shock, due to leakage current pass through transformer structure earthing. However there is no evidence of sparking spot on earthing wire. At the time of visit leakage current not found on that earth site after charging of 11KV Rupamora AG feeder.Hence, this accident is Suspected Report yet not received NA NA Earthing Reactiveted 4
70 JMN Panchvati Sikka-Mohmad Rajula Ansari 28.04.2016 NFHO Victim was trying to cover PVC sleeve pipe to 11KV conductor line is passing nearby building havig nearby 4.5-feet horizontal distance from building to 11KV line. During that work he has not taken permission from PGVCL and done this work himself. At that time he came in contact with 11KV line and got electric shock Report yet not received NA NA Safety sticker & safety pemphlets are distributed for public awareness 5
71 JMN Varvala--Merbai Kasam Sama 01.05.2016 FHO Victim was passing between double pole structure at that time 11KV Disc fault occur and leakage current passing through GI earth wire and victim came in contact in leg. Report yet not received NA NA Earthing Reactiveted 6
72 JMN Kalyanpur-Shuklabha Gagubha Manek 05.05.2016 FHO Victim was climbing on "Ambali" tree and picking "Ambali" from tree by iron rod or other means. 11KV Nageshwar JGY passed from that place and somehow he touches the live line and got shocked Report yet not received NA NA Village meeting carried out time to time 7
73 JMN Dhrol-Shri.Karabhai Kumbhabhai Lambariya 17.06.2016 FA Due to snapping of conductor 11kv Hadmatiya feeder on the tie up bullocks(2 nos) & got electric shock and died. Report yet not received NA NA Conductor rebinded and maintenance carried out 8
74 JMN Dhrol-Bullock of Shri.Karabhai Kumbhabhai Lambariya 17.06.2016 FA Due to snapping of conductor 11kv Hadmatiya feeder on the tie up bullocks(2 nos) & got electric shock and died. Report yet not received NA NA Conductor rebinded and maintenance carried out 9
75 JMN Jamnagar- Goat of Shardaben Pravinbhai Koli 20.06.2016 FA Due to heavy wind & seasonal first rain live phase of 4mm2 cable rubbed to LT girder pole and open phase of said cable touched the wet girder pole,A tubbler iron pole support that girder pole and return leakage current comes in this iron pole support pole from the 4mm2 cable, agoat passing near this wet support pole  and goat got shock and cause to death Report yet not received NA NA Maintenance work is carried out 10
76 JMN Keshiya--Mukeshbhai Chanabhai Tadvi 22.06.2016 FHO As per information received from police department regarding the Fatal Human Electrical accident was occurred as per PM report. Accordingly, the DE. Jodiya has visited the site,there is a no any evidence regarding Electrical accident in Network, also there is a no tripping on 11 KV Keshiya AG feeder. Report yet not received NA NA New jumper work and new TC earthig work carried out 11
77 JMN Green city area-Cow No owner 29.06.2016 FA Due to heavy wind pressure a guard wire of HT pole fall down on streetlight phase wire which was under HT line, a leakage current pass through HT girdaer pole from the guard wire and HT line shorted. The area was wet the cow wass passing nearby got electrocuted. Report yet not received NA NA Earthing Reactiveted 12
78 JMN Surajkaradi-Cow of Shri Dhanabha Samatbha Manek 01.07.2016 FA Service wire insulation got short with telephone pole and due to rainy season leackage current on wet land came and cow came in contact with leackage current and got shocked and died Report yet not received NA NA DAMAGED SERVICE WIRE REPLACE WITH NEW SERVICE 13
79 JMN Falla-Buffalo of shri Tidabhai Bijalbhai Bambhava 10.07.2016 FA While buffalo was grazzing near about AG TC, Due to leakage current passed through TC earthing, it got electric shock and died Report yet not received NA NA Earthing Reactiveted 14
80 JMN Dwarka-Anilbha Verashibha Manek 11.07.2016 FHO At the site building construction work was going on, victim pulling iron rod from ground to 2nd floor of building, while pulling the iron rod which is approx 18-feet length accidently touched to 11kv Dwarka Urban feeder line wire passing nearby building & got electric shock and died & feeder was also tripped Report yet not received NA NA Safety awareness meetings are carried out time to time 15
81 JMN Okha-Bharatbhai Muljibhai Panjari 19.07.2016 NFHD Victim was climbing to LT pole to attain complain at that time he sliped from third step of pole and fall down to groung Report yet not received NA NA The safety awareness oath every morning to line staff were taken and the periodically safety meetings are arranged 16
82 JMN Miyatra-Buffalo of Lakhman Pola Chuchar 19.07.2016 FA In wet outfield of transformer center due to rain, earth leackage current was flowing through earth wire. Buffalo passing through nearby T/C get in contact of earth wire of T/C and got electrocuted Report yet not received NA NA Earthing Reactiveted 17
83 JMN Jamnagar-Goat of Shri Bodu Abdul Popar 28.07.2016 FA One sevice wire with open joint of has a phase and neutral, There was 2-feet service wire was connected and this service wire phase touch to GI wire of service wire which binded with that telephone pole where accident occurred. Two goat passed near the pole and shocked. At that time rain was falling and land near that pole is wet Report yet not received NA NA Service wire changed 18
84 JMN Jamnagar-Goat of Shri Bodu Abdul Popar 28.07.2016 FA One sevice wire with open joint of has a phase and neutral, There was 2-feet service wire was connected and this service wire phase touch to GI wire of service wire which binded with that telephone pole where accident occurred. Two goat passed near the pole and shocked. At that time rain was falling and land near that pole is wet Report yet not received NA NA Service wire changed 19
85 JMN Bhanvad-Cow of Shri Rajeshbhai Dayabhai Sagathiya 29.07.2016 FA A cow wandering near transformer centre for eating grass at that time its mouth moving up and accidently touch nearby live LT section cutout fuse wire and cow got eletrocuted Report yet not received NA NA Section fuse in LT Line was removed permenantly.and public awreness for safety purpose arrange in local city area . 20
86 JMN Bhinda-Rajendrasinh Mahendrasinh Gohel 30.07.2016 NFHD Victim was binding DO fuse after jointing a LT line conductor on transformer center of 11KV Manza ag feeder. When he was binding DO fuse of Y-phase he got electric shock as Line clear is taken of 11KV Bhinda AG feeder instead of 11KV Manza AG feeder by supervisor Lineman Shri. M.U.Shukla Report yet not received NA NA Time to time safety meeting arrange at sub division level and safety oath taken by line staff. 21
87 JMN Shishang-Cow of Shri Mangalsinh Lakhubha Jadeja 30.07.2016 FA Cow passing nearTC, due to leackage current passing through earthing and due to rain wet soil cow got electric shock Report yet not received NA NA Earthing Reactiveted 22
88 JMN Bakodi-Karnabhai Fogabhai Gojiya         Date of death:10/08/2016 27.07.2016 FHO As per press note in news paper on dated:11/08/2016 accident occurred at bakodi agriculture area, Site visit taken on Date:11/08/2016 as per eye witness statement the victim was farming in his farm on dated:27/07/2016 near pin pole of 11-kv bakodi ag feeder. He was got electric shock from unknown source and fall down but he was conciousstate and the victim was hospitlize on the same day and then victim health was normal no any pain or injury so he was release on dtd:28/07/2016. Then again he was admitted on dtd:31/07/2016 and the victim died on dtd:10/08/2016 the reason of electric shock is suspected Report yet not received NA NA LT line maintenance carried out 23
89 JMN Kanchanpur-Vinubhai Alabhai Vaniya 02.08.2016 NFHD A Non-fatal human departmental electrical accident occurred in network to shri Vinodbhai Alabhai Vaniya, EA while victim was climbed to attain the jumper fault after taking LCP of Dharmpur AG feeder by ALM G K Parmar and three phase shorted and earth the line, while attaining the jumper fault try was taken in the Kanchanpur JGY feeder, due to that return power came in Dharmpur AG feeder and some leakage voltage passes through earthed chain and he got minor induction voltage and he fall down. As per investigation it is concluded that cable of Shaktinagar AG feeder is running parallel with Dharmpur AG feeder and the wire of 11-kv Shaktinagar feeder touch on Kanchanpur JGY feeder near Vidhana vadi vistar this is the reason for return power Report yet not received NA NA The safety awareness oath every morning to line staff were taken and the periodically safety meetings are arranged 24
90 JMN Sarmat-Buffalo of shri Gopal Lakha Thunga 04.08.2016 FA The fatal electrical accident to animal was occurred due to the buffalo rubbing with LT ckt pole of transformer center, LT line AB cable joint touch with the earth wire of PSC pole hence leakage current pass through earth wire front right leg came in contact with earth wire hence it got shock Report yet not received NA NA Earthing Reactiveted 25
91 JMN Okha-Cow of shri Sadurbha Ghogubha Jagatiya 05.08.2016 FA LT line live phase conductor came in contact with wet PSC pole cause off heavy rain & wind. Leakage current pass from LT line phase conductor to wet PSC pole to ground and cow came in contact with leakage current and died Report yet not received NA NA Earthing Reactiveted 26
92 JMN Okha-Cow of shri Godad Kaya Chanpa 05.08.2016 FA LT line live phase conductor came in contact with wet PSC pole cause off heavy rain & wind. Leakage current pass from LT line phase conductor to wet PSC pole to ground and cow came in contact with leakage current and died Report yet not received NA NA Earthing Reactiveted 27
93 JMN Lakhabaval-Buffalo of shri Punshi Dhanabhai Hajani 06.08.2016 FA The fatal electrical accident to animal was occurred due to the LT line snapped from the pole during heavy rain and wind in agriculture area in farm with wired fencing the line snapped conductor touched to fence which caused the current leaked from the wire on to fence a buffalo came in contact of the fence and got electric shock. Report yet not received NA NA Conductor rebinded and maintenance carried out 28
94 JMN Chur-Buffalo of shri Vira Vejanand Kandoriya 06.08.2016 FA Buffalo was passing near 11-kv Golansheradi JGY feeder pole no:310, PSC pole fall down on it due to heavy rain and wind.buffalo came in contact with live 11-kv conductor and got electric shock Report yet not received NA NA Conductor rebinded and maintenance carried out 29
95 JMN Gundla-Buffalo of shri Govindbhai Samatbhai Chhataka 06.08.2016 FA LT conductor was snapped due to heavy wind and rain near river, buffaloes are drinking water at that time accidentally touched the live wire and got electric shock. Report yet not received NA NA Conductor rebinded and maintenance carried out 30
96 JMN Gundla-Buffalo of shri Govindbhai Samatbhai Chhataka 06.08.2016 FA LT conductor was snapped due to heavy wind and rain near river, buffaloes are drinking water at that time accidentally touched the live wire and got electric shock. Report yet not received NA NA Conductor rebinded and maintenance carried out 31
97 JMN Surajkaradi-cow of shri Dineshbhai Maldebhai Mavadiya 07.08.2016 FA LT line conductor snapped due to heavy rain and wind pressure and fall down on ground, at that time cow passing near that line conductor and came in contact with wire and got shock Report yet not received NA NA Conductor rebinded and maintenance carried out 32
98 JMN Dwarka-Cow Unknown 07.08.2016 FA Cow was passing near transformer center and came in contact with ormer earthing. The phase wire of streetlight connection contacted to transformer earthing wire and due to heavy raind and wind pressure, the ground is wet so the cow came contact with leakage current and got electric shock Report yet not received NA NA Earthing Reactiveted 33
99 JMN Dwarka-Cow Unknown 07.08.2016 FA Cow was passing near transformer center and came in contact with ormer earthing. The phase wire of streetlight connection contacted to transformer earthing wire and due to heavy raind and wind pressure, the ground is wet so the cow came contact with leakage current and got electric shock Report yet not received NA NA Earthing Reactiveted 34
100 JMN Surajkaradi-Bullock of Shri .Dhadhabha Bodabha Nayani  21.08.2016 FA As per eye-witness statement due to leakage current passes through LT PSC pole to ground and bullocks are came in contact with leakage current and got electic shock. At the time of site visit there is no path for leakage current at LT PSC pole & pole was not wet as much as leakage current passes through, hence reason for accident is suspected actual reason for accident may find out after PM. report Report yet not received NA NA Maintenance work is carried out 35
101 JMN Surajkaradi-Bullock of Shri .Palabha Babubha Sumaniya 21.08.2016 FA As per eye-witness statement due to leakage current passes through LT PSC pole to ground and bullocks are came in contact with leakage current and got electic shock. At the time of site visit there is no path for leakage current at LT PSC pole & pole was not wet as much as leakage current passes through, hence reason for accident is suspected actual reason for accident may find out after PM. report Report yet not received NA NA Maintenance work is carried out 36
102 JMN Sanosari-Buffalo of shri. Punabhai Fogabhai Godham 22.08.2016 FA As per eye-witness statement coated conductor of 11-kv Kabarka JGY feeder "Y" phase snapping through AG/JGY (Sanosari AG upper and Kabarka JGY lower) at that time buffalo grazzing under the said JGY feeder line and snapped conductor was fallen on she buffalo and got electric shock. No any tripping noted in 66-kv Sanosari S/S in both the feeders at that time. The accident is suspected Report yet not received NA NA Maintenance work is carried out 37
103 JMN Bed-Buffalo of shri Rama Pitha Hajani 23.08.2016 FA Buffalo passing below LT circuit of 11-kv vasai JGY feeder near IOC petrol pump transformer center, anothore buffalo rubbing its body with LT pole and due to heavy rubbing, LT line conductors was swinging and got entangled and due to twisting of conductors one live LT conductor fall down on another buffalo passing below it and that buffalo came in conatct with broken live LT wire and got electrocuted. Report yet not received NA NA Conductor rebinded and maintenance carried out 38
104 JMN Dhinchada-Buffalo of shri Ranabhai Tejabhai Aswar 29.08.2016 FA LT pole location no.11, open joint of private streetlight fixture was in direct contac with earth wire of PSC pole hence leakage current passes through earth wire, the rain water is collected in land area near buffalo came in contact with the water poo, and got electric shock Report yet not received NA NA Earthing Reactiveted and necessary maintenance work was carried out 39
105 JMN Shankar tekari-Cow No owner 30.08.2016 FA Due to heavy rain the insulation of the LT ABC of LT pole was broken at contact point of the angle and live phase touch to the angle of girder pole so the leakage current passed through the girder pole and become shorted, the area was watery and at that time the cow came in contact passing nearby the pole and touched to girder pole and got electric shock Report yet not received NA NA Maintenance work is carried out 40
106 JMN Bhandariya Ag area-Meraman Ramshi Nandaniya 01.09.2016 FHO victim having 1-phase AG-RL connection on name Meraman Ramshi Nandaniya, cons. no. 33012/00292/8 is existing on site, while victim was trying to bypass the meter with the help of 3-core patti cable from LT side fuse which is situated under the 10-KVA transformer. At that time accidentally touched the open terminal of 3-core patti cable and he got electric shock.  Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 41
107 JMN Dhun dhoraji-Kalawad-Kalawad w-Vipul Shankarbhai Parmar(Fatal) 03.09.2016 FHO Farmer has passing unauthorized electric current through fencing wire around his farm, accidentally victims came in contact and got electric shock and 1-fatal & 4-non-fatal human electrical accident occurred. Farmer has put electric shock in fencing wire hence farmer Ranchhodbhai Jerambhai Varani is responsible for this accident. Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 42
108 JMN Dhun dhoraji-Kalawad-Kalawad w-Anilbhai Shankarbhai Parmar(non-fatal)  03.09.2016 NFHO Farmer has passing unauthorized electric current through fencing wire around his farm, accidentally victims came in contact and got electric shock and 1-fatal & 4-non-fatal human electrical accident occurred. Farmer has put electric shock in fencing wire hence farmer Ranchhodbhai Jerambhai Varani is responsible for this accident. Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 43
109 JMN Dhun dhoraji-Kalawad-Kalawad w-Jayeshbhai Shankarbhai Parmar(non-fatal)  03.09.2016 NFHO Farmer has passing unauthorized electric current through fencing wire around his farm, accidentally victims came in contact and got electric shock and 1-fatal & 4-non-fatal human electrical accident occurred. Farmer has put electric shock in fencing wire hence farmer Ranchhodbhai Jerambhai Varani is responsible for this accident. Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 44
110 JMN Dhun dhoraji-Kalawad-Kalawad w-Akshaybhai Nagarsingbhai Parmar(non-fatal)  03.09.2016 NFHO Farmer has passing unauthorized electric current through fencing wire around his farm, accidentally victims came in contact and got electric shock and 1-fatal & 4-non-fatal human electrical accident occurred. Farmer has put electric shock in fencing wire hence farmer Ranchhodbhai Jerambhai Varani is responsible for this accident. Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 45
111 JMN Dhun dhoraji-Kalawad-Kalawad w-Sahilbhai Nagarsingbhai Parmar(non-fatal)  03.09.2016 NFHO Farmer has passing unauthorized electric current through fencing wire around his farm, accidentally victims came in contact and got electric shock and 1-fatal & 4-non-fatal human electrical accident occurred. Farmer has put electric shock in fencing wire hence farmer Ranchhodbhai Jerambhai Varani is responsible for this accident. Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 46
112 JMN Rinari-Buffalo of Surabhai Somrajbhai Malani 04.09.2016 FA A fatal animal electrical accident occurred in network to buffaloes due to snapping of conductor falls down on buffaloes passes under the 11-kv Line and came in contact and got electrocuted.  Report yet not received NA NA Conductor rebinded and maintenance carried out 47
113 JMN Rinari-Buffalo of Surabhai Somrajbhai Malani 04.09.2016 FA A fatal animal electrical accident occurred in network to buffaloes due to snapping of conductor falls down on buffaloes passes under the 11-kv Line and came in contact and got electrocuted.  Report yet not received NA NA Conductor rebinded and maintenance carried out 48
114 JMN Mota asota-Khambhaliya-Vadatra-Karubhai Khimabhai Joshi 09.08.2016 FHO Victim was tried to operate the G.O. switch of Zakasia AG feeder near Kathi vadi area by himself at that time any how leakage current passed at other end of G.O switch PVC cable and accidentaly he got electrocuted. Report yet not received NA NA Earthig reactivated and maintenance work carried out 49
115 JMN Dudava-Jamjodhpur-Jamjodhpur W-Premjibhai Bijalbhai Solanki 14.09.2016 FHO The victim was pull out the GI water pipe from water tank(due to negligence of victim pulled out water pipe) was touched to live 11-Kv Kotada AG feeder's conductor, hence he got electric shock and died Report yet not received NA NA Time to time safety awarness village meeting were aranged safety pemphlet distributed 50
116 JMN Hanumandhar-Buffalo of Hira Lakha Mori 22.09.2016 FA There was a rainy atmosphere, the buffalo was passing near the water works TC centre and the earthing wire of the TC centre was open, buffalo was came in contact with the earth wire and due to the buffalo was died Report yet not received NA NA Earthig reactivated and maintenance work carried out 51
117 JMN Mulvel-Sheep of Raymalbhai Virabhai Mori 27.09.2016 FA Due to flash over of pin insulator direct current passing from 11-kv PSC pole to ground  in 11-kv Padali AG feeder and live phase conductor came in conatct with V cross arm and current pasing through earth wire to ground. At that time sheep passing near to this  pole and came in contact with the current and got electric shock Report yet not received NA NA Earthig reactivated and maintenance work carried out 52
118 BHUJ KOTHARA, CAMEL (FEMALE) - OWNER: ALI HARUN JAT 18.4.16 FA A LT line old deteriorated conductor snap and fall down on ground of existing 63 KVA transformer of 11 KV Vanku Ag feeder. D.O. fuse not blown out. At that time, Camel (Female) passing through this site & direct contact with live conductor and fatal accident occurred. Report yet not received NA NA NECESSARY MAINT. WORK DONE. 1
119 BHUJ ANGIA NANA, SMT VANITA HIRJI BAMBHNIYA 29.4.16 FHO A truck was standing under 11 KV line on the farm road of the Angia Nana village simtal area. The victim was climbed up on the cabin (Top roof) of the truck for any work. Victim’s head touched with live conductor of 11 KV Bela Ag feeder and got electrocuted and died spot.   Report yet not received NA NA NECESSARY MAINT. WORK DONE. 2
120 BHUJ BHUJ, COW(JERSEY) OF SHRI SAMA SULEMAN OSMAN 6.5.16 FA STREET LIGHT FIXTURE DIRECTLY FIXED ON POLE AND CONNECTED BY TWIN WIRE DUE TO JOIINT OF FIXTURE WIRE IS OPEN AND INSULATION TAPE IS NOT WOUND ON IT . IT MAY CAME CONTACT OF GIRDER POLE AND A COW MAY COME IN CONTACT WITH POLE AND GOT ELECTOCUTED. Report yet not received NA NA NECESSARY MAINT. WORK DONE. 3
121 BHUJ  RATADIYA,BUFFELOW OF SHREE SHIVARAJ MALSHI GADHAVI 30.5.16 FA 11 KV LUNI AG HT CONDUCTOR BROKEN DOWN DUE TO TOP PIN BROKEN FROM PIN HARDWER & LIVE CONDUCTOR TOUCH WITH SIDE CROSS ARM & DUE TO RETURN KICK AND EARTH FAULT 11 KV LUNI AG B PHASE CONDUCTOR BROKEN DOWN  FROM SHACKLE POINT JUMPER AND 2 NOS OF BUFFELOW ACCIDENTLY TOUCHED THE LIVE CONDUCTOR & GOT ELECTRIC SHOCK AND DIED Report yet not received NA NA NECESSARY MAINT. WORK DONE. 4
122 BHUJ  RATADIYA,BUFFELOW OF SHREE SHIVARAJ MALSHI GADHAVI 30.5.16 FA 11 KV LUNI AG HT CONDUCTOR BROKEN DOWN DUE TO TOP PIN BROKEN FROM PIN HARDWER & LIVE CONDUCTOR TOUCH WITH SIDE CROSS ARM & DUE TO RETURN KICK AND EARTH FAULT 11 KV LUNI AG B PHASE CONDUCTOR BROKEN DOWN  FROM SHACKLE POINT JUMPER AND 2 NOS OF BUFFELOW ACCIDENTLY TOUCHED THE LIVE CONDUCTOR & GOT ELECTRIC SHOCK AND DIED Report yet not received NA NA NECESSARY MAINT. WORK DONE. 5
123 BHUJ NAKHTRANA,.BHARATBHAI B. KODIYATAR, EA(VS) 17.6.16 NFHD A victim Bhartbhai B.kodiyatar climbed on Lt line PSC pole in 11 kv nagalpar jgy feeder for attending consumer complaint of Gurukrupa enggineering . During removing of circuit cable from LT pole one terminal of cable momentarily came into contact with 11 kv nagalpar jgy line which is passing near to LT pole & victim got minor electric shock.. Report yet not received NA NA NECESSARY MAINT. WORK DONE. 6
124 BHUJ NAKHATRANA, RATANSHI ACHAR MEGHVAL 28.6.16 FHO The victim Shri Ratanshi Achar Meghwal was driving a tractor in the farm, While he was reversing tractor on the boundary of farm, back side top roof of tractor direct came with live conductor of 11 KV vyar AG feeder  and got electrocuted. The line was old, as per pole marking it was erected in year 90. The stay sets of tapping pole & Transfomer centre broken due to ageing and due to long span (75 meter), ground clearance of line at accident point became lower up to 7.2 foot Report yet not received NA NA Necessary instruction has been given to SDO to erect new pole between all long distance (Span /locations) under their jurisdiction to avoid such type of accident in future, & timely Maintenance of all feeders. 7
125 BHUJ VADAJAR ROAD , FH-Suresh Adhu Koli, 10.7.16 FHO Both victims were helping in installation of submersible motor in bore well of Kapilbhai’s farm. They were giving the iron rod of about 12 mtr length to the person installing the motor in the bore well. While doing so, they had taken an iron rod and rose it up from the ground, accidently the rod came in induction zone as they were working near and under the transformer center and they both get electric shock. As the victim Sureshbhai was near transformer center he was thrown away from the transformer center and victim Adhubhai was holding the iron rod touching his stomach, so he got electric shock and fell down unconscious on the ground.   Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 8
126 BHUJ VADAJAR ROAD , NFH-Adhu Adam Koli 10.7.16 NFHO Both victims were helping in installation of submersible motor in bore well of Kapilbhai’s farm. They were giving the iron rod of about 12 mtr length to the person installing the motor in the bore well. While doing so, they had taken an iron rod and rose it up from the ground, accidently the rod came in induction zone as they were working near and under the transformer center and they both get electric shock. As the victim Sureshbhai was near transformer center he was thrown away from the transformer center and victim Adhubhai was holding the iron rod touching his stomach, so he got electric shock and fell down unconscious on the ground.   Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 9
127 BHUJ FULAYVANDH, 1 NO  COW OF DESAR SULEMAN SUMARA 14.7.16 FA  The accident occurred at Transformer center of Fulayvandh village under kothara Sub division. Leakage current is continue and flowing through x’mer center earthling.  Due to rain and wet land, potential barrier build up on the surface of land near transformer center earthling.   The cow passing this surrounding area, got electric shock and died Report yet not received NA NA Earthing reactivation done 10
128 BHUJ BHUJ,1 NO  COW OF KUMBHAR ABDERAHEMAN  ISMAILBHAI 18.7.16 FA Street light fixture fixed on pole and the joint of the stree light was open which came into contact with earthing wire which makes the pole electrocuted. A cow may come in contact with pole and got electrocuted. Report yet not received NA NA NECESSARY MAINT. WORK DONE. 11
129 BHUJ PRAGPAR - AG AREA, 1 NO COW OF JAYENDRASINH MANGALSINH ZALA 2.8.16 FA 11 KV PATRI AG FEEDER SIDE CONDUCTOR SEPARATED FROM PIN INSULATOR & CAME IN CONTACT WITH POLE EARTHING WIRE,BUT 11 KV  LINE WAS NOT TRIPPED.HENCE LEACKAGE CURRENT PASS THROUGH EARTHING WIRE.COW CAME IN CONTACT WITH THIS EARTHING WIRE & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA Deteriorated conductor replaced 12
130 BHUJ  MUNDRA,COW OF Maheshbhai Kanjibhai Mali 5.8.16 FA Fatal accident occurs due to 11 kv line jumper fault from load side of 11 kc ab switch and jumper touched to iron angle and return power comes through GI wire , also due to rainy atmosphere wet  land, and 2 nos of cow was accidently touched with earthing gi wire and got electrocuted.  Report yet not received NA NA Earthing reactivation done 13
131 BHUJ  MUNDRA, COW OF Maheshbhai Kanjibhai Mali 5.8.16 FA Fatal accident occurs due to 11 kv line jumper fault from load side of 11 kc ab switch and jumper touched to iron angle and return power comes through GI wire , also due to rainy atmosphere wet  land, and 2 nos of cow was accidently touched with earthing gi wire and got electrocuted.  Report yet not received NA NA Earthing reactivation done 14
132 BHUJ MOTA KAPAYA, .COW OF Manubha Karasanji Pingol

6.8.16 FA During rainy atmosphere earth leakage current passes  through GI wire of x’mer center . One cow touched the Gi wire & felt electric shock. Other cow touched this cow & also felt electric shock & died. Report yet not received NA NA Earthing reactivation done 15
133 BHUJ  
MOTA KAPAYA,.COW OF Devji Parbat Maheshwari
6.8.16 FA During rainy atmosphere earth leakage current passes  through GI wire of x’mer center . One cow touched the Gi wire & felt electric shock. Other cow touched this cow & also felt electric shock & died. Report yet not received NA NA Earthing reactivation done 16
134 BHUJ KUNDRODI, 1 NO OF BUFFALO Viramji Gabhubha Jadeja  6.8.16 FA Fatal accident occurs due to heavy rain and logging nearer it psc pole also due to wet land leakage it current comes at bottom of it psc pole and due to foot step of buffalo got electric shock it leakage current and died. Report yet not received NA NA Earthing reactivation done 17
135 BHUJ Moti Khakhar,Near Vadi Vistar  Primary School , BUFFALO OF Rajesh Versi Maheshwari  8.8.16 FA During Rainy atmosphere Earth Leakage Current passes through GI Wire of X’Mer Center. Due to Rain Small Water  Pond Occurred near X’mer Center. Hence current
 Flow in this small pond. Two Buffalos came in
Contact with this water pond & Felt Electric Shock & Died.
Report yet not received NA NA Earthing reactivation done 18
136 BHUJ Moti Khakhar,Near Vadi Vistar  Primary School , BUFFALO OF Rajesh Versi Maheshwari  8.8.16 FA During Rainy atmosphere Earth Leakage Current passes through GI Wire of X’Mer Center. Due to Rain Small Water  Pond Occurred near X’mer Center. Hence current
 Flow in this small pond. Two Buffalos came in
Contact with this water pond & Felt Electric Shock & Died.
Report yet not received NA NA Earthing reactivation done 19
137 BHUJ BHADRESWAR,1 NO BULLOCK OF JADEJA BARATSINH JATUBHA 11.8.16 FA Fatal accident occur when one lt  wire broken from lt pole near village transformer at Bhadreswar and laying on earth and 1 bullock was passing from there  & accidently  touched the live lt wire  and got shocked and died. Report yet not received NA NA Deteriorated conductor replaced 20
138 BHUJ Dumara,1 no. FH -Rupsinh Parmar  27.8.16 FHO The accident occurred at Indian Oil Petrol pump site near at Village: Dumra . While erecting tubular steel pole for petrol pump internal lightning purpose at that time top side of pole touch with 11kv live line of Hajapar Ag feeder. The victim  :1 got electric shock and died and victim : 2  met with non-fatal electrical accident. The vertical ground clearance of line at accident location is 6.50 meter as per norms.
 The work was executed by petrol pump authority without taking any due care to keep safe distance from 11 kv line passing very nearby. The accident occurred due to criminal negligence by them.  More information there were total 06 persons working among 02 person got electric shock.
Report yet not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 21
139 BHUJ Dumara, 1 no NFH -Ankit  Arvind  Vasani                                                                27.8.16 NFHO The accident occurred at Indian Oil Petrol pump site near at Village: Dumra . While erecting tubular steel pole for petrol pump internal lightning purpose at that time top side of pole touch with 11kv live line of Hajapar Ag feeder. The victim  :1 got electric shock and died and victim : 2  met with non-fatal electrical accident. The vertical ground clearance of line at accident location is 6.50 meter as per norms.
 The work was executed by petrol pump authority without taking any due care to keep safe distance from 11 kv line passing very nearby. The accident occurred due to criminal negligence by them.  More information there were total 06 persons working among 02 person got electric shock.
Report yet not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 22
140 BHUJ New BOP Budhabandar  ,1 no she buffalo of Gendan Punjaji gadhavi 28.8.16 FA Accidently neutral leakage current flow through wet earth surface area during rainy season near transformer Centre and buffalo came in contact with this potential barrier and got electric current and died. Report yet not received NA NA Earthing reactivation done 23
141 BHUJ Gadani,1 no she buffalo of Velji mavji Chaudhary 31.8.16 FA Lt line conductor was broken and fall down on the land while buffalo passing near this broken conductor came with direct contact and got electric shock & died. Report yet not received NA NA Deteriorated conductor replaced 24
142 BHUJ SIRACHA,RAJESH RAMASIYA SHAH 3.9.16 FHO after parking the bulker no gj 18 ax0301 under 11 kv kandagara jgy line,victim climb on bulker for some work,while doing some work,he may came in induction zone & felt eletric shock & died. Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 25
143 BHUJ BHUJ,1 NO OF COW SUMRA GAFUR OSMAN 14.9.16 FA Lt conductor snapped due to many birds flied together on the lt line. The cow was standing under the lt line which got electocuted due to snapping of conductor and got to death Report yet not received NA NA Deteriorated conductor replaced 26
144 BHUJ PATRI,1 NO OF BULLOCK OF VANRAJSINH ZALUBHA JADEJA 16.9.16 FA between 11 kv top conductor & top clamp one squirrel stuck in, hence power passing thought 11 kv conductor to squirrel to top clamp to gi earthing wire of psc pole than one bullock came in contact with this  gi wire & felt electric shock and died. Report yet not received NA NA Earthing reactivation done 27
145 ANJ Varsana, Buffalo - OWNER: BHACHU MOTI KOLI 7.05.16 FA On dated 7.05.16 around hours shri popat bhachu koli went to grazing his buffalo behind ashok werehouse at village varsana. There is 11kv varsana ind feeder line passing near rough road side at the same time one buffalo went under 11kv line of varasana ind feeder and at the same time conductor of yph found broken due to high wind pressure and short ckt. buffalo came into contact with it and died.  Report yet not received NA NA Conductor of particular portion has been replaced.
Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly.
1
146 ANJ Sudana, Camel, Owner: Laxmiben Somabhai Rabari 9.05.16 FA Due to heavy wind pole bend and stringing of wire became loose at site. Also span was long about 70 mtrs. At that time hight was not proper due to slugedown. At that time two camels came in contact with live HT wire and get electrocuted and died at sight. Report yet not received NA NA one pole irrected in line for span reduced,maintenance work carrid out.
Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly.
2
147 ANJ Sudana, Camel, Owner: Laxmiben Somabhai Rabari 9.05.16 FA Due to heavy wind pole bend and stringing of wire became loose at site. Also span was long about 70 mtrs. At that time hight was not proper due to slugedown. At that time two camels came in contact with live HT wire and get electrocuted and died at sight. Report yet not received NA NA one pole irrected in line for span reduced,maintenance work carrid out.
Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly.
3
148 ANJ Palasava, Ravi Meghabhai Goyal 5.8.16 FHO The victim came in contact with earting wire and got shocked. TV channel cable joined with LT pole earthing wire and leakage current comes from TV channel cable to earth wire. Report yet not received NA NA TV channel cable and amplifier booster removed from LT pole 4
149 ANJ Rapar, Narshi Chaganbhai Bhil 12.8.16 FHO The victim touched the live bare conductor to win the "BET" they had and got an electric shock. Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 5
150 ANJ Chobari, Buffalo, Owner:Deviben Vashrambhai Khetani 28.8.16 FA Due to rain water logging surrounding area of LT pole  and also pole was wet. LT conductor touch shackle clamp, so some leakage current may be pass in this wet pole, at that time buffalos came near LT pole and got shock and died. Report yet not received NA NA Necessary maintenenance work carrid out 6
151 ANJ Chobari, Buffalo, Owner: Raniben Ranmalbhai Dhila 28.8.16 FA Due to rain water logging surrounding area of LT pole  and also pole was wet. LT conductor touch shackle clamp, so some leakage current may be pass in this wet pole, at that time buffalos came near LT pole and got shock and died. Report yet not received NA NA Necessary maintenenance work carrid out 7
152 JND SHRI  HARESHBHAI   DEVAYATBHAI  PAMAK of village PIKHOR under ANKOLVADI SDN. 06/04/16 FHO It Is To Kindly Inform That The Said Accident Was Occurred On Date 6.04.2016 But It Has Not Been Informed At Local S/Dn Office.It Has Come To Know When A Report Regarding The Said Accident Was Asked By Talala Police Station On Date.18.04.2016.This Accident Occured When Victim Was Trying To Repair D O Fuse By Climbing On Said T/C.He Came In Contact With Live Power At 11Kv Side Bushing And Met With Fatal Accident. Report yet not received NA NA Unauthosized work 1
153 JND SHRI  MAHAMMAD  SALAUDIN  of village SABALPUR under JND RURAL SDN. 20/04/16 FHO A Fatal Electrical Accident Occurred To Mohammad Salaudin , While Keeping Sliding Iron Tower Ladder , 21 Feet Height, Near Newly Constructed Compound Wall Of Mahindra Showroom And At That Time Iron Part Of Tower Ladder Touch To Live Conductor Of  11 Kv  Feeder, Passing Over And Above Compound Wall And Victim Met To Fatal Electrical Accident On Spot, Further Investigation Is Under Process. Victim Was Resi. At Present Mumbai , Labour Of J Ms Univarsal Technology Pvt Ltd.  Report yet not received NA NA line shifted to safer distance 2
154 JND SHRI  TAHIRKHA   SARVARKHA  BELIM of village ARANIYALA under MENDARDA SDN. 21/04/16 NFHO 11 Kv Line Erection Work Was Under Progress In The Supervision Of E.A. Sh.K.N.Solanki. New Line Of Jgy Bileswar Feeder Was Under Progress Crossing Multiple Ag Feeders.  Ag Feeders Of Work Execution Made Off By Lcp. But, The Victim Climbed On Pole Of Araniyala Ag Feeder By Mistake, On Which Work Was Not Planned To Execute, For Which Power Was On In Single Phase Supply. The Victim Climbed On Pole To Color On Tapping Angle. He Came Into Induction Zone And Fallen From Pole And Got Injuries. There Is No Tripping Noted In Araniyala Ag Feeder. The Victim Is Under Treatment At Private Hospital At Junagadh. Detailed Investigation Is Being Carried Out. Report yet not received NA NA safety meeting will be done 3
155 JND SHRI  VEJANANDBHAI   RAMDEBHAI  KAMALIYA of village TALALA under TALALA SDN. 23/04/16 NFHD While Attending One Of Fault Regarding Short Observation On Girder Pole (Pole Short), After Verification Of Lt Network When He Was Coming Back Towards Ground, Stopped Near One Point (About Eight To Ten Feet Above The Ground) To Check Service Line Wires, He Came In Contact With One  Of Insulation Breakage (Damaged) Wi Fi Wire Passing Through That Girder Pole.   Wi Fi Wire’S Other Open Part (Insulation Breakage) Was Also Touching To 11 Kv Jumper At Two Different Location Nearer To Place Where Accident Occurred. Report yet not received NA NA unauthorized work 4
156 JND Shri DEVABHAI BHARMALBHAI AAL of village KANZADI under SHAPUR SDN. 23/04/16 FA There Is 11 Kv Mota Kajariyala Ag Feeder Passing Parallel River Bank At Kanzadi ,Village:- Near Water Works .Due To Excavation And Shifting Land And Digging Of Land ,Pole Became Deeper Compare To Land Towards Tapping Line To Ag Group. Camel Crossed Tap 11 Kv For Eating Of Tree Of Sargva And Electroculated By Passing Under 11 Kv Line Hence Fatal Accident Occurred. Report yet not received NA NA line shifted to safer distance 5
157 JND SHRI  CHANDUBHAI   KALYANJI  DEKIVADIYA of village MOHABATPUR under SHAPUR SDN. 26/04/16 NFHO A Non Fatal Accident Occured  To Chandubhai Kalyanjibhai Dekivadiya .Victim Has Climbed Unauthorisely On Transformer Structre Which Is Situated On His Ag Land Without Informing Pgvcl Or Taking Prior Permission And Touched To The  Live Ht/Lt Line .While Coming In Direct Contact With The Live Wire Of Ht/Lt, He Got Electric Shock And Fallen From The Transformer.Detail Investigation Is Under Progress. Report yet not received NA NA unauthorized work 6
158 JND SHRI  DILAVAR    GULMOHMAD  MULTANI of village JUNAGADH under GANDHIGRAM SDN. 07/06/16 NFHD During Working On Tower Ladder For L T Line  Network  Tree Cutting Work, Victim  Slept From Ladder And Fall Down To Ground  And Non Fatal Departmental  Mechanical Accident Occurred.    Mechanical accident do work with safety NA Safety meeting arranged and given instruction 7
159 JND SHRI  VISHVAJITBHAI   BHAGVANBHAI  BARAD of village AMRAPUR under PRANCHI SDN. 18/06/16 FHO Victim May Have Unauthorizly Try To Work On Tc And Came In Contact With Live Power And Met With Fatal Accident. Sparking Observed On Jumper At 11 Kv Side And In Earthing Wire. Detail Investigation Under Progress. Report yet not received NA NA unauthorized work 8
160 JND SHRI  HITENDRA   HIRALAL  KALA of village MAJEVADI under JND RURAL SDN. 29/06/16 NFHD While Working On Four Pole Structure  To Attend 11 Kv Line Fault And After Completion Of Work On That Location Of Valasimdi Jgy Feeder , He Fall Down From Structure Via Sliding  With  Existing Old Guy So  Old Guy Wire Breaked During   That Instance And  Victim Got Injury In His Right Hand Elbow And Leg.  Safty Articles Were Used By Victim And Line Section Was Isolated And Earthed By Victim. Further Investigation Is Under Process.    Report yet not received NA NA Safety meeting arranged and given instruction 9
161 JND     Shri NARANBHAI HIRABHAI SOLANKI ,Of Village MADHUPUR ,Under, ANKOLVADI, SDN. 04/07/16 FA Due To Rain  Lt Shackle Insulator  Broke And Due To This Conductor Snapped On Land .Victimized Buffalos Came In Contact With This  Live Conductor And Met With Fatal Accident.  Report yet not received NA NA Shackle insulator replaced 10
162 JND     Shri NARANBHAI HIRABHAI SOLANKI ,Of Village MADHUPUR ,Under, ANKOLVADI, SDN. 04/07/16 FA Due To Rain  Lt Shackle Insulator  Broke And Due To This Conductor Snapped On Land .Victimized Buffalos Came In Contact With This  Live Conductor And Met With Fatal Accident.  Report yet not received NA NA Shackle insulator replaced 11
163 JND     Shri NARANBHAI HIRABHAI SOLANKI ,Of Village MADHUPUR ,Under, ANKOLVADI, SDN. 04/07/16 FA Due To Rain  Lt Shackle Insulator  Broke And Due To This Conductor Snapped On Land .Victimized Buffalos Came In Contact With This  Live Conductor And Met With Fatal Accident.  Report yet not received NA NA Shackle insulator replaced 12
164 JND SHRI VIJAYBHAI   BABUBHAI JETHAVA ,Of Village GHANTIYA ,Under, PRANCHI, SDN. 10/07/16 NFHO Contractors Were Erecting Girder Pole Under11Kv Maruti Jgy Feeder.Line Clear Of Maruti Feeder Was Taken.But, At 66Kv Sub Station End Operator Was Working In Breaker And At That Time Due To Failure In Breaker Power Came On Maruti Feeder And Contractor Person Who Are Standing On Ground And In Touch Of Girder Pole And Which Is Touching Line Of Maruti Feeder Got Electric Shock And Met With Non Fatal Aaccident.Also Operator Of Getco  Got Non-Fatal Accident At Ss End. Report yet not received NA NA Safety meeting arranged and given instruction 13
165 JND SHRI PRAFULBHAI  BHIKHABHAI CHUDASAMA ,Of Village GHANTIYA ,Under, PRANCHI, SDN. 10/07/16 NFHO Contractors Were Erecting Girder Pole Under11Kv Maruti Jgy Feeder.Line Clear Of Maruti Feeder Was Taken.But, At 66Kv Sub Station End Operator Was Working In Breaker And At That Time Due To Failure In Breaker Power Came On Maruti Feeder And Contractor Person Who Are Standing On Ground And In Touch Of Girder Pole And Which Is Touching Line Of Maruti Feeder Got Electric Shock And Met With Non Fatal Aaccident.Also Operator Of Getco  Got Non-Fatal Accident At Ss End. Report yet not received NA NA Safety meeting arranged and given instruction 14
166 JND     ShriSOMRAJBHAIMULABHAINAKRANI ,Of Village SAMATPARA ,Under, BHESAN, SDN. 18/07/16 FA A Buffalow Passed Under The Transformer Structure During That Time Due To Rain The Land Was Wet So When Buffalow Passed It May Be Leakage Current Passes Through Buffalow And Met With Fatal Accident. Pvc Rigid Pipe Was Installed And It Was Intact. Matter Is Under Investigation. Report yet not received NA NA Earthing reactivate 15
167 JND SHRI DEVSHIBHAI  ARJANBHAI VADHIYA ,Of Village TIMBAVADI ,Under, SATELLITE, SDN. 30/07/16 NFHO While Victim Trying To Move About 12 Feet Long Galvenised Steel Ladder From 1St Floor Of Newly Constructed Gaushala Building, Victim Loose His Balance Due To Heavy Weight Of Steel Ladder And Ladder Came In Contact With Live Wire Of 11 Kv Timbavadi Feeder And Electocuted And This Non Fatal Outsider Human Accident Take Place In Network, This Construction Was Done Unauthorisely Owner Had Not Informed Our Local Office About Construction Near Line And Construction Was Done In Such A Way That Horizental Distance Between Line And Building Is Only Approx. 1.5 Feet As Measured.  Report yet not received NA NA illegal construction 16
168 JND     ShriRAMBHAIBHURABHAIMER ,Of Village KHADIYA ,Under, BILKHA, SDN. 01/08/16 FA Due To Heavy Wind And Rain,Tree Branch Fall On Lt Line And Lt Line Conductor Snaps From Pole And Fall On Ground.At That Time Cow Come In Contact With Snapped Conductor And Got Electrocuted And Met With Fatal Accident. Report yet not received NA NA Tree cutting done 17
169 JND SHRI MUKESHKUMAR  BHANSHANKAR JALEJA ,Of Village MADHUPUR ,Under, ANKOLVADI, SDN. 03/08/16 NFHD By Mistake Victim Disconnected Gang Switch Of Other Section And Climb On 11Kv Line For Pin Binding Work.So, He Came In Contact With Live Power And Met With Non Fatal Accident. Report yet not received NA NA Safety meeting arranged and given instruction 18
170 JND     ShriPOPATBHAIDEVABHAIKHAMBHALA ,Of Village SHAPUR ,Under, SHAPUR, SDN. 02/08/16 FA A Fatal Accident Occurred To She Buffalo As She Baffalo Might Be Crossing Through The Ratibhai Fadadu Tc And As She Baffalo Touched Guy And Guy Was Broken From The Ground And Due To Swing It  Touched Live Part Of Nearby Tc So Came In Direct Contact With Live Phase Through Guy And Probably Electrocuted  & Met With Accident. There Is Sparking Fouund In Guy Wire. Report yet not received NA NA Earthing reactivate 19
171 JND     Shri BHUPATBHAI KHODABHAI RABARI ,Of Village SABALPUR ,Under, GIDC JND, SDN. 04/08/16 FA While Visit To Accident Place,It Comes To Know That A Cow Was Passing Near Ram Mandir Sabalpur At Early Morning Nearly 5:00 Am Aprox At That Time A Conductor Of Load Side Of Street Light Meter Was Snapped And Fallen On Ground , So It May Happened That The Cow Came In Contact With Load Side Wire Of Street Light And Accident May Occurred Report yet not received NA NA notice given to corporation 20
172 JND     Shri ARJANBHAI JADAVBHAI MER ,Of Village PANDVA ,Under, PPATAN, SDN. 08/08/16 FA Due To Rain And Heavy Wind Branches Of Tree Fall Down On Abcable So Cable Broke And Fall Down On Earth.Victimized Cow Came In Contact With This Live Lt Cable And Met With Fatal Accident. Report yet not received NA NA Tree cutting done 21
173 JND     Shri FOREST DEPT. ,Of Village MITHAPUR ,Under, PPATAN, SDN. 07/08/16 FA In Rainy Season A Leopard And Peahen Was Found Dead On The Transformer Center Of Village Mithapur.As Per Site Situation This Accident Might Be Occurred When Leopard Might Have Gone To Attack On Pehan Which Was Sitting On T/C.Thus, Both Came In Contact With Live Power At 11Kv Bushing Side And Met With Fatal Accident. Report yet not received NA NA NA 22
174 JND     Shri FOREST DEPT. ,Of Village DHAVA ,Under, TALALA, SDN. 15/08/16 FA Due To Heavy Wind Pressure Tree Branches Came In Contact With Lt Line Conductor And Due To That Conductor Broke And Fall Down On Earth. When The Hyna Was Passing From There It Came In Contact With  Live Conductor And Met With Fatal Accident. As Per De Talala Report Condition Of Conductor Is Good. Report yet not received NA NA Tree cutting done 23
175 JND     Shri HARDASBHAI BHIMSHIBHAI RAM ,Of Village GHUSIYA ,Under, TALALA, SDN. 18/08/16 FA 1 Ph Twin Core Service Wire Was Short Due To That A Leakage Current Was Passing And Surrounded Area Of Tranformer Center Was Wet  When Victimized Buffalo Was Passing Near From This Transformer Center Got Electricshock And Met With Fatal Accident Report yet not received NA NA Earthing reactivate 24
176 JND     ShriN.A. ,Of Village BODAKA(S) ,Under, VANTHALI, SDN. 25/08/16 FA A Fatal Electrical Accident Occurred To Leopard At Bodaka Ag Feeder It May Have Happened That He Climbed On Pole May Be For Hunt And Came In Contact With Live Electric Line And Met With Fatal Accident.  Report yet not received NA NA NA 25
177 JND     Shri JIVABHAI AMRABHAI MORI ,Of Village JUNAGADH ,Under, GANDHIGRAM, SDN. 06/09/16 FA A Fatal Accident Occurred To A Buffalo(She) Due To Returned Leakage Current In Neutral Wire From Datar Manzil Police Quarter Block No.7 Consumer No.30806170255,It Flowed From Locked House Through Lt Line Common Neutral Which Connected With Earthing Of Tc No,Gg09 And Due To Wet Ground Surface In Monsoon And Buffalo(She) Got Electrolided And Contected With Wet Area & Got Electric Shock And Fatal Animal Accident Occurred.  Report yet not received NA NA Earthing reactivate 26
178 JND     Shri MALABHAI KARSHANBHAI DODIYA ,Of Village BHIMDEVAL ,Under, ANKOLVADI, SDN. 07/09/16 FA Fatal Electrical Animal Accident Occurred Due To Motor Was Short Of Sri Bharat Uka And Due To That Leakage Current Was Passing From Neutral Of Tc. A Victimized Buffalo When Passing Near From That Tc It Came In Contact With Earthing Of Tc And Got Electric Shock Due To Leakage Current And Met With Fatal Accident. Report yet not received NA NA Earthing reactivate 27
179 JND     ShriHamir Vejanand  Ram&Malde Naga solanki ,Of Village UMRETHI ,Under, TALALA, SDN. 19/09/16 FA Due To Rain Lt Shackle Insulator Broke Accidently Due To That Lt Line Conductor Was Snapped, Victimized Buffalos Came In Contact With This Snapped Conductor And Met With Fatal Accident Report yet not received NA NA Shackle insulator replaced 28
180 JND     ShriHamir Vejanand  Ram&Malde Naga solanki ,Of Village UMRETHI ,Under, TALALA, SDN. 19/09/16 FA Due To Rain Lt Shackle Insulator Broke Accidently Due To That Lt Line Conductor Was Snapped, Victimized Buffalos Came In Contact With This Snapped Conductor And Met With Fatal Accident Report yet not received NA NA Shackle insulator replaced 29
181 JND     ShriHamir Vejanand  Ram&Malde Naga solanki ,Of Village UMRETHI ,Under, TALALA, SDN. 19/09/16 FA Due To Rain Lt Shackle Insulator Broke Accidently Due To That Lt Line Conductor Was Snapped, Victimized Buffalos Came In Contact With This Snapped Conductor And Met With Fatal Accident Report yet not received NA NA Shackle insulator replaced 30
182 BVN Bhavnagar City - Rameshbhai Manubhai Vagh 13/04/16 NFHO Victim unauthorizly climbed on TC strucure to tighten rope of banner to pole of TC and came in induction zone of live power and got electric shock and met with non fatal accident. Report yet not received NA NA Give guideline to other public for regarding PGVCL network and never climb on it. 1
183 BVN Shobhavad village - Sh.Bharatbhai Danabhai Vaghela 22/04/16 FHO THE VICTIM WAS CLIMBED ON TREE UNDER THE 11KV PASVI AG FDR TO CUT THE TREE BRANCHES AND BY MISTAKE GOT IN TOUCH WITH 11 KV CONDUCTOR OF PASVI AG FDR AND VICTIM GOT ELECTRIC SHOCK AND DIED.  Report yet not received NA NA Give guideline to other public for regarding PGVCL network. 2
184 BVN Sukhpar village - Sh.Hipabhai Vashrambhai Suvan  owner of 2 Nos of Indian Cow 09/05/16 FA The lower proceline part of DO fuse and it was lying on x'mer body, due to this whole DP structure electrocuted. Two cows came in contact with the electrocuted DP stucture. So they got electric shock and died. At that time heavy wind with shower rain was flowing. Report yet not received NA NA Departmental maintenance done and instruct line staff for more awareness about line network. 3
185 BVN Sukhpar village - Sh.Hipabhai Vashrambhai Suvan  owner of 2 Nos of Indian Cow 09/05/16 FA The lower proceline part of DO fuse and it was lying on x'mer body, due to this whole DP structure electrocuted. Two cows came in contact with the electrocuted DP stucture. So they got electric shock and died. At that time heavy wind with shower rain was flowing. Report yet not received NA NA Departmental maintenance done and instruct line staff for more awareness about line network. 4
186 BVN Valukad village - Jaydipbhai Nileshbhai Baraiya 17/05/16 FHO At the place of accident the area was hilly. The victim was trying to cross the farm boundary. The farm boundarywas made of 8 ft cement pole with fencing of barbered wire. The victim was jumped to cross fencing boundary. While doing this he was touched to HT line of 11 KV kankot Ag feeder which near to fencing boundary and electrocuted.     Report yet not received NA NA New HT pole erected between span 5
187 BVN Adhevada village - Rambhai Bijalbhai Mevada owner of Cow(Indian) 23/05/16 FA Cow was passing under 11kv line at that time  conductor broken of 11 kv Adhewada jgy and cow came in touch with broken wire , so  got shock And died. Report yet not received NA NA Couductor replaced. 6
188 BVN Bhavnagar City - Yasinkhan "urfe Arifbhai" Usufkhan Baloch 04/06/16 FHO The victim is contractor labour person. During LT rectification work while climbing the round pole, victim was fall down and met with fatal accident. Detail investigation of cause of accident is under progress. We have approach government hospital for PM report but it is still awaited. Report yet not received NA NA proper communication and proper supervision must be taken and line must be isolated and earthed and safety equipment must be used by all to prevent such accident in future. 7
189 BVN Chok village - Sh Himanshubhai J Mehta 16/06/16 FHD As there is one complain, Victime was doing Jumper work on TC known as Chok Bus stand Group, While Victim was about to start the work , He came in contact with live wire of 11 KV Chok ag feeder and he got electric shock and electrocuted. Report yet not received NA NA All line staff instucted to use all safety tools and more aware during work. 8
190 BVN Nicha Kotda village - Ashokbhai Jadavbhai Bhil 18/06/16 NFHO 11 KV line conductor Snapped due to Pin fault and at the same time victim was passing from there & conductor touched to him & Non fatal accident occures Report yet not received NA NA PIN replaced and conductor repair and inform to all line staff to more aware regarding network. 9
191 BVN Vadli village - WITHOUT OWNER (VENDERING ANIMAL) 1-Cow Indian & 1 Oxe 25/06/16 FA Due to heavy rain and wind one of the jumper of 11kv Line Malvav JGY  broken and touched to DO Angle and earth wire on Pole, meantime one cow and one OXE were standing under the TC and both came in contact with the earth wire of TC structure & electrocuted. Report yet not received NA NA New jumper provided and inform to all line staff to more aware regarding network. 10
192 BVN Mahuva village - WITHOUT OWNER (VENDERING ANIMAL) 1-Cow Indian 25/06/16 FA Due to rain Cabel from transformer to pole fired  & touched the girder  pole as girder pole was wet due to rain current leakages through pole, at that time cow came in contact with that girder pole and met with electric shock and died. Cow was totally wet and in contact with water neasr girder pole Report yet not received NA NA Cable replaced and inform to all line staff to more aware regarding network. 11
193 BVN Gandhol village - Rudiben Kababhai Luni owner of 2 Nos of Indian Cow 25/06/16 FA Due to return current from LT side B phase to neutral, leakage current flow in to transformer earthing and when cow goes near surrounding to transformer and got electric shock and died. After investigate this, it comes to know that this return current comes from any of house under this transformer which may be due to short circuit of any instrument of their. Report yet not received NA NA Earthing reactivate 12
194 BVN Gandhol village - Rudiben Kababhai Luni owner of 2 Nos of Indian Cow 25/06/16 FA Due to return current from LT side B phase to neutral, leakage current flow in to transformer earthing and when cow goes near surrounding to transformer and got electric shock and died. After investigate this, it comes to know that this return current comes from any of house under this transformer which may be due to short circuit of any instrument of their. Report yet not received NA NA Earthing reactivate 13
195 BVN Kukad village - Pachiben Premjibhai 28/06/16 NFHO On date:28-06-2016, app 12:05 PM at village kukkad, motipara area, near residance of Bhimabhai Ramjibhai, Con no:37675004586 in front side of the consumer 3 wire LT line pole no: S-06/20.3.09 exist. On that day may be due to rain and wind pressure dropper of above LT pole touched to pole GI wire and power flow through GI wire to ground and due to rain pole is wet. So at that time buffaolw and victim Panchiben were passing near to the pole and at that time buffolw got electrolyte and died and due to metal chain tied to animal neck and other side of chain was in her (panchiben's) hand so that also got shock and met with non fatal accident. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 14
196 BVN Kukad village - Premajibhai Mohanbhai owner of 1 Buffalo 28/06/16 FA On date:28-06-2016, app 12:05 PM at village kukkad, motipara area, near residance of Bhimabhai Ramjibhai, Con no:37675004586 in front side of the consumer 3 wire LT line pole no: S-06/20.3.09 exist. On that day may be due to rain and wind pressure dropper of above LT pole touched to pole GI wire and power flow through GI wire to ground and due to rain pole is wet. So at that time buffaolw and victim Panchiben were passing near to the pole and at that time buffolw got electrolyte and died and due to metal chain tied to animal neck and other side of chain was in her (panchiben's) hand so that also got shock and met with non fatal accident. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 15
197 BVN Hanol village - Raghubhai Nanubhai Rabari owner of 1-Cow Indian 29/06/16 FA 100 KVA xmer exist TC in village Hanol for cattering of powersupply for this village xmer earthing touch with 11 kv garding and that garding touch with further 11 kv line pole earthing due to rain season leakage current produced in xmer centre earthing and that current passing through 11 KV line garding and 11 KV pole earthing land Surrounding the pole was wet and filled with water due to heavy rain so step voltage produced inpole surrounding area and cow come in contact with this difference of potential produced in their front both legs, cow got electric shock and died. Report yet not received NA NA Earthing reactivation done 16
198 BVN Dihor village - Ashvinbhai Nandrambhai Dhandhliya owner of 1 Buffalo 29/06/16 FA On dtd, 29.06.16 around 15.45 HRS, when buffalo of shri Ashvinbhai Nandrambhai was pasing along road, due to heavy rain and water logging around village TC, buffelo went near TC. Due to service fault in the connection of Ajitsinh Shivubha, Current was returning through neutral and hence, due to this current while buffalo went near TC, She got electrocuted and met with fatal Accident. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 17
199 BVN Thalsar village - Mahendrasinh Pravinsinh Gohil owner of 1-Cow Indian 29/06/16 FA LT pole dropper connected by private person in LT line with live LT wire by approx 2 meter. Dropper wire which is touch in LT pole earth wire current passing in earth wire at a time high rain and wind flow and at this time cow passing through near to way to LT pole and came in contact of current by water and cow got electric shock and died. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 18
200 BVN Tarsara village - Sh. Bhupatbhai Dudabhai Vegad owner of 1 Buffalo 01/07/16 FA As per talk shri bhupatbhai dudabhai vegad he comes with his 4 buffalo from field to his house in between near to village after river crossing one of buffalo run and walk through TC and as monsoon is started and continuous raining one service is damage and it touch with earthing wire and it charge TC area surrounding area of TC so buffalo electrocuted and died. Report yet not received NA NA Earthing reactivation done 19
201 BVN Kharakdi village - Maldevsinh Bahadursinh Gohil owner of 1-Cow Indian 02/07/16 FA Cow was Passing near 11 KV pole of navyug jgy feeder on which 5 KVA TC mounted. Leakage current of LT side of TC passing through pole and earth to ground and step potential created between four leg of cow so got shocked and died. Report yet not received NA NA Earthing reactivation done 20
202 BVN Bhavnagar City - Ranjitbhai Devabhai Bharvad owner of 1-Cow Indian 02/07/16 FA Due to fault in Streetlight tube, Street light fixture got electrically live, due to this leakage power is pass from girder pole to ground and so girder pole got electrically live. When cow came in contact with this electrically live girder pole, cow is electrocute. Report yet not received NA NA Letter written to Nagarpalika for Check Street light wiring in all jurisdiction 21
203 BVN Bhavnagar City - Muljibhai Ratnabhai Chouhan 18/07/16 FHO The victim was on top of the newly under constructed building to fix up parapet and construction work. He was working in vicinity of 11 KV line. He might be came in contact of 11 KV line and electrocuted. Report yet not received NA NA To issue notice in case where line clearance is not as per IE rules & remove such clearances 22
204 BVN Kamlej village - Muljibhai Devbhai Sangha owner of 1-Cow Indian 04/07/16 FA On date 25-07-2016, cow's owner gave detail of accident with post mortem report and police punchnama. So as per cow's owner statement cow passing near transformer and comes under induction zone of transformer and got shocked and died. Report yet not received NA NA Earthing reactivation done 23
205 BVN Songadh village - Shaileshbhai Gobarbhai Aal owner of 1-Hourse 12/08/16 FA At place of accident, LT Girder pole exist and street light also exist on this pole. Street light's fixture found short at there due to internal wiring of it hence live phase current passed through fixuture handle to girder pole and top of the girder pole laying guy with tapping angle while turn buckle of this guy has one iron wire bounded, it is not PGVCl wire but it is found like mainly use in dis TV cable support iron wire. This iron wire laid from top of the girder to land and it miight be throughly passed live current due to above reason hence this live wire laid on ground so any time female horse might be touched and might got shock and this wire wounded it's body same might be got unfortunately shock (electrocution) and dead. There is no any lacuna of PGVCL work/Staff etc but street light fixture was short and Dis TV network wire comes on contact through girder pole and this accident unfortunately. Report yet not received NA NA Letter written to Panchayat and Cable operate for Check Street light wiring in all jurisdiction 24
206 BVN Bharoli village - Mahavirsinh Virubha Gohil owner of 1 Buffalo 25/08/16 FA ON Dtd 25.08.16 around 11.30 HRS, an LT Line conductor of AG group TC cut down from the binding and fall on buffalo of Shri Mahavirsinh Virubha Gohil, Standing Right below the LT Line, Due to live conductor fall on buffalo, She got electrocured and met with fatal accident. Report yet not received NA NA Deteriorated conductor replaced 25
207 BVN Gundarana village - PATABHAI RAMBHAI KAMALIYA owner of 1 Buffalo 26/08/16 FA when buffalo started rubbing with guy wire at that time below insulation guy wire get connected with jumper wire of live gang switch  pole no-bag/kum/248/ag of 11 kv bhaguda ag .feeder  and accident occurred. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 26
208 BVN Varal village - Rasabhai Jethabhai Makvana 19/08/16 FHO As shihor police station has informed to Shihor Rural sdn on Date:26-08-2016 and site visit carried out on date:26-08-2016. Victim Shri Rasabhai Tejabhai doing work of grass cutting with use of stickle at farm of Kanabhai Arjanbhai Tejani at Varal. Accidently he touched the earthing wire of TC and due to leakage current, victim electrocuted. Report yet not received NA NA All earthing of transformer are reactivated 27
209 BVN Nesda village - Sureshbhai Nathubhai Rathod 23/07/16 NFHO As shihor police station has informed to Shihor Rural sdn on Date:26-08-2016 and site visit carried out on date:26-08-2016. Victim was doing construction work for building new house for Vallabhbhai at Nesda village. The construction of Kitchen done below the 11 KV line of Nesda Ag. During such construction work of terrace, victiom accidentlly touch the 11 KV line and got shock. Report yet not received NA NA To issue notice in case where line clearance is not as per IE rules & remove such clearances 28
210 BVN Valavad village - Nanjibhai Dhudabhai Jadav owner of 1 Buffalo She (Below Two yrs) (Padi) 31/08/16 FA The animal (Padi) tied with metal chain with a big metal nail and the nail was punch in soil near fencing of farm of Shri Nanjibhai Dhudabhai, Vill: Valavad. As the conductor of 11 KV Padapan Ag feeder snapped and fall on fencing and also snapped on 11 KV Gautmeshwar Urban feeder. Hence, the the line of 11 KV Padapan Ag and 11 KV Gautmeshwar feeder and fencing became short. As the nail was punch in soil near fencing and the land was wet, due to leakage current animal got electrocuted. There is no any mark of electrical accident hence, this preliminary reason confirmed after PM Report. (Suspected) Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 29
211 BVN Bhavnagar City - Vishalbhai Kantibhai Rathod 04/09/16 FHO An Accident Occur In PGVCL Network,
Accident occurred while deceased person was fixing private yellow colour service wire (for Ganpati Utsav near Ravi Darshan Complex) on transformer center (Location No. VID/33), he was came in contact with drop out fuse of transformer center. Hence he was electrocuted. Thus met with electrical accident. Deceased person was not authorized to do so.
Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 30
212 BVN Bhankhal village - Sh Mehulbhai Mangabhai Mori 07/09/16 NFHD Shri Mehulbhai Mori went to attend the complain of Shri Ghanshyambhai  Mathurambhai along with shri Tadavi LM, and Shri K D Joshi EA, Shri Tadavi took LC of 11 KV Bhakal AG Feeder, the jumper of 11 KV Bhakhal AG fdr was blown of at Narbherambhai Bhaishankarbhai's farm. Shri Mori climb the angle on which DO fuse are fixed. During work he Sliped down and got mechanical injury. Report yet not received NA NA Instruction given to all line staff that proper care taken while climbing on TC center / Pole. 31
213 BVN Nava Kotda village - Bhaolabhai Amarashibhai Makvana owner of 1 Buffalo She  07/09/16 FA Buffalo pass near the LT line pole and rubbed body with pole and horn of buffalo stuck in earthing wire and while trying to came out from this, earthing wire of pole was touch with live phase of line and due to this buffalo electrocuted. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 32
214 BVN Bhavnagar City - Hamabhai Sondabhai Mer owner of 1 Buffalo She  19/09/16 FA At place of accident, buffalo was passing near LT pole and touch with guy wire in which guy insulator is broken. Hence current leakage from open joint of LT ABC and LT PVC cable flew through wet PSC pole and guy wire. Buffalo touched with this guy wire and got electric shock and died. Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 33
215 BVN Ayavej-2 village - Rajubhai Ananadubha Sarvaiya owner of 1-Hourse 01/09/16 FA When horse was rubbing with damaged pole , at that time visible Iron rod in LT Pole no. I51/21.06.78 Touched to it, and leakage current passed through body and Horse was electrocuted Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 34
216 BVN Saloli village - Jasabhai Kanabhai Giyad owner of 1 Buffalo She  09/09/16 FA When Buffalo started Rubbing with PSC pole No. BAG/GUN/221/R094 of  11kv Gundarana JGY Feeder, Suddenly it get contact with G.I Wire and Due to leakage current flowing through same wire, buffalo got electric shock and died on the spot Report yet not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC center" during khedut-shibir & village meeting regularly. 35
217 BTD At Village Dhola Godaji of Shri visnubhai Rameshbhai Chudasama 07/04/16 NFHO On dated 07.04.2016 the labours of contractor M/s Shivranajani Const, Bhavnagar were working on 11 kv Hadmatala Jgy feeder by isolating jumper at location no DHO/HAD/JGY/227/R66. By mistake the victim climbed on same DP structure from where such line was isolated and touched live conductor momentarily of 11 KV Hadmatala JGY feeder . Due to this He got an electric shock & fell down due to the impact . Report yet not received NA NA Disciplinary action taken agaist defaulter and safety awareness meeting done regulerly 1
218 BTD At Botad Town of Shri KHODABHAI MAVJIBHAI GHODAKIYA 09/06/16 NFHO As Per Report Of Eye Witness, As On Dt:- 09.06.2016 & In Morning Victim Was Repairing Galvanized Iron Sheet On The Roof Accidently Lapse The Legs And Touch Iron Rod And Came In Contact With 11 Kv Gayatrinagar Feeder Ht Line Report yet not received NA NA Public awareness program done in different villages regulerly 2
219 BTD At Botad Town of Shri
DINESHBHAI ODHABHAI VASANI
09/06/16 NFHO As Per Report Of Eye Witness, As On Dt:- 09.06.2016 & In Morning Victim Was Repairing Galvanized Iron Sheet On The Roof Accidently Lapse The Legs And Touch Iron Rod And Came In Contact With 11 Kv Gayatrinagar Feeder Ht Line Report yet not received NA NA Public awareness program done in different villages regulerly 3
220 BTD At Botad Town & Baffalo of Shri
Ukabhai Chhaganbhai Chosala
20/06/16 FA Buffalo was passing nearby Gang Switch DP No. HAD/RAM/JGY/069/R/021 of 11 KV Ramdev JGY feeder and it was rubbing it’s horns on GUY wire, Due to loose Guy wire, the GUY wire touched with gang switch jumper. Hence, Jumper disconnected from binding and hanging, the same was came in contact with buffalo and got electrocuted and died suddenly Report yet not received NA NA Tightning of Loose Guy Wire 4
221 BTD At Village Taraghara of Shri Dhudabhai Muljibhai Jamod 25/06/16 FHO At the Place of accident there is11 KV Taraghara AG Feeder, While contractor demanded LC from LM of 11 KV Babarkot AG feeder. Hence wrong LC taken by Line Man as per demanded by Contractor person. Victim climb the pole for shorting the 11 KV line by hand, at that time victim toch the live wire and got electrocuted. Report yet not received NA NA Disciplinary action taken agaist defaulter and safety awareness meeting done regulerly 5
222 BTD At Village Dadva, Cow of Shri SUKHABHAI KAMABHAI KHATANA 25/06/16 FA On preliminary investigation it was found that the accident occurred due to HT conductor break down from anchor point disc insulator near village TC of Dadva village. The said cows which belonged to Sukhabhai Kamabhai Khatana were standing under thrown tree (baval) over which HT line was passing. About at 15.10 hrs. the top conductor of the HT line broken and fall on the tree under which cow was standing. The cow came into contact with the Snapped HT line live conductor and got electrocuted. At same time, another cow came into contact with electrocuted cow. She also got electric shock and this way both cow electrocuted and died on the spot. Report yet not received NA NA Snapped Conductor Rejoint 6
223 BTD At Village Dadva, Cow of Shri SUKHABHAI KAMABHAI KHATANA 25/06/16 FA On preliminary investigation it was found that the accident occurred due to HT conductor break down from anchor point disc insulator near village TC of Dadva village. The said cows which belonged to Sukhabhai Kamabhai Khatana were standing under thrown tree (baval) over which HT line was passing. About at 15.10 hrs. the top conductor of the HT line broken and fall on the tree under which cow was standing. The cow came into contact with the Snapped HT line live conductor and got electrocuted. At same time, another cow came into contact with electrocuted cow. She also got electric shock and this way both cow electrocuted and died on the spot. Report yet not received NA NA Snapped Conductor Rejoint 7
224 BTD At Village Dharvala of Shri Pintuben maganbhai Vasava 03/07/16 FHO Vehicle no. GJ 25T5493 collide with PSC P ole of 11kv Limda JGY feeder & due to this it brakes the PSC pole from the bottom. From this HT pole tap line was their & due this collision live line conductor lower down and the truck which was loaded with iron scrap was toppled. The iron scrap of the truck came in contact with live conductor. Nearby this collision there is barbed wire fencing of the farmer. The truck iron scrap which was in contact with this live line conductor came in contact with this barbed wire.
      The victim Pintuben who were @ 250mtr away from this accident place came in contact with this barbed wire and got electrocuted and died on the spot.
 Other girl came in contact with this lady victim also got electric shock and met with nonfatal accident. She is hospitalized for treatment.
Report yet not received NA NA Public awareness program done in different villages regulerly 8
225 BTD At Village Dharvala of Shri Laxmiben Mukeshbhai Vasava 03/07/16 NFHO Vehicle no. GJ 25T5493 collide with PSC P ole of 11kv Limda JGY feeder & due to this it brakes the PSC pole from the bottom. From this HT pole tap line was their & due this collision live line conductor lower down and the truck which was loaded with iron scrap was toppled. The iron scrap of the truck came in contact with live conductor. Nearby this collision there is barbed wire fencing of the farmer. The truck iron scrap which was in contact with this live line conductor came in contact with this barbed wire.
      The victim Pintuben who were @ 250mtr away from this accident place came in contact with this barbed wire and got electrocuted and died on the spot.
 Other girl came in contact with this lady victim also got electric shock and met with nonfatal accident. She is hospitalized for treatment.
Report yet not received NA NA Public awareness program done in different villages regulerly 9
226 BTD At Village Kariyani, Cow of Shri Pethabhai Ratnabhai Dambha 29/06/16 FA When Cow was passing nearby Madhuli Valu Village TC of 11 KV Fakadanath JGY feeder and due to leakage cuurrent due to wet atmosphere and wet soil, cow got shocked and died at place.  Report yet not received NA NA Earthing Reactivated 10
227 BTD At Village Pati of Shri Andarsang Nandiyalbhai Rathwa 29/07/16 FHO Victim was cutting tree branches without informed to PGVCL authority near 11 KV Ningala AG feeder line in AG area of Vill. Pati. During tree cutting, victim cut one tree branch which falls on live 11 KV Ningala AG feeder line and power comes in the body of victim through this cutted tree branch and electrocuted and fall down from tree. Report yet not received NA NA Public awareness program done in different villages regulerly 11
228 BTD At Village Panvi of Shri Ravibhai Rameshbhai Rathod 19/08/16 FHO As per primary information received, The victim was probably working  near bore well  under  11 KV Panvi AG feeder, 11 KV " R Phase Conductor snapped during this time and the victim came in con tact with this snapped conductor and get electrocuted.  Report yet not received NA NA Public awareness program done in different villages regulerly 12
229 BTD At Village Barwala Town, Buffalow of Shri Kanubhai Dhurabhai Bhuva 28/08/16 FA During the rain buffalo was passing near transformer center such that it's come in contact with GI wire of earthing and get electrocuted so one no of buffalo died.Detail investigation reports follows Report yet not received NA NA Earthing Reactivated 13
230 BTD At Village Zamrala, Buffalow of Shri Maheshbhai Babbhai Khachar 17/09/16 FA Due to Buffalo abrase its body with guy wire of AB Switch DP. The Guy wire was in water logged area. Hence during abrasing the guy wire break and touches with jumper of DP and buffalo got shocked and died at place. Report yet not received NA NA Guy wire replaced 14
231 AMR KATHROTA,CHHAGNABHAI RUDABHAI SAVALIYA 03/05/16 FHO AS PER UNKNOWN TELEPHONIC INFORMATION   WE INVESTIGATE THE MATTER AND ONLY ABOVE DETAIL ARE FIRMS IN OUR KNOWLEDGE. VICTIM WAS FOUND NEAR THE TRANSFORMER CENTER ( BDR/GHD/AG/010/L-127/DT-23) IN HIS FARM WITH BURN SPOT  AT THAT TIME AS PER SAID BY SHRI PUNABHAI MADHUBHAI SAVALIYA , VILL. KATHROTA.  AND AFTER TAKING HIM TO GOVERNMENT HOSPITAL DHARI BY VEHICAL, DOCTOR TREATS HIM AND REFERS TO AMARELI FURTHER TREATMENT.  FURTHER DETAILS ARE UNDER INVESTIGATION. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 1
232 AMR CHALALA, SHRI HIMMATBHAI KARSHANBHAI BAMBHANIYA(E.A.) 20/05/16 NFHD AS PER PRIMARY INVESTIGATION HE WAS DOING  JUMPER OF FEEDER GOPALGRAM AG AT  LOCATION NO. CHL/GPL/0014/AG DUE TO INDUCTION OF 66 KV CHALALA –SARAMBHADA  LINE MID SPAN CROSSING HE GOT MILD ELECTROCUTE. HE SLITELY SLIP AND INJURED.
Report yet not received N.A. N.A. AWARENESS AMONG GENERAL DEPARTMENTAL STAFF REGARDING SAFETY IN EVERY SAFETY MEETING 2
233 AMR MOHBATPARA,1-LEOPARD(WILD ANIMAL) 21/05/16 FA THE PEACOCK COME IN TOUCH WITH TRANSFORMER DP CENTRE ON 21.05.16  AT EARLY MORNING & GET ELECTROCUTED DUE TO PHASE TO PHASE SHORT-CIRCUIT. NO TRIPPING IS OBSERVED DURING THIS INCIDENT.THAN AFTER LEOPARD MIGHT SEE PEACOCK ON DP STRUCTURE & TRY TO EAT, HENCE LEOPARD ALSO GET ELECTROCUTED DUE TO INTER PHASE SHORT CIRCUIT Report yet not received N.A. N.A. REQUIRED TRANSFORMER MAINTENANCE CARRIED OUT 3
234 AMR CHHACHHAR, 1-BUFFALLO OF SHRI INDUBHAI KARSHANBHAI MUNDAVA 24/05/16 FA DUE TO SNAPPING 11KV KHODIYAR AG CONDUCTOR , AT THE TIME BUFFALO CAME IN CONTACT WITH THIS BROKEN WIRE ,GET SHOCKED AND DIED AT THE SPOT .PARTY HAD REPORTED TO THIS OFFICE ON DATE:-24.05.16 AT 5;30PM. Report yet not received N.A. N.A. DETAILED HT LINE MAINTENANCE CARRIED OUT 4
235 AMR RAJULA,SHABIRBHAI YUSUFSHA DAL 15/06/16 NFHO THERE IS A RIVER CROSSING SPAN OF 11 KV  DHARNATH  JGY   FEEDER. RIVER CROSSING SPAN IS 99 METER LONG. BRIDGE WITH IRON PIPE REELING IS PARALLEL TO THIS 11 KV LINE. HORIZONTAL DISTANCE 1.3 METER DURING SITE VISIT NORMAL DEFLECTION OF WIRE WAS FOUND 0.3 METER FORM ORIGINAL POSITION, SPARKING ON REELING AT ROAD SIDE WAS FOUND. SO ON THE DAY OF ACCIDENT, DUE TO VERY HEAVY WIND RESULT IN TO HEAVY DEFLECTION THIS HORIZONTAL DISTANCE MAY REACH TO LESS THAN 1 METER AND AS WE FOUND SPARKING ON REELING AT ROAD SIDE, VICTIM MAY TRY TO DO ANY ACTIVITY LIKE BENDING TOWARDS LINE TO VIEW DOWN THE BRIDGE, FACE TOWARDS 11 KV LINE, ACCIDENTLY COMES IN CONTACT  WITH LIVE 11 KV LINE BY HIMSELF OF BY ANY METALLIC MATERIAL AND GOT ELECTROCUTED RESULTED IN TO NONFATAL ELECTRICAL ACCIDENT. FROM LOGSHEET OF 66 KV RAJULA SS TRIPPING WAS RECORDED ON DATE 15.06.2016 AT 2:55 PM. Report yet not received N.A. N.A. ADEQUATE HORIZONATAL DISTANCE MADE BY EXTRA ERECTION OF GIRDER POLE 5
236 AMR JIRA,1-COW OF SHRI PARBATBHAI SEFABHAI AAL 21/06/16 FA AS PER UNKNOWN TELEPHONIC INFORMATION WHEN WE INVESTIGATE THE MATTER WE FOUND THAT LT ABC CABLE FIRED AT ACCIDENT PLACE, DUE TO HEAVY RAIN AND WIND ACCIDENTLY TOUCHED WITH C CLAMP WHICH WAS CONNECTED TO EARTHING WIRE, AND AS LAND SURROUNDING TO POLE IS WET DUE TO RAIN, WHEN ANIMALS WERE PASSED NEARER  TO POLE BOTH GOT ELECTROCULLATED. Report yet not received N.A. N.A. REQUIRED LT MAINTENANCE CARRIED OUT 6
237 AMR JIRA,1-BUFFALO OF SHRI PARBATBHAI SEFABHAI AAL 21/06/16 FA AS PER UNKNOWN TELEPHONIC INFORMATION WHEN WE INVESTIGATE THE MATTER WE FOUND THAT LT ABC CABLE FIRED AT ACCIDENT PLACE, DUE TO HEAVY RAIN AND WIND ACCIDENTLY TOUCHED WITH C CLAMP WHICH WAS CONNECTED TO EARTHING WIRE, AND AS LAND SURROUNDING TO POLE IS WET DUE TO RAIN, WHEN ANIMALS WERE PASSED NEARER  TO POLE BOTH GOT ELECTROCULLATED. Report yet not received N.A. N.A. REQUIRED LT MAINTENANCE CARRIED OUT 7
238 AMR PREMPARA,1-GOAT OF SHRI HAMIRBHAI NARANBHAI PARMAR 22/06/16 FA AS PER TELEPHONIC INFORMATION RECEIVED AND   WE INVESTIGATE THE MATTER, IT IS FOUND THAT STREET LIGHT WIRE JOINT BRACKED AT ACCIDENT LOCATION, DUE TO RAIN AND HEAVY WIND  ACCIDENTLY TOUCHED WITH EARTH WIRE OF EXISTING POLE , AS LAND IS WET SURROUNDING THE POLE DUE TO RAIN WHEN ANIMAL PASSED NEARER TO POLE GET ELECTROCUTED  Report yet not received N.A. N.A. REQUIRED LT MAINTENANCE CARRIED OUT 8
239 AMR SAVARKUNDLA,BHARATBHAI SHAMJIBHAI SOLANKI 22/06/16 NFHO VICTIM WAS A LABOURER AND WORKING ON OVER EXTENDED SLAB OF AN UNDER CONSTRUCTION SHOP. 11KV KUNDLA CITY FEEDER IS PASSING ABOVE SAID OVER EXTENDED SLAB. A BAMBOO WAS PROVIDED TO KEEP AWAY 11KV LINE FROM OVER EXTENDED SLAB. ON THE DAY OF ACCIDENT, TERRACE WAS FILLED WITH WATER FOR CURING, DURING SITE VISIT PEOPLE WERE SAYING THAT VICTIM FALLEN FROM SLAB AND WAS SENT TO NEARBY HOSPITAL FOR FIRST AID AND THEREAFTER REFER TO OUT OF SAVARKUNDALA FOR FURTHER TREATMENT. THEREFORE FROM PRIMARY INVESTIGATION AND AD THERE IN NO ANY EYEWITNESS AND VICTIM HIMSELF CAN SPEAK ANYTHING IN HIS STATEMENT AND THEREAFTER ANALYZING  MEDICAL REPORT ACTUAL CAUSE OF THIS ACCIDENT MAY COME TO KNOW. Report yet not received N.A. N.A. ADEQUATE HORIZANTAL MADE BY INSERTING EXTRA ERECTION OF POLE. 9
240 AMR KOVAYA,1-BUFFALLO OF SHRI BHAGVANBHAI BHIKHABHAI VAGH 26/06/16 FA ON THE DAY ACCIDENT THERE WAS RAIN FALLING AND LAND SURROUNDING TO TRANSFORMER CENTRE WAS WET.WHEN A BUFFALLOW CRAWLING NEARED TO TRANSFORMER CENTRE, DUE TO LEAKAGE EARTHING CURRENT, IT WAS GOT ELECTROCUTED AND DIED. Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 10
241 AMR BHADA,1-COW OF SHRI ARJANBHAI NATHUBHAI MAKVANA 27/06/16 FA LT CONDUCTOR WAS BROKEN AT ACCIDENT PLACE AND WHEN COW WAS PASSING NEAR THIS LOCATION AT THAT TIME A COW WAS CAME IN CONTACT WITH LIVE CONDUCTOR AND GOT ELECTROCUTED AND DIED Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT & AB CABLE REPLACED BY BARE CONDUCTOR 11
242 AMR AMRELI,TOGARAM RUPRAM 30/06/16 FHO VICTIM WAS BINDING A PLASTIC COVER ON THE ROOF OF TERRACE BY THROWING PRIVATE CABLE WIRE WHOSE BOTH END ARE OPEN, STANDING ON OVER EXTENDED TERRACE OF GROUND FLOOR, AT THAT TIME ONE SIDE OF CABLE WIRE CAME IN CONTACT WITH ADJACENT HT LINE CONDUCTOR AND AT THE SAME TIME OTHER OPEN SIDE OF CABLE WIRE WAS REMAIN IN HIS HAND & ACCIDENT OCCURRED. HT LINE IS PASSING PARALLEL TO SHOP BUILDING. VERTICAL DISTANCE OF HT LINE IS 7 MTR FROM GROUND, 2.2 MTR FROM ACCIDENT PLACE AND LINE IS PASSING ABOVE OVER EXTENDED TERRACE. AS THIS TERRACE IS CONSTRUCTED DANGEROUSLY NEARER TO EXIST 11KV LINE, DISTANCE IS REDUCED FROM 7 MTR TO 2.2MTR FROM ACCIDENT PLACE. SO THIS ACCIDENT OCCURRED DUE TO PERFORMING ABOVE ACTIVITY CARELESSLY HIMSELF Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 12
243 AMR KADIYALI,1-GOAT OF SHRI VASHRAMBHAI SAMATBHAI RATHOD 02/07/16 FA THERE WAS A RAIN AND WIND ON ACCIDENT DAY .LT LINE COATED BROKEN CONDUCTOR WAS FALLEN ON ROAD .COATING OF CONDUCTOR WAS DAMAGED .DUE TO RAIN MANY PUDDLES WERE CREATED ON THAT ROAD .SO DUE TO THIS WHOLE AREA BECOME CONDUCTIVE AND LIVE CURRENT OF BROKEN WIRE CAME IN CONTACT WITH THIS ANIMALS WHEN THEY PASSED FROM ACCIDENT PLACE AND GOT ELECTROCUTED. Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 13
244 AMR KADIYALI,1-GOAT OF SHRI VASHRAMBHAI SAMATBHAI RATHOD 02/07/16 FA THERE WAS A RAIN AND WIND ON ACCIDENT DAY .LT LINE COATED BROKEN CONDUCTOR WAS FALLEN ON ROAD .COATING OF CONDUCTOR WAS DAMAGED .DUE TO RAIN MANY PUDDLES WERE CREATED ON THAT ROAD .SO DUE TO THIS WHOLE AREA BECOME CONDUCTIVE AND LIVE CURRENT OF BROKEN WIRE CAME IN CONTACT WITH THIS ANIMALS WHEN THEY PASSED FROM ACCIDENT PLACE AND GOT ELECTROCUTED. Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 14
245 AMR KADIYALI,1-GOAT OF SHRI VASHRAMBHAI SAMATBHAI RATHOD 02/07/16 FA THERE WAS A RAIN AND WIND ON ACCIDENT DAY .LT LINE COATED BROKEN CONDUCTOR WAS FALLEN ON ROAD .COATING OF CONDUCTOR WAS DAMAGED .DUE TO RAIN MANY PUDDLES WERE CREATED ON THAT ROAD .SO DUE TO THIS WHOLE AREA BECOME CONDUCTIVE AND LIVE CURRENT OF BROKEN WIRE CAME IN CONTACT WITH THIS ANIMALS WHEN THEY PASSED FROM ACCIDENT PLACE AND GOT ELECTROCUTED. Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 15
246 AMR KADIYALI,1-GOAT OF SHRI VASHRAMBHAI SAMATBHAI RATHOD 02/07/16 FA THERE WAS A RAIN AND WIND ON ACCIDENT DAY .LT LINE COATED BROKEN CONDUCTOR WAS FALLEN ON ROAD .COATING OF CONDUCTOR WAS DAMAGED .DUE TO RAIN MANY PUDDLES WERE CREATED ON THAT ROAD .SO DUE TO THIS WHOLE AREA BECOME CONDUCTIVE AND LIVE CURRENT OF BROKEN WIRE CAME IN CONTACT WITH THIS ANIMALS WHEN THEY PASSED FROM ACCIDENT PLACE AND GOT ELECTROCUTED. Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 16
247 AMR KADIYALI,1-SHIP OF SHRI VASHRAMBHAI SAMATBHAI RATHOD 02/07/16 FA THERE WAS A RAIN AND WIND ON ACCIDENT DAY .LT LINE COATED BROKEN CONDUCTOR WAS FALLEN ON ROAD .COATING OF CONDUCTOR WAS DAMAGED .DUE TO RAIN MANY PUDDLES WERE CREATED ON THAT ROAD .SO DUE TO THIS WHOLE AREA BECOME CONDUCTIVE AND LIVE CURRENT OF BROKEN WIRE CAME IN CONTACT WITH THIS ANIMALS WHEN THEY PASSED FROM ACCIDENT PLACE AND GOT ELECTROCUTED. Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 17
248 AMR JUNA VAGHANIYA,1-COW OF SHRI DEVAYATBHAI HARSURBHAI DAV 02/07/16 FA DUE TO WEATHER EFFECT SINGLE PHASE SERVICE WIRE INSULATION DAMAGE AT POLE SIDE. SO, THAT BARE CONDUCTOR OF PHASE WIRE CAME IN CONTACT IN C-CLAMP OF PSC POLE. HENCE, LEAKAGE CURRENT WAS PASSING FROM C-CLAMP TO PSC POLE UP TO GROUND LEVEL. ON THAT DAY DUE TO HEAVY RAIN WHOLE POLE AND SURROUNDING AREA OF LAND WAS WET. AT THAT TIME COW PASSING NEAR PSC POLE AND CAME CONTACT WITH LEAKAGE CURRENT AND ACCIDENT OCCURRED. Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 18
249 AMR LATHI.SANDHYABEN RANJITBHAI KANANI 11/07/16 NFHO AS PER POLICE STATION LETTER NO:-1623 DT-12.7.16 REGARDING NON FATAL ACCIDENT THIS OFFICE VISITED SITE ON DT 12.7.16 AN IDLE 11MTR GIRDER POLE WITH DITACHED GUY IS NEARER TO EXISTING 11KV KERALA AG FEEDER 11KV FEEDER IS ON 8MTR PSC POLE AT A DISTANCE OF APPROXIMATELY 3 FEET FROM IDEAL GIRDER POLE.BOTH VICTIMS WERE PLAYING AROUND IDEAL POLE WITH DITACHED GUY WIRE WHICH CAME IN INDUCTION ZONE OF LIVE 11KV KERALA AG FEEDER LINE MOMENTARLY DUE TO INDUCTION THEY GOT ELECTRIC SHOKED MOMENTARLY AND RESULTED INTO NON FATAL ACCIDENT. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 19
250 AMR LATHI,SANDHYABEN DINESHBHAI KAKADIYA 11/07/16 NFHO AS PER POLICE STATION LETTER NO:-1623 DT-12.7.16 REGARDING NON FATAL ACCIDENT THIS OFFICE VISITED SITE ON DT 12.7.16 AN IDLE 11MTR GIRDER POLE WITH DITACHED GUY IS NEARER TO EXISTING 11KV KERALA AG FEEDER 11KV FEEDER IS ON 8MTR PSC POLE AT A DISTANCE OF APPROXIMATELY 3 FEET FROM IDEAL GIRDER POLE.BOTH VICTIMS WERE PLAYING AROUND IDEAL POLE WITH DITACHED GUY WIRE WHICH CAME IN INDUCTION ZONE OF LIVE 11KV KERALA AG FEEDER LINE MOMENTARLY DUE TO INDUCTION THEY GOT ELECTRIC SHOKED MOMENTARLY AND RESULTED INTO NON FATAL ACCIDENT. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 20
251 AMR RAJAPARA,1-COW OF SHRI PRATAPBHAI JAGMALBHAI VALA 13/07/16 FA WHEN  TWO COW PASSING NEAR JAPA VALU TC OF RAJPARA VILLAGE AT THAT TIME THE BOTH COW CAME IN CONTACT WITH EARTH WIRE OF TC CENTRE GET SHOCKED DUE TO EARTH LEAKAGE CURRENT AND DIED ON THE SPOT THE PARTY REPORTED TO THIS OFFICE ON DATE:-13.07.16,TIME:-16:45 Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 21
252 AMR RAJAPARA,1-COW OF SHRI PRATAPBHAI JAGMALBHAI VALA 13/07/16 FA WHEN  TWO COW PASSING NEAR JAPA VALU TC OF RAJPARA VILLAGE AT THAT TIME THE BOTH COW CAME IN CONTACT WITH EARTH WIRE OF TC CENTRE GET SHOCKED DUE TO EARTH LEAKAGE CURRENT AND DIED ON THE SPOT THE PARTY REPORTED TO THIS OFFICE ON DATE:-13.07.16,TIME:-16:45 Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 22
253 AMR MOTI MOLI,1-BUFFALLO OF UMARBHAI SATARBHAI NAAYA 20/07/16 FA A BUFFALO CAME IN CONTACT WITH BROKEN LT CONDUCTOR HENCE ELECTROCULATED AND DIED ON THE SPOT. THE PARTY REPORTED TO THIS OFFICE ON DT.-20.07.2016, TIME 17:15 PM.   Report yet not received N.A. N.A. LT LINE MAINTENANCE CARRIED OUT 23
254 AMR DAMNAGAR,1-BUFFALLO OF SHRI KALUBHAI POPATBHAI SARVAIYA 22/07/16 FA AS PER SITE VERIFICATION LOAD (RETURN ) SIDE CONDUCTOR OF 11KV HAJIRADHAR JGY SNAPPED FROM DIS INSULATOR AT THAT TIME A BUFFALO  PASSING NEARER TO CONDUCTOR CAME IN DIRECT CONTACT WITH LIVE WIRE AND AS FEEDER WAS CHARGE ON FIRST TRY ANIMAL GET ELECTROCUTED . INCIDENT CAME TO KNOWLEDGE BY LOW VOLTAGE COMPLAIN IN FEEDER. IN THIS FEEDER FIRST 30 LOCATION EARTHLING WERE RE ACTIVATED AND INCIDENT OCCURRED AT LOCATION NO-22 Report yet not received N.A. N.A. HT LINE MAINTENANCE CARRIED OUT 24
255 AMR GHANTVAD,1-BUFFALLO OF BALUBHAI PITHABHAI VANJA 26/07/16 FA WHEN  TWO BUFFALO’S PASSING NEAR GITABEN JESHINGBHAI BARAD AG  TC OF GHATVAD VILLAGE AT THAT TIME THE BOTH BUFFALO’S CAME IN CONTACT WITH EARTH WIRE OF TC CENTRE GET SHOCKED AND DIED ON THE SPOT THE PARTY REPORTED TO THIS OFFICE ON DATE:-26.07.16,TIME:-15:15 Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 25
256 AMR GHANTVAD,1-BUFFALLO OF BALUBHAI PITHABHAI VANJA 26/07/16 FA WHEN  TWO BUFFALO’S PASSING NEAR GITABEN JESHINGBHAI BARAD AG  TC OF GHATVAD VILLAGE AT THAT TIME THE BOTH BUFFALO’S CAME IN CONTACT WITH EARTH WIRE OF TC CENTRE GET SHOCKED AND DIED ON THE SPOT THE PARTY REPORTED TO THIS OFFICE ON DATE:-26.07.16,TIME:-15:15 Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 26
257 AMR DEVALAKI,1-COW OF GANDABHAI OGHADBHAI TOLIYA 30/07/16 FA ACCIDENT PLACE WAS DP OF 100 KVA AG TC GROUP. OWNER WITH HIS CATTLES RETURNING TOWARDS VILLAGE AT THAT TIME THIS COW PASSED UNDER TRANSFORMER DP AND COMES IN CONTACT WITH EARTH UNBALANCED NEUTRAL EARTH CURRENT AND AS SURROUNDING WAS WET DUE TO RAIN FALLING AT THAT TIME AND ANIMAL GOT ELECTROCUTED AND DIED ON THE SPOT WITHIN 5 TO 6 SECOND  Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 27
258 AMR KATHROTA,1-BUFFALLO OF SHRI KISHANBHAI DUNGARBHAI MORVADIYA 31/07/16 FA AS PER UNKNOWN TELEPHONIC INFORMATION WHEN WE INVESTIGATE THE MATTER WE FOUND THAT LT ABC CABLE FIRED AT ACCIDENT PLACE, DUE TO HEAVY  RAIN AND WIND ACCIDENTLY  TOUCHED  WITH G I WIRE WHICH WAS PROVIDED ON POLE OF TRANSFORMER DP. SO LEAKAGE CURRENT RUNNING THROUGH G I WIRE TO GROUND LEVEL. DUE TO HEAVY RAIN SURROUNDING AREA OF TRANSFORMER DP BECOME WET. SO WHEN BUFFALO PASSED NEARER TO THIS TRANSFORMER CENTER CAME IN CONTACT WITH LEAKAGE CURRENT AND GOT ELECTROCULLATED Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 28
259 AMR ZUDVADLI,1-BUFFALLO OD SHRI ARJANBHAI DAYABHAI DABHI 08/08/16 FA ON THE DAY OF ACCIDENT THERE WAS A RAIN & SURROUNDING OF TC WAS WET DUE TO THIS RAIN .BUFFALLOW PASSING NEARERE TO FATSAR ROAD AG TC OF VILLAGE ZUDVADALI, AT THAT TIME THIS BUFFALLO CAME IN CONTACT WITH LEAKAGE CURRENT OF TRANSFORMER THREW EARTH WIRE OF TC CENTER VIA WET SURROUNIG & GET SHOCHED AND DEAD ON THE SPOT. THE PARTY REPOETED TO THIS OFFICE ON DTD:-08.08.16 TIME:-1:30 Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 29
260 AMR MUNJIYASAR,1-BUFFALLO OF SHRI PARVAINBHAI CHHAGANBHAI DUDHAT 10/08/16 FA ACCIDENT TOOK PLACE AT DP OF 63 KVA TC . WHILE BUFFELOW PASSING UNDER THE TRANSFORMER DP AND AND CAME IN CONTACT WITH LEAKAGE CURRENT WHIS IS PASSING THROUGH G.I WIRE AND AS SURROUNDING WAS WET DUE TO RAIN FALLING AT THAT TIME AND GOT ELECTROCUTED AND DIED ON SAME TIME. Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 30
261 AMR DUDHALA,PRAVINBHAI SURABHAI SOLANKI(FH) 16/08/16 FHO AS PER TELEPHONIC INFORMATION RECEIVE ON DT. 17.08.2016 AT 0:30 HRS BY UNKNOWN PERSON AND ACCORDINGLY SITE VISITED STATEMENT OF CO PERSON TAKEN AND INVESTIGATE THE MATTER. THE VICTIMS WERE TRY TO REACH ON TERRACE OF COMMUNITY HALL BY CLIMBING WINDOW CHHAJA (AS NO STAIR CASE AVAILABLE) WHEN ALL ARE STANDING ON CHHAJA (VERTICAL DISTANCE OF 11 KV LINE FROM CHHAJA = 3.2 MTR.) SUDDENLY ALL ARE FAIL DOWN TO GROUND. AS PER STATEMENT OF TWO LIVE PERSONS THEY FILL TIGLING AND FAIL DOWN AND OUT OF THREE SHRI NARANBHAI KESHUBHAI RANOLIYA WAS STAND UP AFTER SOME TIMES AND  OTHER TWO ARE IN COMA SO HE CALL THE NEARBY  HOUSE PERSON AND ALL GO TO DHARI  GOVT. HOSPITAL WHERE  SHRI PRAVINBHAI SURABHAI SOLANKI DECLARE AS DEAD AND OTHER TWO ARE REFER TO GOVT. HOSPITAL AMARELI. VICTIM 1 GOT SERIOUS INJURIES TO HEAD (PRAVINBHAI SURABHAI SOLANKI ) AS PER OUR INVESTIGATION. ALSO NOTED THAT , AS PER LOG SHEET  RECORD OF 66 KV DUDHALA S/S FOR 11 KV JALJIVADI  JGY NO TRIPING OBSERVED DURING 10 PM TO 8 AM NEXT DAY AND NO EVIDENCE FOUND  FOR ELECTRICAL AT SITE HOWEVER PM REPORT IS AWAITED HENCE ACTUAL DEATH OF CAUSE NOT FOUND. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 31
262 AMR DUDHALA,SURESHBHAI JASABHAI DUBANIYA(NFH) 16/08/16 NFHO AS PER TELEPHONIC INFORMATION RECEIVE ON DT. 17.08.2016 AT 0:30 HRS BY UNKNOWN PERSON AND ACCORDINGLY SITE VISITED STATEMENT OF CO PERSON TAKEN AND INVESTIGATE THE MATTER. THE VICTIMS WERE TRY TO REACH ON TERRACE OF COMMUNITY HALL BY CLIMBING WINDOW CHHAJA (AS NO STAIR CASE AVAILABLE) WHEN ALL ARE STANDING ON CHHAJA (VERTICAL DISTANCE OF 11 KV LINE FROM CHHAJA = 3.2 MTR.) SUDDENLY ALL ARE FAIL DOWN TO GROUND. AS PER STATEMENT OF TWO LIVE PERSONS THEY FILL TIGLING AND FAIL DOWN AND OUT OF THREE SHRI NARANBHAI KESHUBHAI RANOLIYA WAS STAND UP AFTER SOME TIMES AND  OTHER TWO ARE IN COMA SO HE CALL THE NEARBY  HOUSE PERSON AND ALL GO TO DHARI  GOVT. HOSPITAL WHERE  SHRI PRAVINBHAI SURABHAI SOLANKI DECLARE AS DEAD AND OTHER TWO ARE REFER TO GOVT. HOSPITAL AMARELI. VICTIM 1 GOT SERIOUS INJURIES TO HEAD (PRAVINBHAI SURABHAI SOLANKI ) AS PER OUR INVESTIGATION. ALSO NOTED THAT , AS PER LOG SHEET  RECORD OF 66 KV DUDHALA S/S FOR 11 KV JALJIVADI  JGY NO TRIPING OBSERVED DURING 10 PM TO 8 AM NEXT DAY AND NO EVIDENCE FOUND  FOR ELECTRICAL AT SITE HOWEVER PM REPORT IS AWAITED HENCE ACTUAL DEATH OF CAUSE NOT FOUND. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 32
263 AMR NARANBHAI KESHUBHAI RANOLIYA(NFH)-DUDHALA 16/08/16 NFHO AS PER TELEPHONIC INFORMATION RECEIVE ON DT. 17.08.2016 AT 0:30 HRS BY UNKNOWN PERSON AND ACCORDINGLY SITE VISITED STATEMENT OF CO PERSON TAKEN AND INVESTIGATE THE MATTER. THE VICTIMS WERE TRY TO REACH ON TERRACE OF COMMUNITY HALL BY CLIMBING WINDOW CHHAJA (AS NO STAIR CASE AVAILABLE) WHEN ALL ARE STANDING ON CHHAJA (VERTICAL DISTANCE OF 11 KV LINE FROM CHHAJA = 3.2 MTR.) SUDDENLY ALL ARE FAIL DOWN TO GROUND. AS PER STATEMENT OF TWO LIVE PERSONS THEY FILL TIGLING AND FAIL DOWN AND OUT OF THREE SHRI NARANBHAI KESHUBHAI RANOLIYA WAS STAND UP AFTER SOME TIMES AND  OTHER TWO ARE IN COMA SO HE CALL THE NEARBY  HOUSE PERSON AND ALL GO TO DHARI  GOVT. HOSPITAL WHERE  SHRI PRAVINBHAI SURABHAI SOLANKI DECLARE AS DEAD AND OTHER TWO ARE REFER TO GOVT. HOSPITAL AMARELI. VICTIM 1 GOT SERIOUS INJURIES TO HEAD (PRAVINBHAI SURABHAI SOLANKI ) AS PER OUR INVESTIGATION. ALSO NOTED THAT , AS PER LOG SHEET  RECORD OF 66 KV DUDHALA S/S FOR 11 KV JALJIVADI  JGY NO TRIPING OBSERVED DURING 10 PM TO 8 AM NEXT DAY AND NO EVIDENCE FOUND  FOR ELECTRICAL AT SITE HOWEVER PM REPORT IS AWAITED HENCE ACTUAL DEATH OF CAUSE NOT FOUND. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 33
264 AMR JAFRABAD,VAGHJIBHAI KANABHAI BARAIYA 17/08/16 NFHO WELCOME FUNCTION WAS ARRANGED FOR NEW SACHIVE, AT THAT TIME OF ACCIDENT CRACKERS LIKE ROCKET GOES TOWARDS THE SKY AND ACCIDENTALLY TOUCH LIVE HT (COPPER) CONDUCTOR RESULTING IN HEAVY EXPLOSION THUS BROKEN IT FROM DISC H/W END AND LIVE BROKEN CONDUCTOR FALLON DOWN AND REMAIN IN AIR WITH SUPPORT OF FESTOON PROVIDED FOR DECORATION. VICTIM ACCIDENTALLY COMES IN CONTACT WITH LIVE CONDUCTOR MOMENTARY AND GOT ELECTROCUTED. NO TRIPPING RECORDED IN FEEDER DURING ACCIDENT TIME AS CONDUCTOR WAS IN AIR AND MOMENTARY GROUNDED THREW VICTIM, HENCE REQUIRED FAULT CURRENT FOR SPECIFIED TIME PERIOD AND SOLID GROUND WAS NOT GENERATED TO TRIP THE RELAY. Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 34
265 AMR VAVDIROAD,SHRI K.B.GAMETI(EA) 10/09/16 NFHD AS PER REPORTED BY LI THAT A NON-FATAL HUMAN ELECTRICAL DEPARTMENT ACCIDENT IN NETWORK OCCURRED DURING RELEASING A NEW AG CONNECTION OF ARUNBHAI PARSOTTAMBHAI THUMMAR  AT VILLAGE : VAVDI ROAD
             ON DATE 10.09.16 WORK OF PROVIDING JUMPER TO NEW AG. COON WITH ROUTINE FAULT WAS GIVEN TO VICTIM WITH 1 ALM AND 2 APP. LM THEN THEY TO GATHER ALL ON THEIR PRIVATE VEHICLES WENT FOR THEIR WORK AND ON THE WAY DECIDED THAT WORK BELONGS TO VAVDI ROAD VILLAGE WILL CARRIED OUT BY VICTIM WITH APP. LM AND FAULTS OF VILLAGE TALALI WITH CARRIED OUT BY ALM WITH 1 APP. LM SO AFTER DECIDING ABOVE ALL LC OF 11 KV TALALI AG & 11 KV VAVDI AG FEEDER WAS TAKEN BY ALM AS WORK BELONG TO THIS FEEDER ONLY. DURING SITE VISIT FOUND THAT VICTIM CLIME ON 11 KV BADANPUR AG WHILE LINE SORT WORK WAS IN PROGRESS BY APP. LM AND GOT SHOCK. NAME OF RELEVANT FEEDER WAS PROVIDED ON POLE
Report yet not received N.A. N.A. AWARENESS AMONG  DEPARTMENTAL STAFF REGARDING SAFETY IN EVERY SAFETY MEETING 35
266 AMR BHADER,1-BUFFALLO OF TAKHUBHAI BHIMBHAI BASIYA 19/09/16 FA DUE TO HEAVY RAIN AND WIND LT JUMPER  BURNED OUT AND ACCIDENTLY  TOUCHED WITH C CLAMP AND AS GI WIRE PROVIDED ON POLE FOR EARTHING, GI WIRE BECAME LIVE. DUE TO HEAVY RAIN WATER WAS CONTINUALLY RUNNING FROM SURROUNDING OF POLE AT THE TIME OF ACCIDENT. SO WHEN BUFFALO PASSED NEARER TO THIS LT POLE, CAME IN CONTACT WITH LEAKAGE CURRENT VIA RAINY WATER AND ACCIDENT OCCURRED. Report yet not received N.A. N.A. HT LINE MAINTENANCE CARRIED OUT 36
267 AMR ZUDVADLI,1-BUFFALLO OF RAJNIKANTBHAI VALLABHBHAI DOAMDIYA 20/09/16 FA RAIN WAS FALLING ON ACCIDENT PLACE I.E.TC CENTRE WAS FILED BY RAINY WATER. WHEN A BUFFALO WAS PASSING NEARER TO THIS TC, CAME IN CONTACT WITH LEAKAGE CURRENT OF TRANSFORMER CENTRE VIA RAINY WATER AND ELECTROCUTED. Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 37
268 AMR NANI VADAL,1-BUFFALLO OF SHRI DUDABHAI GOBARBHAI KATARIYA 24/09/16 FA ON DAY OF ACCIDENT THE LAND SURROUNDING TO TC IS WET DUE TO RAINY SEASON , BUFFALO   WAS CRAWLING NEARER TO TRANSFORMER CENTER AT THAT TIME COME IN CONTACT WITH EARTHING LEAKAGE CURRENT OF TC VIA WET SURROUNDING & GOT ELECTROCUTED. Report yet not received N.A. N.A. TRANSFORMER MAINTENANCE CARRIED OUT 38
269 AMR VAVDI,RANJITBHAI BADRUBHAI JEBALIYA 27/09/16 FHO AS INFORMED BY POLICE STATION ON DATE 28.09.16 AT 12.30 SITE IS VISITED AT 16.30 PM AND IT IS OBSERVED THAT VICTIM WORKING AT FARM OF SHRI MANSUKHBHAI KANJIBHAI BHARAD WHERE PGVCL CONN.NO-838270002575 CONN.NAME- SHRI MANSUKHBHAI KANJIBHAI BHARAD IS EXISTING AND POWER SUPPLIED FROM TRANSFORMER CENTRE. AT SITE R PHASE OF SERVICE WIRE IS RECENTLY SHARPENED BUT NOT CONNECTED WITH LT STUD AND YB PHASE PHASE CONNECTED WITH LT STUD. BLACK SPOT FOUND ON 11 KV BUSHING OF TC AND EARTHING WIRE.AS PER STATEMENT OF CO – WORKER SHRI CHAMPUBHAI MAMAIYABHAI JEBALIYA ,HE HARD HIGH SPARKING VOICE AND SO THAT HE RUN TOWARDS VOICE WHERE WHERE  HE SEEN THAT VICTIM WAS LYING ON GROUND IN COMMA POSITION SO THAT HE IMMEDIATELY CALLED NEARBY  PERSONS AND TAKE HIM TO CHALALA GOVT HOSPITAL BY 108 AMBULANCE WHERE HE WAS  DECLARED AS DEAD.VERIFYING LOGSHEET OF 66 KV CHALALA SS TRIPPING WAS RECORDED AT THE TIME 17.00 PM DATED 27.9.16 SO INFORMATION COLLECTED TILL NOW AND PRIMARY INVESTIGATION DONE, VICTIM MAY DOING UNAUTHORIZED ELECTRIC WORK ON TC AND ELECTROCUTED. FURTHER DETAIL INVESTIGATION IS IN PROGRESS AND PM REPORT AWAITING Report yet not received N.A. N.A. AWARENESS AMONG GENERAL PUBLIC REGARDING SAFETY IN EVERY KHEDUT SHIBIR/GRAMSABHA 39
270 SNR VILL- JAMWADI   AMITBHAI KANJIBHAI CHAUHAN 19/04/16 FHO Victim on the cabin of truck for cover the goods when truck driver park the truck exactly under the 11kv line and getting
live contact with conductor.
Report yet not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 1
271 SNR VILL-JEGADAVA  AND OWNER  OF BUFFALO SHRI AMARSHIBHAI LAXMANBHAI RATHOD 08/05/16 FA AT VILLAGE JEGADVA ,  IN  VILLAGE TRANSFORMER   ABC LT CABLE WAS EXISTING   FROM LT SIDE BUSHING TO LT POLE .  THEN ONE  PHASE OF   CABLE WAS DAMAGED, AND JOINT WAS MADE, WHICH WAS OPEN. THE SAID BUFALLO DIRECTLY CAME IN CONTACT WITH  CABLE JOINT, AND DIED. DETAILED INVESTIGATION WILL BE DONE & REPORTED. Report yet not received NA NA Cable replaced. 2
272 SNR VILL-VISAVAD AND OWNER  OF BUFFALO SHRI KHENGARBHAI RATUBHAI GOHIL 18/05/16 FA ELECTRICAL ACCTDENT OCCURRED TO oNE BUFFALOW DUE To SNAPPING oF oNE CONDUCTOR oF 11KV VISAVADI
AG FEEDER AND BUFFALOW WAS PASSING THERE AND TOUCH BODY TO LIVE CONDUCTOR AND ELECTROCUTED
Report yet not received NA NA Necessary maintenance done 3
273 SNR VILL- THAN  MAYUR VALJIBHA MAKWANA 31/05/16 NFHD Non Fatal Mechanical Accident Occurred When Victim Start to Climb on the PSC POLE,  in Second SteP of the Pole, Victim's Right Foot Slip inside the Pole Gape and Primary Treatment, Bone of Right Foot Damage. Report yet not received NA NA Instruction given to all line staff that proper care taken while climbing on  Pole. 4
274 SNR VILL - DASADA  DAKSHIT BHIKHABHAI RABARI 03/06/16 FHO :A ELECTRICAL OUTSIDER HUMAN FATAL ACCIDENT OCCURRED TO DAKSHIT BHAIKHABHAI RABARI AGE ABOUT 13
YEARS oN DATE 03.06.16 AT 1o ro 10:30 AM AT GoKULNAGAR(NAGAWADA VASAHAT) VILLAGE AS VICTIM WAS PLAYING ON TARRACE OF VIKRAMBHAI JAGABHAI RABARI AND BY ANY MEANS TOUCH TO 11KV GHASPUR JGY LINE
WHICH PASSING 4FT AWAY AND 6FT ABOVE BEHIND TARRACE OF VIKRAMBHAI JAGABHAI RABARI AND GOT ELECTROCUTED.
Report yet not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 5
275 SNR BECHARBHAI DEVUBHAI SOLANKI 28/06/16 FA AT VILLAGE RAJSITAPUR, DUE TO RAINY SEASON AND WET ATMOSPHERE, MOMENTORY LEAKAGE CURENT PASSED THROUGH THE EARTHING WIRE OF TC AND THE VICTIM COW PASSED NEAR THE TC TO EAT GARBAGE & GOT ELECTROCUTED AT EARTHING OF TC. Report yet not received NA NA EARTHING REACTIVATION DONE 6
276 SNR VILL- SURENDRANAGAR AND OWNER  OF COW  SHRI MAFABHAI SINDHABHAI SINDHGAV 13/07/16 FA Due to rain wire suppling power to Street Light from LT Line burnt and touch to iron pole. COW came contact with iron pole and  get socked and died. Report yet not received NA NA NEW WIRING OF STREET LIGHT DONE BY N P  7
277 SNR VILL-ZINZUWADA AND OWNER  OF COW SHRI DALPATSIH BHIKHUBHA ZALA 15/07/16 FA Due to insulation of AB cable is damged on LT ple & phase wire become open which was came in direct contact of LT cross arm so leakage current passed throug LT cross arm through GI wire throug the body of COW which passing near this pole and came in contact with GI wire and electrocuted. Report yet not received NA NA AB CABLE REPLACED  8
278 SNR VILL- KERALA AND OWNER  OF BUFFALO SHRI BHARVAD NANUBHAI SAGRAMBHAI 18/07/16 FA A fatal accident ocuured due to a BUFFELOW while crossing farm guard fencing and farmer has carrying lunger from PSC pole through galvenizing fencing and insulation of that lunger wire has been flash over and touch with galvenizingfencing guard, buffelow came in contact with fancing and electrocuted. Report yet not received NA NA LUNGER REMOVED AND FIR DONE 9
279 SNR VILL- HARIPAR AND OWNER  OF BUFFALO SHRI GHANSHYAMBHAI BHIKHBHAI PATEL 18/07/16 FA A fatal accident occurred to BUFFELOW during itching, when it was pasing near transformer cetre, its head fixed to PVC pipe of earthin wire of transformer centre by its horn and got electrocuted. Report yet not received NA NA EARTHING REACTIVATION DONE 10
280 SNR VILL- ISHDHRA AJAYYBHAI KALUBHAI SINGOD 27/07/16 NFHO Non fatal outsider electrical accident occurred due to victim was climed on tree branch suddenly tree branch bend dowards to our HT liine passing near the tree due to weight of victim and he came in catact with line & got electric shock. Report yet not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 11
281 SNR VILL- DHG  GANGABEN KANJIBHAI MAKVANA 29/07/16 FHO According to eyewitness statement victim was filling water from underground water tank suddenly she lost his balance and catch the girder for suporting the body and on that girder pole of LT streetlight fixture is direct and joint is open which came in contact with girder pole and victm electrocuted. Report yet not received NA NA NEW WIRING OF STREET LIGHT DONE BY N P  12
282 SNR VILL- JORAVARNAGAR BHAGIRATHSIH V RATHOD 06/04/16 NFHD A non fatal electrical accident occurs to victim, while he was working on LT Network line through the tower ladder. 11 KV K C Mill feeder was passing nearby this LT network. When victim was trying to remove the twisted LT conductor suddenly he was come in induction zone of 11 kV kc mill passing nearby this LT line. After got momentary jerk he lost his balance from the tower ladder and fell down and thus accident took place.   Report yet not received NA NA Instruction given to all line staff that proper care taken while climbing on  Pole. 13
283 SNR  VILL- DHG AND OWNER  OF COW SHRI RAVIJIBHAI LAKHABHAI BHARVAD 08/09/16 FA Accident  occurred to animal due to  short street light fixture came in contact with GI wire through LT cross arm, leakage current passes through fixture to LT cross arm to the earth wire due to heavy rain  & wet condition and hence current passed through animals body. Earthling pvc pipe provided. Report yet not received NA NA NEW WIRING OF STREET LIGHT DONE BY N P  14
284 SNR VILL-RAJSITAPUR AND OWNER  OF TWO BUFFALO SHRI HARESHBHAI DHIRUBHAI DESAI 23/08/16 FA AT VILLAGE RAJSITAPUR, ON GUY DARWAJA TC’s LT LINE, PHASE OF SERVICE LINE BECOME OPEN, LEAKAGE CURRENT PASSED THROUGH FABRICATION ,THROUGH EARTHING WIRE CONNECTED TO FABRICATION OF POLE AND 2 NOS BUFFALOS PASSED NEAR THE POLE AND GOT ELECROCUTED. Report yet not received NA NA SERVICE WIRW REPLACED 15
285 SNR VILL-RAJSITAPUR AND OWNER  OF TWO BUFFALO SHRI HARESHBHAI DHIRUBHAI DESAI 23/08/16 FA AT VILLAGE RAJSITAPUR, ON GUY DARWAJA TC’s LT LINE, PHASE OF SERVICE LINE BECOME OPEN, LEAKAGE CURRENT PASSED THROUGH FABRICATION ,THROUGH EARTHING WIRE CONNECTED TO FABRICATION OF POLE AND 2 NOS BUFFALOS PASSED NEAR THE POLE AND GOT ELECROCUTED. Report yet not received NA NA SERVICE WIRW REPLACED 16
286 SNR VILL- PIPLA AND OWNER  OF COW SHRI UGRIBEN MELABHAI MALKIYA 25/08/16 FA A ftal animal accident occurred due to service wire was burnt and live part of service wire came in contact with fabrication of earthing which was connected to earthing wire so leakage current passed through the earthing wire, due to water logging area near the pole cow is passing from the water logged and current passing through its body and electrocuted. Report yet not received NA NA SERVICE WIRW REPLACED 17
287 SNR VILL - REAMDEVGADH AND OWNER  OF BUFFALO SHRI DILIPBHAI GHANSHYAMBHAI MASANI 09/07/16 FA Insulation of AB cable was damaged and live part of AB cable came in ci=ontact with fbrication and leakage current passed through fabrication in GI wire and due to heavy rain in last night land surrounding guy was wet and buffalo pasing from this area and electrocuted. Report yet not received NA NA AB CABLE REPLACED  18
                   
2ND Half                  
1 RCC Rajkot-Jigneshbhai Amrutlal Kadivar                            18.10.16 FHO A victim may got electrocute/induction when he was lifted 20 ft steel pipe from factory ground to first floor at that time. Steel pipe might be came in contact with 11 KV Shivam Feeder.  Victim  breach  safety & Ele supply regulation  2010 - clause No 64  work under proper supervision Victim himself responsible Victim himself responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 1 Victim  breach  safety & Ele supply regulation  2010 - clause No 64  work under proper supervision Victim himself responsible Victim himself responsible Public awareness
2 RCC Rajkot-Imranbhai Ranmalbhai Sama  18.10.17 NFHO A victim may got electrocute/induction when he was lifted 20 ft steel pipe from factory ground to first floor at that time. Steel pipe might be came in contact with 11 KV Shivam Feeder.   Victim  breach  safety & Ele supply regulation  2010 - clause No 64  work under proper supervision Victim himself responsible Victim himself responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 2  Victim  breach  safety & Ele supply regulation  2010 - clause No 64  work under proper supervision Victim himself responsible Victim himself responsible Public awareness
3 RCC Navagam-Mukeshbhai Mohanbhai Dudhat  13.10.16 FHO "This incident came to known from Kuvadava Road Police Station. On site visit  and eye witness it concluded that the victim while supervising the construction, which is under the 11 KV line, lost his balance and accidentally came in contact with 11 KV line and fall down on ground & had head injury met with non-fatal accident. He was admitted to Sterling Hospital, Rajkot, where he died on 28.10.2016 thus non-fatal accident converted to fatal accident.           

The victim him self had applied for line shifting and has paid line shifting charge on 08.10.2016 & was inform  in estimate to do any construction work near or beneath the electric line after it is shifted . Detail investigation will be sent soon."
 Victim  breach  safety & Ele supply regulation  2010 - clause No 61   Victim and DE-Madhapar responsible Victim himself responsible Shifting of line to maintain clearance & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. Notice Issue to remove unauthorised construction work 3  Victim  breach  safety & Ele supply regulation  2010 - clause No 61   Victim and DE-Madhapar responsible Shifting of line to maintain clearance  Public awareness and Notice Issue to remove unauthorised construction work
4 RCC Rajkot-Shravannag Shukarunag 15.03.16 FHO As per site situation / site Rojkam / co-worker statement / statement of owner of premises / details regarding tripping from these supporting evidences it is not clear that the accident occurred due to electric shock. But, as per PM report of victim, it is mentioned that reason for death “Shock due to electricity current burn”. As per CEI report received, victim came in induction zone of 11 KV line which passing nearby premises during doing construction work using aluminium plate in hand and got electrocuted and met with fatal human accident.  House Holder  breach  safety & Ele supply regulation 2010 - clause No 58 and Victim breach  safety & Ele supply regulation  2010 - clause No 64   If victim observed safety & Ele supply regulation 2010- clause no 64 accident could be avoided. House Holder & Victim himself responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. and Notice Issue to remove unauthorised construction work 4  House Holder  breach  safety & Ele supply regulation 2010 - clause No 58 and Victim breach  safety & Ele supply regulation  2010 - clause No 64   If victim observed safety & Ele supply regulation 2010- clause no 64 accident could be avoided. House Holder & Victim himself responsible Public awareness and Notice Issue to remove unauthorised construction work
5 RCC Rajkot-Nikunj Chhabildas Gondaliya 22.09.16 FHO The victim was fallen down on ground from the terrace of Jay Murlidhar house. 11 KV Gandhigram feeder line is passing near/ along the terrace of Jay Murlidhar house, while the victim falling from the terrace, he might have come in contact with guard wire or conductor.  House Holder  breach  safety & Ele supply regulation 2010 - clause No 61  If house holder observed safety & Ele supply regulation 2010- clause no 61 accident could be avoided. House Holder responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. and Notice Issue to remove unauthorised construction work 5  House Holder  breach  safety & Ele supply regulation 2010 - clause No 61  If house holder observed safety & Ele supply regulation 2010- clause no 61 accident could be avoided. House Holder responsible Public awareness and Notice Issue to remove unauthorised construction work
6 RCC Rajkot-Pruthvi Rameshbhai Sarvaiya 08.01.17 FHO A victim trying to catch kite from 11 KV line by using approximately 10 ft long iron rod from his terrace. Hence when iron rod came in contact with 11 KV line, victim electrocuted due to current passes through iron rod. Victim breach safety & Ele supply regulation   2010 - clause No 64.   If victim observed safety & Ele supply regulation 2010- clause no 64 accident could be avoided. Victim himself responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 6 Victim breach safety & Ele supply regulation   2010 - clause No 64.   If victim observed safety & Ele supply regulation 2010- clause no 64 accident could be avoided. Victim himself responsible Public awareness
7 RCC Rajkot-Vichiyabhai Ramanbhai Bhil  10.02.17 NFHO About these accident come to know from police station. The non-fatal accident was occurred when victim – labour of contractor Shri. Rajubhai Gohel is doing new irregular construction work on a terrace of house of Prakashbhai Sejpal & accidentally touch 11 KV HT line conductor. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. and Notice Issue to remove illegal construction work 7 Report yet not received NA NA Public awareness and Notice Issue to remove illegal construction work
8 RCC Rajkot-Hitesh Girdharbhai Parmar 23.02.17 FHO About accident come to know from police station. As per site visit and panch rojkam it concluded that victim– labour of   contractor Shri. Jitendrabhai Harjivanbhai Nadiyapara doing construction work on terrace of bathroom on first floor of house of Poonam Devlopers. While doing so, levelling work with the help of 5.5 ft aluminium section strip, this strip come in induction zone of conductor of 11 KV Alap feeder which was about 2 feet away from the wall of new construction works and got electric shock and fell down on ground level and was admitted to Giriraj Hospital and then to civil hospital where he declare dead thus met with fatal accident. Inspecting aluminium strip no black spot found on aluminium strip nor on wire of 11 KV. No tripping observed on 11 KV Alap feeder at time accident.
For construction work temporary connection no. 986 obtain from Nana Mava s/dn. This accident occurred due to irregular construction without keeping safe distance from the existing 11 KV line conductor.
Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. and Notice Issue to remove illegal construction work 8 Report yet not received NA NA Public awareness and Notice Issue to remove illegal construction work
9 RCC Rajkot-Dhirubhai Keshubhai Jotaniya 09.03.17 FHO About accident come to know from police department on dt.10.03.17.from site visit it found that victim while doing construction on first floor. For this he was lifting iron rod("khilasali")of about 12 ft long from ground floor to first floor while that tail end of iron rod come in touch with live conductor of 11 KV Omnagar feeder and got electric shock and met with fatal accident. Horizontal distance of conductor from the wall is 9 feet. Tripping was observed on 11 KV Omnagar feeder at time of accident. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. and Notice Issue to remove unauthorised construction work 9 Report yet not received NA NA Public awareness and Notice Issue to remove unauthorised construction work
10 RRC Kotda Sangani         Girish Devsi Rathod 03.10.16 FHO Intimation received from  police department on dated 13/10/2016 and site is visited on date 14/10/2016. As per victim’s father statement taken and observations during site visit we found that accident occurred due to illegal additional   construction of residential premise near 11 kv Kotda JGY FDR.  The owner of house is  Shree Devshibhai Bhimabhai Rathod(victim’s father ). The victim was standing on the terrace   of this single storey premises and while he was splashing water on newly constructed parapet wall and other new construction with the help of tumbler by hand and came in induction zone of 11 kv feeder. So got electrocuted. Further investigation is under progess. Victim himself is responsible for said accident. N.A Victim himself responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly & Notice issued to concern. 1 Victim himself is responsible for said accident. N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly & NOTICE ISSUED TO CONCERN
11 RRC Jam Kandorna -2         Rajendrasinh Ratansinh Rajput(Contractor Person) 08.10.16 FHO This fatal accident occurred to the above person(victim) of contractor M/s Sati Aai Krupa enterprise, when he had climbed to a live 11 kv Dadar ag line pole near road cross before completing of L C procedure.
A new JGY link line was being erected for new 66 kv Gundasari s/s .This new JGY link line route is crossing over the existing road cross of 11 kv Dadar AG feeder. To make crossing of these two lines, pole are erected on both sides of existing 11 kv Dadar ag feeder road cross. To carry out this new JGY link line work, two line clear permits had been asked for 11 kv Baradiya ag feeder ( at 3:28:16 pm) and for 11 kv Dadar ag feeder ( at 3:33:30 pm) by the PGVCL's supervisor Shri V.J.Bhokiya, EA (VS) by SMS who was present at site. Mr. Bhokiya had received an SMS from 66 kv Chitravd s/s for the LC no 6431 for 11 l(/ Baradiya ag feeder (at 3:35:30pm),but the SMS of LC of 1'1 kv Dadar ag feeder was pending to be received. Mean while, at that time, the victim climbed to the pole without taking confirmation of both LCs, without observing safety rules (viz line discharge, earthing and making short of 3 phases) and without using safety gadgets (viz safety belt& helmet) and touched the tive wire of 11 kv Dadar AG feeder and spark occurred and fall down on ground.( A TT in Earth fault relay is recorded on 11 Kv DadarAg feeder panel at 15:30 hrs, SMS for LC of 11 KV DadarAg feeder received at 3:48:07pm).lmmediately, the victim was taken to the Jamkandorna civil hospital and then after Dhoraji civil hospital where the probable cause of death is found due to cardio-respiratory arrest due to ele$rocution. pM report is awaited.
Victim himself & PGVCL both is responsible for said accident. NA Victim himself responsible Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules. 2 Report yet not received N.A N.A Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules.
12 RRC Navagadh          Soniya(Sunil) Nanajibhai Rathava(Alm) 16.10.16 NFHD    Accident occurred to the victim when the victim with LM Sh. Nanjibhai Sutariya went to attend a fault of a W/W TC lug of 11KV side Y phase. The TC is on 11KV Pithdia JGY feeder. They have taken LC of 11 KV Jepur JGY feeder instead of 11 KV Pithdia JGY feeder. The victim climbed on TC pole from LT side wearing hand gloves and came in contact of LT and induction zone of live 11 KV line. Immediately he was taken to Hospital at Navagadh and then after to Sterling Hospital Rajkot. The matter is under further investigation Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line. 3 Report yet not received N.A N.A Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules.
13 RRC Jam Kandorna -1           Babubhai Z. Katara (Ea) 02.11.16 NFHD Accident occurred to the victim when the victim with
shri. H D Makwana, L.M.went to attend a fault of neutral missing on AG connection of Madhubhai
Nagjibhai Valu TC.
They have cut the D,O. fuse element of two phases and remaining third phase D.O. fuse
element was remained unremoved with hanging position from upper side of live 11 k.v. line with
gap of approx 2 inch from lower side Gontact. The victim climbed on T.C. pole from H.T. side
without using safety gadgets and touch'the jumper connecting DT phase and D.O. lower contact,
thus indirectly came in contact of induction zone of live 11K.V. line. Immediately he was taken to
hospital at jamkandorna and then after to Dr.Chikhaliiya's Hospital at junagadh. The matter is
under further investigation.
Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line. 4 Report yet not received N.A N.A Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules.
14 RRC Vichhiya      Vishlbhai Pravinbhai Rangpar 11.11.16 FHO As information got from police station on DT: 15.11.2016,DE-Vinchhiya rushed at site, as per eye witness statement Main service of the AG connection of Savshibhai Popatbhai Rangapara (con. No. 81821003373) is burned and fallen down on the earth at that time Victim was passing there and he came in contact with burned service and he got electric shock. In this connection no any leakage current found in PGVCL network and in load side wiring protective device like MCB/ELCB is not provided. Burnt service is taken under custody for forensic Lab Examination. Further investigation is under progress. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 5 Report yet not received N.A N.A Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules.
15 RRC Vichhiya         Sanjaybhai Ranchhodbhai Taviya 14.11.16 FHO As per site visit and statement of eye witness, victim Sh. Sanjaybhai Ranchhodbhai Taviya was doing unauthorized work at nearby 10KVA Transformer of Sh. Devabhai Rupabhai Taviya (con.no:81820004937),At that time he came in contact with live 11KV Bushing and got electric shock. Service wire of this connection found ok and not any leakage current found from PGVCL network.Further investigation under progress.  Victim himself is responsible for said accident. N.A Victim himself responsible Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 6 Victim himself is responsible for said accident. N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
16 RRC Lodhika      Kamleshbhai Mangalbhai Patel (Contractor Person) 29.11.16 NFHO On dated 29.11.2016 at approximately 4:00 PM contractor’s labour(outsider) Shri Kamleshbhai Mangalbhai Patel was working for HVDS work  Of 11 KV AG Dom feeder at village Kalyanpur Ta. Lodhika, Dist. Rajkot. In order to fixing tapping angle on existing transformer centre while climbing  on DP  of 11 KV Kangshiyali AG feeder instead of 11 KV Vagudad AG Feeder at village Kalyanpur Ta: lodhika DIs: Rajkot Accidently victim came in contact with live conductor of 11 KV Kangshiyali AG feeder and consequently got electric shock on his right hand. Report of medical officer and Police punchnama is awaited.      Report not received NA NA Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules. 7 Report yet not received N.A N.A Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules.
17 RRC Metoda      Yogesh Kanubhai Dabhi 11.12.16 NFHO On dated 19.12.2016 letter from metoda police choki (Inward No-2022 dt 19.12.2016) a non fatal accident occurred to Shri Yogesh Kanubhai Dabhi at Metoda GIDC at time approx 21:35.The consent SDO rushed to accident site for investigation,it is found that at accident place there is passing of  11 KV Kohinoor GIDC feeder from 66 KV central SS and in 11 KV line span between pole No   CNT/KOH/054/L-04 and DP 63 KVA black spot appears in two phases which is clearly shown from ground,also thread of kite wound from live wire to TC DO. There is possibility of this accident occurred due to victim was removing kite which is wound on wire by any conductive apparatuses and contact with indirectly with live wire and got electric shock at that time and victim was admitted to hospital for further treatment. Actual reason of accident will be known after reciving of medical report from hospital. Report not received N.A N.A Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 8 Victim himself is responsible for said accident. N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
18 RRC Tramba    Mukeshbhai Ranchhodbhai Makwana 07.02.17 FHO This Accident was occurred on the date 07.02.2017 and  DE-Tramba has visited site and as per accident place shown a victim has unauthorized filch guy wire from the ground and climb on the pole for removing guy wire that time upper v-cross arm is tilted and touched with live 11 kv conductor of Dhadhani Ag feeder and this accident occurred. Further investigation under follows.      

Report not received N.A N.A Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 9 Victim himself is responsible for said accident. N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
19 RRC Atkot     A Goat Of Shri Limbabhai Bhayabhai Dharangiya 08.02.17 FA A s per  prliminary investigation report when 2-3 gaoats are passing at Gobarbhai Jinabhai Vasani's farm under 11 KV Murlidhar Ag feeder neara pole N 53 that time suddenly 11 KV Disc insulator blast hence , live 11 KV conductor broken of Murlidhar Ag feeder and fall on the ground same time one goat came in contact with that wire and got electric shock and this accident occurred   Report not received NA NA Faulty Disc replaced and install 2 disc at shackle pole for better power stability & conductor is also replaced of 3 nos. of span 10 Report yet not received N.A N.A Faulty Disc replaced and install 2 disc at shackle pole for better power stability & conductor is also replaced of 3 nos. of span
20 RRC Atkot       Narendarsinh Ramdayalsih Chauhan 18.02.17 FHO Information regarding this accident was got From line staff and DE Atkot with DE tech Jasdan DO  has visited site on the date 18.02.2017(same day). As per site visit victim was doing jumper of HVDS work in Bakhalvad Ag feeder that time suddenly power started and victim got electric shock.
 After primary investigation LC of Bakhalvad Ag feeder was already taken by K.T. Bhesjadiya L.I. but nearer one feeder Dungarpur Ag feeder is “ON” it is also came to notice that there is one consumer who has two Ag connections one connection is given from Dungarpur Ag Feeder and another is given from Bakhalvad Ag feeder and this consumer is using both feeders power through one 3 core cable of approx 250 Mtr. long. This consumer has made one junction in this cable near his home at near Dungarpur Ag connection. Thorough this junction LT power of Dungarpur Feeder Fed to another connection of Bakhalvad feeder. Hence it may be possible that LT power of Dungarpur feeder become 11 KV power through transformer of Bakhalvad feeder and this accident occurred. Both connections are disconnected and both meters are remove for taking MRI and further investigation.     
Report not received NA NA Awareness regarding safety among all labour of line work contractor had been carry out and instruct all line staff to strictly follow safety rules. 11 Report yet not received N.A N.A Instruct all staff & line contractors to strictly follow safety rules and do necessary earthing of line both side where work is going on.. And also awareness among general public had been carry out.
21 RRC Kotda Sangani       Dineshbhai Jagabhai Solanki 04.02.17 FHO The guy foundation at above location was damaged by R&B department’s Highway Road construction agency KETAN CONSTRUCTION during construction work of under construction new bridge over Ghoghavadhar to Ramod highway road. So, when victim came into contact of above guy, guy rod came out from the ground and guy wire below guy insulator touched to jumper of tapping line on nearby PSC pole. So, the leakage power flown through the guy and victim. So, he electrocuted and died. This accident occurred mainly due to removal of guy rod by ketan construction. So, the procedure for lodging FIR against the same is initiated which is under process. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 12 Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
22 RRC Atkot       Jasmat Jadav Rojasara 31.01.17 FHO WE got information regarding this accident date 14.02.17 by victim’s son Shri – Bhupatbhai Jadavbhai Rojasara’s letter. Accident was occurred on date 31.01.17, during treatment in hospitals victim died on date 05.02.17. And this Non fatal accident is converted in to fatal. As per Bhupatbhai statement Victim got injury like electric burns on his stomach, Chest, Legs and wrist of left hand.
 But During Site Visit of DE Atkot on date 15.02.2017 there is  11KV Jumper on TC from DO fuse in  Y Phase  11KV Bushing  have sparking , blackish burning signs. Also there is  not possible to victim was came in contact or touch  with  jumper of DO fuse (Busing to DO) hence it is not clear that this accident exactly which place occurred Hence, all three jumper of DO remove with Videography and photography and send for investigation in Forensic lab Rajkot.
Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 13 Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
23 RRC Vichhiya      Manga Nanji Baraiya 21.02.17 FHO information received from sarpanch shree gram panchayat ankadiya on dtd21.2.2017 at 23:07 , complaint no-462, as per statement of first seeing person ghanshyam khoda bariya ,victim falL down on earth And sanpped lt conductor is falling down to earth, there is one ag a1 connection given to the consumer name nanji virambhai conn no-81821050142 , load -5 HP , also load side kit ket fuse provied , there is no any kind of protective devise provided like MCB/ELCB is not provided and also not found that open case starter use for staring the electric motor but as per site visit and as per the photograph of victim,,there is doubt of accident as there is no any blood marking at site and on snapped  conductor hence also pieces of sapped lt conductor are taken in custody for FSL investigation further detail investigation is under progress  Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 14 Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
24 RRC Vichhiya      Sh. Vipulbhai Rajubhai Goraswa 20.03.17 FHO Information regarding this accident was got from line staff Sh. R.S.Jadav(ALM) and DE Vinchhiya has visited site on the date 23.03.2017(Same Day). As per site visit victim was grassing goat at prabhudabhai Bachubhai haraniya’s farm at that time victim was climb on neem tree for cutting its branches for goats that time victim was fall on HT line of 11 KV veraval AG feeder and this accident occurred. Further detail investigation is under process. Report not received NA NA Necessary Tree Cutting had been carry out and Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 15 Report yet not received N.A N.A Necessary Tree Cutting had been carry out And Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
25 RRC Upleta Pravin Babuji Rathod 19.03.17 FHO This accident occurred at Supedi Village agricultural extension (khetivadi sim Vistar) in 11kv Zanzmer AG feeder on dt 19.03.17 under Upleta Rural Sdn. From the site investigation it is found that Victims were in truck (GTY-5166). Truck was loaded with agricultural waste (Coriander waste). This loaded truck passing parallel to 11kv line of Zanzmer AG feeder and extended metal projection of the truck came in to contact with live conductor. Victims were already in contact with the body part of truck and therefore Victims were short circuited and one of the victims got electrocuted. 11kv Zanzmer AG feeder have tripping in 66kv Supedi Ss  around time 10:05am. So Nonfatal injury occurred to Shri Sagar Panchhiji Rathod  and Fatal accident occurred to Pravin Babuji Rathod.     Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly 16 Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
26 RRC Upleta Sagar Panchhiji Rathod 19.03.17 NFHO This accident occurred at Supedi Village agricultural extension (khetivadi sim Vistar) in 11kv Zanzmer AG feeder on dt 19.03.17 under Upleta Rural Sdn. From the site investigation it is found that Victims were in truck (GTY-5166). Truck was loaded with agricultural waste (Coriander waste). This loaded truck passing parallel to 11kv line of Zanzmer AG feeder and extended metal projection of the truck came in to contact with live conductor. Victims were already in contact with the body part of truck and therefore Victims were short circuited and one of the victims got electrocuted. 11kv Zanzmer AG feeder have tripping in 66kv Supedi Ss  around time 10:05am. So Nonfatal injury occurred to Shri Sagar Panchhiji Rathod  and Fatal accident occurred to Pravin Babuji Rathod.     Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly 17 Report yet not received N.A N.A Awareness among general public & "Gram Panchayat" regarding electrical safety during khedut-shibir & village meeting regularly
27 MRB Wankaner City-Sh. Dilipbhai Balwantbhai Jani 01.10.16 FHD The victim was requested to properly install halogen light on LT pole for lighting Garba venue of the society, where the victim lived. The victim having climbed the pole to properly install this halogen may have felt leakage current and thereby fell on ground on this back. Due to this fall, the victim sustained severe head injury. He was immediately admitted to the hospital and during treatment he succumbed to the injury.  victim himself is responsible  N.A. Victim himself responsible Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 1 victim himself is responsible  N.A. N.A. Awareness among line staff by weekly safety meeting.
28 MRB  Kankot-2,1 Buffalo of Husenbhai Ahmedbhai 05.10.16 FA Due to heavy rain there was water logging near transformer centre. While buffaloes passing from this water logging area leakage current of transformer earthing passing through this water logged area and step potential created, hence victim buffaloes electrocuted & met with fatal accident.  Report not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, Transformer Centre shifted with new earthing. 2 Report yet not received N.A. N.A. Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, Transformer Centre shifted with new earthing.
29 MRB Kankot-2,1 Baffalo of Bhikha Vasram 05.10.16 FA Due to heavy rain there was water logging near transformer centre. While buffaloes passing from this water logging area leakage current of transformer earthing passing through this water logged area and step potential created, hence victim buffaloes electrocuted & met with fatal accident.  Report not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, Transformer Centre shifted with new earthing. 3 Report yet not received N.A. N.A. Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, Transformer Centre shifted with new earthing.
30 MRB Velala-Smt. Amiben Punjabhai Bharvad 22.10.16 NFHO In the Farm due to wind conductor of 11kv Virpar AG Feeder Broken which is fall on wet groundnuts plants. At that time victim working in the farm and contact with wet groundnuts plants which is resultant into this nonfatal human accident.   Report not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, conductor replacement of 0.310KM & erection of 6 new span far from trees. After visit of CEI, old line 6 span of conductor will be dismantling. 4 Report yet not received N.A. N.A. Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, conductor replacement of 0.310KM & erection of 6 new span far from trees. After visit of CEI, old line 6 span of conductor will be dismantling.
31 MRB Shapa-Sh Anwarbasha Mehboobjohn 06.11.16 FHO On dt.06.11.2016, around 16:55 Victim had parked his 40 ft heavy duty Container truck along road side, in parallel to 11 KV Euro Fdr HT Line. As he realized that back door of container was open, Victim was closing the door by hand, Top of the container door accidentally touched the nearby 11 KV Euro Fdr line and victim was electrocuted. Ground clearance of HT line was 19 ft.  PGVCL is partially responsible  Vertical distance of 11kv line must be 6.1mtr. As part of corrective maintenance, Transformer Centre shifted with girder pole 11kv line. Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, Transformer Centre shifted with girder pole 11kv line. 5 PGVCL is partially responsible  Vertical distance of 11kv line must be 6.1mtr. As part of corrective maintenance, Transformer Centre shifted with girder pole 11kv line. Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, Transformer Centre shifted with girder pole 11kv line.
32 MRB Matel-Sh Chetan Jayntilal Ranipa 18.12.16 FHO Above victims works as labours in M-Bo Granito P L industry. They moving/pulling an iron made tower ladder having height of approx. 6 mtr (18.5ft). While moving tower ladder from one place to other place, top part of tower ladder touched to 11 KV Line (which vertical distance 17.5ft), hence tower ladder energized, victims got shocked and electrocuted. Out of three victims, one Victim met with fatal accident and other two met with non-fata| accident. Report not received NA NA Notice issue to owner of M-BO granito for breaking of safety regulation  rules no.60 and 61.
Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
6 Report yet not received N.A. N.A. Notice issue to owner of M-BO granito for breaking of safety regulation  rules no.60 and 61.
Awareness among general public regarding safety in every khedut shibir/gramsabha
33 MRB Matel-Sh Hemant Gandubhai Setaniya 18.12.16 NFHO Above victims works as labours in M-Bo Granito P L industry. They moving/pulling an iron made tower ladder having height of approx. 6 mtr (18.5ft). While moving tower ladder from one place to other place, top part of tower ladder touched to 11 KV Line (which vertical distance 17.5ft), hence tower ladder energized, victims got shocked and electrocuted. Out of three victims, one Victim met with fatal accident and other two met with non-fata| accident. Report not received NA NA Notice issue to owner of M-BO granito for breaking of safety regulation  rules no.60 and 61.
Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
7 Report yet not received N.A. N.A. Notice issue to owner of M-BO granito for breaking of safety regulation  rules no.60 and 61.
Awareness among general public regarding safety in every khedut shibir/gramsabha
34 MRB Matel-Sh Jamra Raju Ramsing 18.12.16 NFHO Above victims works as labours in M-Bo Granito P L industry. They moving/pulling an iron made tower ladder having height of approx. 6 mtr (18.5ft). While moving tower ladder from one place to other place, top part of tower ladder touched to 11 KV Line (which vertical distance 17.5ft), hence tower ladder energized, victims got shocked and electrocuted. Out of three victims, one Victim met with fatal accident and other two met with non-fata| accident. Report not received NA NA Notice issue to owner of M-BO granito for breaking of safety regulation  rules no.60 and 61.
Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
8 Report yet not received N.A. N.A. Notice issue to owner of M-BO granito for breaking of safety regulation  rules no.60 and 61.
Awareness among general public regarding safety in every khedut shibir/gramsabha
35 MRB Vadadhra-1 Buffalo of Sh Gelabhai Bhurabhai Bharvad  14.01.16 FA A Buffalo was going after drinking water from water source (AVEDO), at that time conductor of 11 KV Fuliya AG feeder snapped due to kite thread or any other reason & fall, at that time buffalo passing through it and met with fatal electrical accident.  Report not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, conductor has been replaced for 2 spans 9 Report yet not received N.A. N.A. Awareness among general public regarding safety in every khedut shibir/gramsabha. As part of corrective maintenance, conductor has been replaced for 2 spans
36 PBR Village: Khageshri-Siyabhai Avdabhai Chavda 30.09.16 NFHO As per preliminary investigation, 2nos of non fatal human accident (1. Contractor person and another outsider) occurred due to replacement of fail TC of kishorbhai faldu valu TC marvadi group-2 at village Khageshri of Shiva AG feeder at 12:25 on dt 30.9.16. The cause of accident is suspected and matter is under investigation. Report not received NA NA action taken against farmer who was using dual power in his ag premises connection room and FIR lodge against Sh. Hitesh jentibhai kansagra and theft bill of Rs. 4,62,324/- is issued against defaulter. Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 1 Report yet not received NA NA action taken against farmer who was using dual power in his ag premises connection room and FIR lodge against Sh. Hitesh jentibhai kansagra and theft bill of Rs. 4,62,324/- is issued against defaulter
37 PBR Village: Khageshri-Bharatbhai Chhaganbhai Dabhi 30.09.16 NFHO As per preliminary investigation, 2nos of non fatal human accident (1. Contractor person and another outsider) occurred due to replacement of fail TC of kishorbhai faldu valu TC marvadi group-2 at village Khageshri of Shiva AG feeder at 12:25 on dt 30.9.16. The cause of accident is suspected and matter is under investigation. Report not received NA NA action taken against farmer who was using dual power in his ag premises connection room and FIR lodge against Sh. Hitesh jentibhai kansagra and theft bill of Rs. 4,62,324/- is issued against defaulter. Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 2 Report yet not received NA NA action taken against farmer who was using dual power in his ag premises connection room and FIR lodge against Sh. Hitesh jentibhai kansagra and theft bill of Rs. 4,62,324/- is issued against defaulter
38 PBR Village: Nandarkhi Ag Area, Buffalo Of Belim Navajkha Hematkha,  04.10.16 FA As per preliminary investigation, Due to rain and wind tree branch laid down on the LT line and the same was snapped & buffalo came in contact with broken LT conductor and got electrocuted .Further matter under investigation. Accident occurred due to tree cutting not done in timely Tree cutting in regularly  Yes Tree cutting done in that AG group & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 3 Accident occurred due to tree cutting not done in timely Tree cutting in regularly  Yes Tree cutting done in that AG group
39 PBR Village:Oddar, Bullock Of Shri. Rajshibhai Meramanbhai Odedara 16.10.16 FA As per preliminary investigation 11kv return single conductor snapped and fallen on ground - rough road, while bullocks with cart passing from this road and came in contact with live conductor and got electrocuted, met to fatal animal electrical accident. Further, Matter regarding cause of accident is under investigation. snapping of conductors-c) due to short circuit Deteriorated conductor replaced  Yes Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 4 snapping of conductors-c) due to short circuit Deteriorated conductor replaced NA Deteriorated conductor replaced
40 PBR Village:Oddar, Bullock Of Shri. Rajshibhai Meramanbhai Odedara 16.10.16 FA As per preliminary investigation 11kv return single conductor snapped and fallen on ground - rough road, while bullocks with cart passing from this road and came in contact with live conductor and got electrocuted, met to fatal animal electrical accident. Further, Matter regarding cause of accident is under investigation. snapping of conductors-c) due to short circuit Deteriorated conductor replaced  Yes Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 5 snapping of conductors-c) due to short circuit Deteriorated conductor replaced NA Deteriorated conductor replaced
41 PBR Village: Rahij- Aslamsha Masumsha Fakir  15.12.16 NFHO Contractor Abubakar Mohmad Pathan's team was working for Ag new connection line work and two workers of the team as per primary investigation came in electric zone of the line and injurious to both. The matter is under investigation that how both worker came in electric zone and flow of current came in line because statements of victims or contractor's other persons were can not take. Report not received NA NA Notice issued to contractor vide latter no: MDO/TECH/7368, Dated:-20.12.2016 & Instructed to create awareness for safety amongst contractor in contractor meetings 6 Report yet not received NA NA Notice issued to contractor vide latter no: MDO/TECH/7368, Dated:-20.12.2016
42 PBR Village: Rahij- Mausin Iqbal Belim 15.12.16 NFHO Contractor Abubakar Mohmad Pathan's team was working for Ag new connection line work and two workers of the team as per primary investigation came in electric zone of the line and injurious to both. The matter is under investigation that how both worker came in electric zone and flow of current came in line because statements of victims or contractor's other persons were can not take. Report not received NA NA Notice issued to contractor vide latter no: MDO/TECH/7368, Dated:-20.12.2016 & Instructed to create awareness for safety amongst contractor in contractor meetings 7 Report yet not received NA NA Notice issued to contractor vide latter no: MDO/TECH/7368, Dated:-20.12.2016
43 PBR Village: Mangrol- Shri Dilkhush Sakraji Kotwal(Dipartmental) 02.02.17 NFHD As per preliminary investigation report While making jumper in 11kv Mangrol City Urban feeder, LC of this and including parallel feeder was taken and earthling, short circuit of three phase of 11kv done, switch opened, leakage current flow may be of inverter or other sources & got shocked, further matter under investigation. Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 8 Report yet not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line.
44 PBR Village: Dharampur- Shri Punjabhai Sukabhai Odedara 13.02.17 FHO While doing any unauthorized work on transformer centre DP structure, victim might touch the do fuse having carrying live power & might electrocuted. Further investigation under process.  Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 9 Report yet not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly
45 PBR Village: Koylana -Yusuf Ismile Jethava 09.03.17 NFHO For carry out the work of new line erection LCP of 11KV Meshwan JGY is invariably needed.  During work time Shri Yusuf Ismail Jethwa (contractor person) climbed the electric pole without any instruction and confirmation from supervisor that the power supply is turned off or not. Hence he electrified with 11KV line and fell off the pole, resulting in Injuries on right solder and on both legs at bottom.  Report not received NA NA Notice issued to contractor vide latter no: KSD/R-1/TECH-1/7453, Dated:-28.03.2017 & Instructed to create awareness for safety amongst contractor in contractor meetings 10 Report yet not received NA NA Notice issued to contractor vide latter no: KSD/R-1/TECH-1/7453, Dated:-28.03.2017
46 PBR Village: Amrapur, Camel Of Balubhai Dhaiyabhai Chavda 13.03.17 FA Due to break down of 11kv katrasa Ag feeder tapping pole no.50 Guy, the said pole inclined and very long span due to this it reduces clearance between ground and 11kv line. The Camel Came between the said span pole no.50 and 51L1 11kv line and at this time camel either came in induction zone of 11kv line or touches the 11kv line and got electric shock and died Report not received NA NA At Tapping pole new Guy set provided and Re stringing of the 2 span & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 11 Report yet not received NA NA At Tapping pole new Guy set provided and Re stringing of the 2 span
47 JMN Mithoi Patiya-Ghelubhai Hamirbhai Patani 06.10.16 FHO Victim Ghelubhai Hamirbhai Patani climbing on top of the truck cabin for taking talpatri, during that time he came in contact with 11-KV line of Zakhar JGY feeder and got electric shock. At the same time leakage current flowed through the wheel of truck to the other victim named Bipin Nathuram Yadav who was checking air level of the truck vehicle and got electrocution and met with non-fatal accident. Distance between the line and ground is 16-feet but the vehicle was parked under the 11-kv line hence the accident took place. Report not received NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time. 1 No NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time.
48 JMN Mithoi Patiya-Bipin Nathuram Yadav 06.10.16 NFHO Victim Ghelubhai Hamirbhai Patani climbing on top of the truck cabin for taking talpatri, during that time he came in contact with 11-KV line of Zakhar JGY feeder and got electric shock. At the same time leakage current flowed through the wheel of truck to the other victim named Bipin Nathuram Yadav who was checking air level of the truck vehicle and got electrocution and met with non-fatal accident. Distance between the line and ground is 16-feet but the vehicle was parked under the 11-kv line hence the accident took place. Report not received NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time. 2 NO NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time.
49 JMN Nana vadala-1-nos bullock of Popatbhai Jadavbhai Lungariya 10.10.16 FA Snapping of LT conductor of 11-KV Nana Vadala AG feeder fall  from pole no.4 & 5 from TC, conductor fall on the bullock and got electrocuted As per CEI accident occurred due to loose span and not maintaining proper clearance between two conductors as per norms and so one of the conductor snapped and accident occurred proper clearance and maintenance of conductor might prevented the accident  Yes Rebinding of Conductor and maintenance work carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 3 As per CEI accident occurred due to loose span and not maintaining proper clearance between two conductors as per norms and so one of the conductor snapped and accident occurred proper clearance and maintenance of conductor might prevented the accident Remedy complied by carried out maintenance. Rebinding of Conductor and maintenance work carried out
50 JMN Pastardi-Lakhman Hardas Mavadiya 17.11.16 FHO As per site visit taken, there is no any eyewitness found at site but as per inspection at the site and first informer statement, victim was fall down on land at that time informer was received at Transformer centre, it is not sure that victim was tried to attempt any illegal work on TC and accidentally somehow he got electric shock. The accident is suspected Report not received NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time. 4 NO NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time.
51 JMN Kandorana Vadi Vistar-She buffalo of Shri Pithabhai Maiyabhai Charan 24.11.16 FA As per site visit taken and inspection carried out of place that 11KV Conductor of Bajana AG feeder was snapped from Disc HW due to heavy fogging in early morning in that area. A she buffalo accidentally passing over the snapped conductor and came in the contact of live wire and got electrocuted. Report not received NA NA Dish insulator replaced & Rebinding of Conductor & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 5 NO NA NA Dish insulator replaced & Rebinding of Conductor.
52 JMN Jamnagar-Dipakbhai Veljibhai Nakum 03.12.16 FHD Victim was working on 11 KV crystal feeder on DP with DT number SRS/CRYSTAL FDR/011/L-018. Victim started his work with necessary safety tools, 3 phase of 11 KV side are shorted with short link (copper wire) and earthed with discharge rod on southside of DP structure, northside of 11 KV side not shorted & not earthed by lineman. Also DO fuse of all 3 phase of HT side not removed by lineman on the d p structure with transformer but 11 KV GO switch cut off, on which accident occurred. 11 KV crystal feeder LCP number 6651/03.12.2016 taken by B N Kotad (LM). Electric current of any generator may have been momentarily passed through line and passed through the body of victim and fatal accident occurred with him. As per CEI accident occurred due to improper earthing of all 3phase and not wearing of all safety gadgets by the victim specially safety shoes and gloves.  Accident can be prevented by proper earthing, use of safety gadgets and proper testing of line before starting of work. All staff were educated in safety meeting by SDO to carry out proper earthing and use of all safety gadgets for accident prevention. Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 6 As per CEI accident occurred due to improper earthing of all 3phase and not wearing of all safety gadgets by the victim specially safety shoes and gloves.  Accident can be prevented by proper earthing, use of safety gadgets and proper testing of line before starting of work. All staff were educated in safety meeting by SDO to carry out proper earthing and use of all safety gadgets for accident prevention. All the line staff instructed to use safety gadgets while working on line and insisted them to short & earth the line on both the sides of the working location as per standard procedure.
53 JMN Bamangam-Kiritbhai Dayabhai Thakar 05.12.16 FHO (Vijalighar helper) While victim has asked wrong feeder LC from Elec. Asst. and he climbed on DTC for service repairing work at Bhikhu Samji's farm and touched 11-KV Napaniya Khijadiya feeder and got electrocuted. Victim was not authorized for this type of work, however Elec. Asst. has given LC to Vijalighar helper unauthorized work by victim According to CEI report LC must not be given to any unauthorized person to avoid such type of accident All staff were educated in safety meeting by sdo not to take LC for unauthorized person for accident prevention. All line staff is educated for not taking any LCP for any type of network related work for the outsider person during safety meeting for safety of staff as well as other people. 7 unauthorized work by victim According to CEI report LC must not be given to any unauthorized person to avoid such type of accident All staff were educated in safety meeting by sdo not to take LC for unauthorized person for accident prevention. All line staff is educated for not taking any LCP for any type of network related work for the outsider person during safety meeting for safety of staff as well as other people.
54 JMN Near Padana Patiya-Sovan Bahadursingh Thakur 13.12.16 NFHO Outsider mechanical accident occurred with Sovan Bahadursingh Thakur, labour person of contractor Shri H P Prajapati at Padana patiya. During mass maintenance work of 11 KV Navaniya  AG feeder during  restringing of 11 KV Navaniya AG line  conductor victim was sitting on shackle point and trying to string the conductor at that time from his front side nearby pole was broken from his foundation and due to tension of wire said shackle point  PSC Pole was also broken and victim fell down with that broken pole and got injured the maintenance work was carried out  under the supervision of Shri R N Makwana Line Inspector sikka sdn and  he is partially responsible for this accident. Report not received NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time. 8 NO NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time.
55 JMN Sikka Ramnagar-Parmjeet Ramesh Makwana 13.12.16 NFHO As per site visited by under signed with EE City 2 and DE tech on Dt .14.12.2016 the site facts was that during incident few children were playing cricket on the ground of the school after school hrs nearly at 18:30 PM, During that time the ball went on the terrace’s ’ of school building and victim went to collect this ball from back side of the wall of school  and due to no staircase for climbing  to terrace victim tried to jump on wall suddenly at that time victim boy lost his balance and grabbed the 11 KV live line wire for support which line was passing nearby building at the back side of school and he came in contact with live wire and he got electric shock .At accident place vertical distance between the line and ground is 14 feet and horizontal distance is 3 ft from 11 KV line, hence victim is partially responsible for this non-fatal accident. Report not received NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time. 9 NO NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time.
56 JMN Ran-1-Buffalo of Shri.Rambhai Punabhai Movar 26.12.16 FA Due to heavy wind conductor of 11Kv Virpar JGY snapped and one conductor broken, at that time one buffalo passed near to that live wire and came in contact with live conductor and got electric shock and electrocuted and died at place Report not received NA NA The broken conductor rebinded and necessary maintenance carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 10 NO NA NA The broken conductor rebinded and necessary maintenance carried out
57 JMN Dhrol-1-Cow of Shri Mombhai Kumbhabhai Lambariya 14.01.17 FA 11-KV conductor broken from load side of 11-KV Itala JGY feeder & one leg of cow laid down on broken conductor portion. No burnt injury shown on died cow. Report not received NA NA Snapped conductor replaced & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 11 NO NA NA Snapped conductor replaced
58 JMN Gokulnagar Jamnagar-Ajay Mansukhbhai Kubavat 15.01.17 FHO Victim was trying to retrieve the kite from 11-KV live conductor with the help of iron rod and current passed through the rod and victim got electric shock. During this time 11-KV Mayurnagar feeder trip on R-B phase. As per CEI report, accident occurred due to unauthorized work carried out by victim and also PGVCL, for not maintaining horizontal as well as vertical clearance from the ground Accident can be prevented by avoiding unauthorized work by victim as well as maintaining ground clearance as per norms. Public awareness carried out by doing area meeting for safety awareness and now line clearance properly maintained as per norms. Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time 12 As per CEI report, accident occurred due to unauthorized work carried out by victim and also PGVCL, for not maintaining horizontal as well as vertical clearance from the ground Accident can be prevented by avoiding unauthorized work by victim as well as maintaining ground clearance as per norms. Public awareness carried out by doing area meeting for safety awareness and now line clearance properly maintained as per norms. Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time
59 JMN Devariya-Karshanbhai Naranbhai Rathod 17.01.17 NFHO Victim was rested on chair under 11-kv Chalana AG feeder, the conductor broken accidentally and fall down near the victim seated chair and there is no evidence of sparking on chair so may be victim came in induction zone Report not received NA NA Snapped conductor replaced & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 13 NO NA NA Snapped conductor replaced
60 JMN Gajna AG area-Naran Daya Bharvad 06.02.17 NFHO While victim was climbed on transformer centre for unauthorized work at that time suddenly he was came in contact with live part and got electric shock Report not received NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time 14 NO NA NA Public awareness meeting for safety, educating the people about the hazards of electricity lines, cables and apparatus is being arranged time to time
61 JMN Charakla-Rajabhai Ashabhai Chanpa 03.03.17 NFHO Purely mechanical accident occurred in n/w when victim was doing work of release of new RL connection of Shri Kanubhai Vaghubhai Desai while climbing pole, his leg slipped from it and fall down and got injured. The above said work was carried out under supervision of Shri J H Dave (LM). Report not received NA NA Notice issued to Devbhumi Enterprise (contractor) for non-utilizing safety tools vide letter no. DSD/Tech/520 dtd:23.03.17 & Imposed penalty Rs.500/- for non-utilizing safety tools vide receipt no.960997 dtd:27.03.17 15 NO NA NA Notice issued to Devbhumi Enterprise (contractor) for non-utilizing safety tools vide letter no. DSD/Tech/520 dtd:23.03.17 & Imposed penalty Rs.500/- for non-utilizing safety tools vide receipt no.960997 dtd:27.03.17
62 BHJ Sherdi, Jilubha Gaguji Zala 13.10.16 FHO When truck passing under 11 KV HT line near Sherdi village tapping new line from vimal residency area 5 KVA TC, hydraulic trolley of truck (which was up from its basic level) touched with 11 KV HT line phase and current pass through truck and when victim jump from truck and he touched with earth and got electrical shock and human fatal accident was occurred. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 1 Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
63 BHJ Tunda Nr.Tata Material Gate, Mahendrasinh Indrasinh Rathod 17.10.16 FHO After parking the bulker no GJ 07 YY 4889 under 11KV kandagara jgy line location no. JGY/164 to 165, victim climb on bulker for some work. While doing some work, he may came in induction zone & electrocuted. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 2 Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
64 BHJ Chandranagar, Near Farm Of Than Jagir Land, Goat Of Shri Premsinh Bhuraji Sodha 03.12.16 FA Due to pin puncture, 11 KV conductor broken and fall down on the earth at that time goat came with direct contract of live broken conductor and got electrocuted Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 3 Report yet not received NA NA Deteriorated conductor replaced
65 BHJ Bharapar, Ganpat Bihari Raut 22.12.16 FHO The contractor’s persons were removing LT line conductor from the LT network of dargah valu TC 100 KVA (7‘th no of LT girder pole from dargah valu TC 100 KVA). While doing so accidently the girder pole on which the victim was climbed, broken from the bottom and the victim fell down with the girder pole on the ground. An angle of the girder pole stabbed in the victim’s stomach due to which the victim died due to high blood loss.  (mechanical) Report not received NA NA Instructed to create awareness for safety amongst contractor in contractor meetings 4 Report yet not received NA NA Instructed to create awareness for safety amongst contractor in contractor meetings
66 BHJ Kalyanpar, Buffalo Of Shri Sale Mamad Nurmamad Kumbhar  23.12.16 FA Buffalo came in contact with broken live 11 KV  wire and  electrocuted. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 5 Report yet not received NA NA Deteriorated conductor replaced
67 BHJ Talwana, Cow of Hothi Chhana Sangar 10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 6 Report yet not received NA NA Deteriorated conductor replaced
68 BHJ Talwana, Cow of Jitu Khimaji Maheshwar 10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 7 Report yet not received NA NA Deteriorated conductor replaced
69 BHJ Talwana, Cow of Vipul Maganlal Patel  10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 8 Report yet not received NA NA Deteriorated conductor replaced
70 BHJ Talwana,  Cow of Ramaji Shamaji Sangar                                               10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 9 Report yet not received NA NA Deteriorated conductor replaced
71 BHJ Talwana, Bullock of Devaji Hamirji Jadeja                       10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 10 Report yet not received NA NA Deteriorated conductor replaced
72 BHJ  Talwana, Cow of Kanaiya Satu Sangar 10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 11 Report yet not received NA NA Deteriorated conductor replaced
73 BHJ  Talwana, Cow of Fuliya Dharmendra Chunilal 10.1.17 FA           Due to snapping of conductor of 11 KV jyotidhar AG feeder, at location no jyotidhar AG/TLV SS/JTD 092-93,were 06 nos of cow and 1 nos of bullock died, there was tripping in jyotidhar AG feeder at 9.40 am and after try taken by 66 KV GETCO talwana ss operator staff feeder is charge, but there may power was still in  snapped conductor and after information SS feeder is made off all above in spite of snapped conductor feeder was not tripped and accident is occurred. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 12 Report yet not received NA NA Deteriorated conductor replaced
74 BHJ Kharau, Camel Of Shri Vanka Khiyashi Rabari 27.02.17 FA The accident occurred at kankvati -kharau river crossing location. While camel was grazing in this place at that time came in direct contact with live conductor of Nudhtad AG feeder got electric current and died. Due to heavy water flow in river during monsoon a sand deposition made in the river. So ground clearance to live conductor became less due to which camel contact with live conductor. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 13 Report yet not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
75 ANJ Chobari, Gomtiben Khimjibhai Prajapati 28.09.16 NFHO The Victim was working below 11 KV Shikara AG line in Mahavirsinh B. Jadeja’s farm. That time birds which sits on this line, suddenly all birds fly, due to birds fly wire of 11 KV line short circuit  and one conductor broken this line and fall on victim & got shock & admitted in hospital Bhachau for treatment and non-fatal accident occurred. Detail report under investigation. No any information given to PGVCL above accident on dated 28.09.2016. Telephonic information given from Mahavirsinh B. Jadeja on dated 10.10.2016 about this Non-Fatal accident, so PAR not submitted in time. Report not received NA NA Necessary maintenance work carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 1 Report yet not received NA NA Necessary maintenance work carried out
76 ANJ Kasez, Virendra Lalan Sing 16.10.16 NFHO Victim has parked his trailer loaded with container under 11 KV line FTZ-1 IND feeder to put M-SEAL on top of container. He climbed over container, then his hand touched to 11 KV feeder and he got electrocuted Report not received NA NA Necessary maintenance work carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 2 Report yet not received NA NA Necessary maintenance work carried out
77 ANJ Khengarpar, Buffalo,Owner:Govindbhai Ranchhodbhai Manvar 25.01.17 FA Buffalo was passed near the AB switch of Khengarpar AG feeder at the location of Khengarpar-Vajepar road. Its horns wrapped with guy wire of ab switch and during removal of its horns, guy wire broken from bottom and touched with live contact of ab switch and got electrocuted and died at site. Report not received NA NA Ab cable provided on switch instead of bare conductor and tighten the guy wire & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 3 Report yet not received Na Na Ab cable provided on switch instead of bare conductor and tighten the guy wire
78 ANJ Tapper, Buffalo,Owner:Vibha Bechra Rabari 15.03.17 FA As per preliminary investigation report on dated 15.3.17, At around 10:30am, near village Tappar, conductor of 11KV Gopalnagar JGY feeder snapped and came in contact with the Land surface and the feeder got tripped and due to conductor snapping, after 2/5 minutes try was taken by SS operator and feeder once again tripped as conductor was snapped. At the same time, group of buffalos pass from the location were conductor was snapped. 6 nos of buffalos an 1 no of cow  came in the contact of snapped conductor. During that time, try was taken from SS and hence, power came in snapped conductor to which these buffalos were in contact, because of that 6 nos of buffalos got electrocuted and died at a time and 1 no of cow got injured.. Report not received NA NA Cond Replacement, Hardware replacement & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 4 Report yet not received NA NA Cond Replacement, Hardware replacement
79 ANJ Tapper, Buffalo,Owner:Kankuben Bhala Rabari, 15.03.17 FA As per preliminary investigation report on dated 15.3.17, At around 10:30am, near village Tappar, conductor of 11KV Gopalnagar JGY feeder snapped and came in contact with the Land surface and the feeder got tripped and due to conductor snapping, after 2/5 minutes try was taken by SS operator and feeder once again tripped as conductor was snapped. At the same time, group of buffalos pass from the location were conductor was snapped. 6 nos of buffalos an 1 no of cow  came in the contact of snapped conductor. During that time, try was taken from SS and hence, power came in snapped conductor to which these buffalos were in contact, because of that 6 nos of buffalos got electrocuted and died at a time and 1 no of cow got injured.. Report not received NA NA Cond Replacement, Hardware replacement & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 5 Report yet not received NA NA Cond Replacement, Hardware replacement
80 ANJ Tapper, Buffalo,Owner: Satish Jayntilal Thakkar 15.03.17 FA As per preliminary investigation report on dated 15.3.17, At around 10:30am, near village Tappar, conductor of 11KV Gopalnagar JGY feeder snapped and came in contact with the Land surface and the feeder got tripped and due to conductor snapping, after 2/5 minutes try was taken by SS operator and feeder once again tripped as conductor was snapped. At the same time, group of buffalos pass from the location were conductor was snapped. 6 nos of buffalos an 1 no of cow  came in the contact of snapped conductor. During that time, try was taken from SS and hence, power came in snapped conductor to which these buffalos were in contact, because of that 6 nos of buffalos got electrocuted and died at a time and 1 no of cow got injured.. Report not received NA NA Cond Replacement, Hardware replacement & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 6 Report yet not received NA NA Cond Replacement, Hardware replacement
81 ANJ Tapper, Buffalo,Owner:Mata Samat Dhana 15.03.17 FA As per preliminary investigation report on dated 15.3.17, At around 10:30am, near village Tappar, conductor of 11KV Gopalnagar JGY feeder snapped and came in contact with the Land surface and the feeder got tripped and due to conductor snapping, after 2/5 minutes try was taken by SS operator and feeder once again tripped as conductor was snapped. At the same time, group of buffalos pass from the location were conductor was snapped. 6 nos of buffalos an 1 no of cow  came in the contact of snapped conductor. During that time, try was taken from SS and hence, power came in snapped conductor to which these buffalos were in contact, because of that 6 nos of buffalos got electrocuted and died at a time and 1 no of cow got injured.. Report not received NA NA Cond Replacement, Hardware replacement & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 7 Report yet not received NA NA Cond Replacement, Hardware replacement
82 ANJ Tapper, Buffalo,Owner: Ramju Ali Kumbhar 15.03.17 FA As per preliminary investigation report on dated 15.3.17, At around 10:30am, near village Tappar, conductor of 11KV Gopalnagar JGY feeder snapped and came in contact with the Land surface and the feeder got tripped and due to conductor snapping, after 2/5 minutes try was taken by SS operator and feeder once again tripped as conductor was snapped. At the same time, group of buffalos pass from the location were conductor was snapped. 6 nos of buffalos an 1 no of cow  came in the contact of snapped conductor. During that time, try was taken from SS and hence, power came in snapped conductor to which these buffalos were in contact, because of that 6 nos of buffalos got electrocuted and died at a time and 1 no of cow got injured.. Report not received NA NA Cond Replacement, Hardware replacement & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 8 Report yet not received NA NA Cond Replacement, Hardware replacement
83 ANJ Tapper, Buffalo,Owner: Ramju Ali Kumbhar 15.03.17 FA As per preliminary investigation report on dated 15.3.17, At around 10:30am, near village Tappar, conductor of 11KV Gopalnagar JGY feeder snapped and came in contact with the Land surface and the feeder got tripped and due to conductor snapping, after 2/5 minutes try was taken by SS operator and feeder once again tripped as conductor was snapped. At the same time, group of buffalos pass from the location were conductor was snapped. 6 nos of buffalos an 1 no of cow  came in the contact of snapped conductor. During that time, try was taken from SS and hence, power came in snapped conductor to which these buffalos were in contact, because of that 6 nos of buffalos got electrocuted and died at a time and 1 no of cow got injured.. Report not received NA NA Cond Replacement, Hardware replacement & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 9 Report yet not received NA NA Cond Replacement, Hardware replacement
84 ANJ Mithaport: Gopalbhai Devjibhai Maheswari 23.03.17 NFHO Truck was laid under 11 KV line of USW feeder. During the unloading of material, trolley was raised using hydraulic and came in contact of live conductor. Hence the frightened driver tried to jumped from truck but got electrocuted while jumping from truck Report not received NA NA Guarding of HT ,LT, TC of USW feeder & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 10 Report yet not received Na Na Guarding of HT ,LT, TC of USW feeder
85 JND Unagadh, Shri Hajibhai  Hasanbhai Patel 03.10.16 NFHO A non-fatal mechanical accident occurred to Shri. Hajibhai Hasanbhai Patel during new transformer and 11 KV line erection work and fall down from PSC pole at Krish Apprtment, Akshar Residency-2, Junagadh Vanthali road, Madhuram. Instruction given to use safety gadgets while work on site Victim resposible Victim resposible Safety meetings are arranged with staff in presence of contractor 1 CEI report not received CEI report not received CEI report not received Safety meetings are arranged with staff in presence of contractor Safety meetings are arranged with staff in presence of contractor
86 JND Lushala , Cow Of Shri Virabhai Vasanbhai  Dangar 05.10.16 FA A cow was found dead near t/c pole. On detail inspection it was found that due to rain conditions leakage current might be passing through t/c pole to the earth. At that time cow might be passing near the t/c pole and probably electrocuted. The earthing is covered with pipe is inserted with pipe and pipe is inserted deep in the earth. Checking by tester there is no direct flow of current through pole or earthing. It is due to leakage earthing current moisture soil in live raining. Matter is under investigation. Earthing is not powerful Earthing is not powerful  Yes Earthing reactivated & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 2 Earthing is not powerful Earthing is not powerful Earthing reactivate Earthing reactivated Earthing reactivated
87 JND Buffalo of Shri Manubha Jalubha Parmar 08.10.16 FA One DO fuse was burnt so may be differential current was passing from neutral of transformer .at the time due to wet land because of rainy season one buffalo when passing near transformer got electric shock and met with fatal accident. Report not received NA NA Earthing reactivated & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 3 CEI report not received CEI report not received CEI report not received Earthing reactivated Earthing reactivated
88 JND Majevadi , Smt  Nathiben   Punabhai  Makwana 25.10.16 NFHO On dt.25.10.2016 at 11:35 am victim Shri Nathiben Punabhai Makwana, age apx. 65 yrs, labour worker was moving/throwing 30 ft. Long iron rods (khilasari) from terrace of Devtankhi Dham (temple), Majevadi. At that time due to mistake of victim, one end of this iron rod touched to vicinity of live 11 KV line and other end touched to ground. So she got very normal electric induction. Tripping is registered at s/s. Victim himself is responsible. Though further investigation is under progress Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 4 CEI report not received CEI report not received CEI report not received Village meeting and khedut shibirs are arranged to educate people about electrical safety Village meeting and khecut shibirs are arranged to educate people about electrical safety
89 JND Ishavariya (Mandavad), Shri Makubha  Abhesinh 06.11.16 FHO As per unknown telephonic information on 7.11.2016,   we investigate the matter and only above detail are firms in our knowledge. During preparation of electric motor installation in bore well in farm of Shri Ratibhai Govindbhai Kapadiya at that time clamp of galvanized pipe broken from metal structure (trolley) & accidentally galvanized pipe touched with near passing 11 KV line & accident occurred. Clearance between 11 KV line and earth is appx more than 6 meter. Victim himself is responsible no any suggestion Victim resposible Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 5 Victim himself is responsible no any suggestion NA Village meeting and khedut shibirs are arranged to educate people about electrical safety Village meeting and khedut shibirs are arranged to educate people about electrical safety
90 JND Semarvav, Buffalo Of Shri Kanabhai Naranbhai Jadav 02.12.16 FA Lt side 'r' phase circuit cable insulation damaged and touched with earthing gi wire so leakage current was passing through earthing and there was water flowing near to transformer centre due to that surrounding area of transformer centre was wet. When victimized buffalo was passing near from this transformer centre got electric shock and met with fatal accident. Report not received NA NA Earthing reactivated & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 6 CEI report not received CEI report not received CEI report not received Earthing reactivated Earthing reactivated
91 JND Vadhavi, Shri  Rambhai   Tharanbhai  Bhurani 04.12.16 NFHD On dt. 04.12.2016, at approx 10.00 am , victim Sh.Rambhai T Bhurani was unclimbing AG LT pole after repairing fault , at that time he slipped due to old spare c clamp came out from PSC pole  and his body became unbalance , due to jerk with ground he felt moch in sole of left leg . At 3.00 pm he went at hospital. As per his statement he has not shown C clamp. This person has problem with leg and eyes. For which treatment is running since long time  Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 7 CEI report not received CEI report not received CEI report not received Safety meetings are arranged with staff in presence of contractor Safety meetings are arranged with staff in presence of contractor
92 JND Vala Simadi, Shri Hareshbhai  Vallabhbhai Satasiya 07.11.16 NFHO Victim was doing work of sprinkling of Kitnasak in vegetables in his farm at that time one phase wire of three phase three wire LT line snapped and he got induction, thrown away. He was immediately transferred to Govt. hospital Junagadh and discharged at 5.00 pm on same day.  Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 8 CEI report not received CEI report not received CEI report not received Village meeting and khedut shibirs are arranged to educate people about electrical safety Village meeting and khedut shibirs are arranged to educate people about electrical safety
93 JND Junagadh, Shri Aminbhai   Jumabhai Sama 26.12.16 FHO The information about accident received on dated 28.12.16 from c-division police station junagadh. After site visit it is found that it may have happened that while victim was pulling up the iron bar approximate 20 ft long from ground level to second floor slab for construction work of house, at that time the iron bar accidently came in contact with live conductor and second side of iron bar was in hand of victim and victim electrocuted. Line to building horizontal distance is 2.6 mtrs away so this fatal accident occurred due to the victim’s own fault.   Victim himself is responsible no any suggestion victim is resposible Victim resposible Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 9 Victim himself is responsible no any suggestion victim is resposible NA Village meeting and khedut shibirs are arranged to educate people about electrical safety Village meeting and khedut shibirs are arranged to educate people about electrical safety
94 JND Gundaran, Shri  Lavdeepbhai   Hareshbhai  Shinghava 31.12.16 FHO As per information received from TALALA police station vide letter dated 27.01.2017 received on 30.01.2017 about fatal accident occurred at vill Gundran on 31/12/2016. So, in this regard, site is visited by the under signed.  As per eye witness statement, victim had himself with about 17 feet long iron pipe in his hand to snapping ambli from tree branches nearer to 11 KV o/h Madhupur ag feeder  line. It is also stated by the eye witness that due to unbalance of long iron pipe, victim may come into the induction zone and hence may converted in to fatal accident. Horizontal and vertical distance is as per rules. Victim unintentionally came in contact with 11 KV line so victim himself responsible .it is to state that no tripping in 11KV Madhupur line during accident time. Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 10 CEI report not received CEI report not received CEI report not received Village meeting and khedut shibirs are arranged to educate people about electrical safety Village meeting and khedut shibirs are arranged to educate people about electrical safety
95 JND Bhutdi, Shri  Kiritbhai   Dhirajbhai  Padya 27.02.17 NFHD Shri P.D.Trivedi, LI Has got the complaint for jumper work from office. To rectify the complaint he has taken line clear from 66 KV Bhutadi s/s by SMS, in connection with this he has got confirmation SMS from SS operator on receipt of SMS Shri P.D.Trivedi instructed victim for earthing and short the line, during this time victim has got electric shock and burns in his hand. During preliminary investigation it was found that the line clear confirmed message done by Shri Shirajbhai Firozbhai Raes SBO as 66 KV Bhutadi SS , but actually he has not proper filled  L.C. Nor done power off. And this accident was took place. At present necessary inquiry is initiated by GETCO & PGVCL ,during this investigation Sh. Shirajbhai Firozbhai Raes  SBO of 66 KV Bhutadi SS has confessed that he has made confirmation SMS without power off for 11 KV Bhutadi AG feeder.  However detailed investigation is under process. Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 11 CEI report not received CEI report not received CEI report not received Safety meetings are arranged with staff in presence of contractor Safety meetings are arranged with staff in presence of contractor
96 JND Natadiya, Leopard Of Shri Forest Department 02.03.17 FA A fatal electrical accident occurred to leopard while he might have climbed on transformer structure for hunt and come in contact with live 11 KV side stud and fatal accident occurred.  Report not received NA NA NA 12 CEI report not received CEI report not received CEI report not received Na NA
97 JND Pandva, Buffalo Of Smt Deviben Devayatbhai Solanki 28.03.17 FA As per eyewitness statement, 11 KV PSC pole situated at farm near water flow (irrigation) due to flow of water and high wind pressure PSC pole fall down on wall and broke down and buffalo came in contact with live wire so buffalo got electrocuted and died on spot.   Report not received NA NA New pole erected &  Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 13 CEI report not received CEI report not received CEI report not received New pole erected  NEW POLE ERECTED 
98 BVN Timba - Shri. Vishvajitsinh Ranjitsinh Gohil owner of 2 Bullock 04.10.16 FA One conductor of L.T Line from AG group of sh.Ranchhodbhai Dayalbhai bhojani was snapped due to wind and Rain. When Sh. Rajubhai Ranchhodbhai vaghani (Person of Owner) was passing with his Bullocks from this Road. Both bullocks touched the snapped conduct of L.t line and electrocuted. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC centre" during khedut-shibir & village meeting regularly. 1 CEI Pending CEI Pending CEI Pending Deteriorated conductor replaced
99 BVN Timba - Shri. Vishvajitsinh Ranjitsinh Gohil owner of 2 Bullock 04.10.16 FA One conductor of L.T Line from AG group of sh.Ranchhodbhai Dayalbhai bhojani was snapped due to wind and Rain. When Sh. Rajubhai Ranchhodbhai vaghani (Person of Owner) was passing with his Bullocks from this Road. Both bullocks touched the snapped conduct of L.t line and electrocuted. Report not received NA NA Deteriorated conductor replaced & Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC centre" during khedut-shibir & village meeting regularly. 2 CEI Pending CEI Pending CEI Pending Deteriorated conductor replaced
100 BVN Bhavnagar City - Shri. Godiya Ishvarbhai Ambarambhai 24.09.16 FHO Victim was labour, who went to deliver sand. It was dumped in a hydraulic truck. While unloading of truck, driver took the dumper up and had half of the sand empty from dumper and further to unload sand dumper moved further up. Ultimately dumper touched 3 ph 4 wire LT line with guarding. Clearance of LT line is 18 feet. Victim was standing on earth with one hand touched with dumper and got electric shock. No one inform this accident to Sdn office. After receipt of PM report and police punchnama, accident reported. Detail investigation follows. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 3 CEI Pending CEI Pending CEI Pending Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
101 BVN Ramgadh - Shri. Ghandhyambhai D Makvana 27.10.16 NFHD Victim Shree Ganshyam D. Makwana doing maintenance work with Varal AG Feeder and Line Clear taken for Varal AG Feeder and Ramgadh JGY feeder Since 11:00 AM Date 27-10-2016 At Approx. 1:15 PM accidently power comes with Varal AG feeder and victim got electric shock. Reason for power comes with Varal AG feeder is under investigation. Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 4 CEI Pending CEI Pending CEI Pending Strictly instruction given to all line staff to use safety measures & tools while working on line.
102 BVN Kharakdi - Shri. Jitendrabhai Gordhandas Vakani 24.10.16 NFHD Shri J.G.Vakani Working on 11KV Kharakdi Ag feeder of new jumper work LC already taken from Kharakdi SS by Shri P.J.Jadeja. During that time jumper fail of 11KV Samadhiyala AG at Substation yard. So shri P.J.Jadeja took LC of 11 KV Samadhiyala ag at substation in presence of operator and technician both. After completion of Jumper work Shri P.J.Jadeja return LC of Samadhiyala AG feeder by Sign at Substation, But by mistake technician shri. Boricha made on 11 KV Kharakdi ag feeder. In place of 11 KV samadhiyala AG So accident occur on 11 KV kharakdi AG feeder. Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 5 CEI Pending CEI Pending CEI Pending Strictly instruction given to all line staff to use safety measures & tools while working on line.
103 BVN Moti Jagdhar - Daxaben Gunabhai Nakum 10.10.16 NFHO While victim was working in farm for Grass cutting, she came into induction zone of 11kv Pole which was tilted recently due to heavy rain, and its conductor was live, due to 11 KV induction victim got electric shock. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 6 CEI Pending CEI Pending CEI Pending Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
104 BVN Bhavnagar City - Shri.Divyarajsinh Ranjitsinh Jadeja 11.11.16 NFHO Non-fatal human accident occurred due to victim was try to remove kite from 11 KV overhead line with the help of iron rod and got electric shock. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 7 CEI Pending CEI Pending CEI Pending Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
105 BVN Devaliya - Shri. Ankitbhai Arvindbhai Vaja 11.12.16 NFHO On Dated 11.12.2016 maintenance work on Makhaniya JGY feeder under coastal scheme carried out by contractor Shri M A Kachwala. During maintenance work about at 17:15 Victim Shri Ankitbhai Arvindbhai Vaja doing pole earthing and climb on pole of 11kv Makhaniya JGY feeder on location no. Dev/Mak/027/JGY with GI wire. During climbing on pole GI wire in his hand got in contact with tap line of 11 KV Jaleshwar AG feeder and he got shock and fall down from pole Report not received NA NA Instructed to create awareness for safety amongst contractor in contractor meetings 8 CEI Pending CEI Pending CEI Pending Instructed to create awareness for safety amongst contractor in contractor meetings
106 BVN Mahuva - Shri. Makabhai Tejabhai Bharvad owner of 1 Buffalo She  06.01.17 FA Buffalo came in contact with Guy wire and rubbing the guy wire with its  body and at that time guy snap and guy wire touch with T.C D.O jumper and leakage current passed through guy wire and buffalo got shock and electrocuted Report not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC centre" during khedut-shibir & village meeting regularly. 9 CEI Pending CEI Pending CEI Pending Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC centre" during khedut-shibir & village meeting regularly.
107 BVN Shihor - Shri. Ghanshyambhai Chhaganbhai Chouhan owner of 1 Cow 01.03.17 FA Dropper phase wire tapped from ABC cable touched the round pole (iron pole) & it became live and cow passing nearby came in contact with this live pole and got electric shock.  Report not received NA NA Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC centre" during khedut-shibir & village meeting regularly. 10 CEI Pending CEI Pending CEI Pending Awareness among general public regarding electrical safety "not tied the animals near the pole/ TC centre" during khedut-shibir & village meeting regularly.
108 BVN Bhavnagar City - Shri. Bhalabhai Mohanbhai Nayaka 06.03.17 FHO Victim was working on removal of overhead dead line of 11 KV Upvan AG feeder. During removal of conductor of Upvan AG feeder the conductor of Upvan AG feeder may be came in induction zone at nearby crossing of 11 KV Chitra urban feeder and victim got electric shock and fall down from pole and electrocuted. Report not received NA NA Instructed to create awareness for safety amongst contractor in contractor meetings 11 CEI Pending CEI Pending CEI Pending Instructed to create awareness for safety amongst contractor in contractor meetings
109 BVN Akwada - Shri. Shambhubhai Jerambhai Gohil 23.03.17 FHO Occurrence of accident as loaded concert trolley victim might to want unloading hence he was up lifted trolley and as up lifted position driven that vehicle torus no:GJ12W9331 and trolley touched our 11 KV salt feeder line (location between GHO/BHU SS/Salt/276JGY to GHO/BHU SS/Salt/277JGY). Hence live current passed in whole body of the torus metal portion and electricity effect occurred with tyres and 11 KV line and resulted two tyres punctured of this vehicle and due to above position and after 11 KV current grounded unsafe driving by victim himself and unknown power of electricity hence above situation created and he was electrocuted. There is no any fault of PGVCL company's line position, work or anything all. But driver/victim was himself responsible for this unfortunately accident happened. Our 11 KV line vertical ground clearance to conductor is found more than 20 ft. Even though slight V cross arm melting due to above situation. Report not received NA NA Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly. 12 CEI Pending CEI Pending CEI Pending Awareness among general public regarding electrical safety "Keep safe distance from Electrical line & Network of PGVCL" during khedut-shibir & village meeting regularly.
110 BTD Bhimdad, Cow of Shri Gabhabhai Masarubhai Saniya  14.10.16 FA As on dtd. 14.10.2016 at about 6:00 AM, neutral conductor broken from shackle insulator of LT Pole & current flows from Cow If PGVCL done maintenance of HT Line,PGVCL insulate the 1Ph AB Cable nutral, PGVCL done proper earthing then this accident may not occurred If PGVCL done maintenance of HT Line,PGVCL insulate the 1Ph AB Cable nutral, PGVCL done proper earthing then this accident may not occurred Yes Bare canductor replaced by 2 core AB cable and New TC earthing provided and new Distribution box provided & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 1 If PGVCL done maintenance of HT Line,PGVCL insulate the 1Ph AB Cable nutral, PGVCL done proper earthing then this accident may not occurred If PGVCL done maintenance of HT Line,PGVCL insulate the 1Ph AB Cable nutral, PGVCL done proper earthing then this accident may not occurred Yes Bare canductor replaced by 2 core AB cable and New TC earthing provided and new Distribution box provided
111 AMR Vadli,1-Cow Of Arjanbhai Gelabhai Parmar 03.10.16 FA There is a DP structure with DO point. Due to rain and wind outgoing jumper of R phase burnt and jumper is hanging. Due to wind this jumper repeatedly and momentary touching to guy insulator, making guy wire live momentary between insulator to ground. Sparking spot also found on guy wire and tripping in feeder at 04:50 pm. During this time cow passing near DP Structure accidentally came in contact to guy wire and get electrocuted resulted in fatal electrical accident. Feeder was in 3 phase shedule.pm report awaiting and further investigation in progress. Leakage current pass from broken (hanging) jumper to guy Provide insulated jumper and provide guy insulator at proper height. Yes Detailed HT line maintenance carried out and guy insulator provided at proper height & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 1 Leakage current pass from broken (hanging) jumper to guy Provide insulated jumper and provide guy insulator at proper height. Yes Detailed HT line maintenance carried out and guy insulator provided at proper height.
112 AMR Lathi,1-Cow Of Bhanubhai Hamirbhai Bhuva 04.10.16 FA On the receipt of application of cow owner declaring fatal electrical accident to his cow site visited today. At site there is a do dp provided with guy on both side. Victim was found at one guy of that DP. At site no leakage current found at dp as well as tripping on that feeder as per log sheet data of 66 kv ss. As post mortem report is awaiting and further investigation is under process actual reason may come to know after that Report not received NA NA Detailed HT line maintenance carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 2 Report yet not received NA NA Detailed HT line maintenance carried out
113 AMR Dhareshwar,1-Sheep Of Shri Pravinbhai Chhanabhai Kukad 06.10.16 FA There is a village TC of Dhareshwar village (named by Dharnath Mandir valu 63 KVA TC). At the time of accident there was a rain. Due to rain or unknown reason DT meter burnt and damage CT coil cable of DT meter came in contact with earthing  wire making wet pole and surrounding live and at that moment both sheep passing near PSC pole, might came in contact in leakage current and so electrocuted ,resulting in fatal electrical accident. Leakage current from CT coil of DT meter. Regular maintenance of transformer like proper earthing and circuit breaker at LT side. Yes Transformer maintenance carried out and fuse provided at LT side & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 3 Leakage current from CT coil of DT meter. Regular maintenance of transformer like proper earthing and circuit breaker at LT side. Yes Transformer maintenance carried out and fuse provided at LT side.
114 AMR Dhareshwar,1-Sheep Of Shri Pravinbhai Chhanabhai Kukad 06.10.16 FA There is a village TC of Dhareshwar village (named by Dharnath Mandir valu 63 KVA TC). At the time of accident there was a rain. Due to rain or unknown reason DT meter burnt and damage CT coil cable of DT meter came in contact with earthing  wire making wet pole and surrounding live and at that moment both sheep passing near PSC pole, might came in contact in leakage current and so electrocuted ,resulting in fatal electrical accident. Leakage current from CT coil of DT meter. Regular maintenance of transformer like proper earthing and circuit breaker at LT side. Yes Transformer maintenance carried out and fuse provided at LT side & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 4 Leakage current from CT coil of DT meter. Regular maintenance of transformer like proper earthing and circuit breaker at LT side. Yes Transformer maintenance carried out and fuse provided at LT side.
115 AMR Sankrola,1-Buffallo Of Shri Virambhai Mangabhai Shiyal 07.10.16 FA Accident place was DP of existing 63 KVA JGY TC of village Sankrola of WW Connection. There is a leakage current in neutral of transformer earthing buffalo come near to the earthing due to linkage current of neutral earthing buffalo got electric shock and died at the time.at the time finding of linkage current there is a one water works connection distance approx. 8 to 10 meter the electric motor of that connection is short internally short body it cause of leakage current.  Due to leakage current from neutral of transformer due to poor earthing. Provide proper earthing & provide cut-out fuse at LT line side. Yes Transformer maintenance like reactivation of earthing and provide fuse at LT side carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 5 Due to leakage current from neutral of transformer due to poor earthing. Provide proper earthing & provide cut-out fuse at LT line side. Yes Transformer maintenance like reactivation of earthing and provide fuse at LT side carried out
116 AMR Zar,Dipakbhai Karshanbhai Parmar(E.A.) 08.10.16 NFHD After taking LC of Zar AG and Somnath JGY( there is only one crossing of this feeder) by line inspector and line short earth done by co-worker, victim were helmet climb on DP. He was doing jumper of TC at farm of Shri Musabhai Umarbhai Rathod vill. Zar and suddenly somehow power on and victim was electrocuted as per information collected till now and primary investigation done. Sparking evidence is found on GI where wire of chain used to short line was connected .further detail investigation is in progress. Report not received NA NA Strictly instruction given to all line staff to use safety measures & tools while working on line by weekly safety meeting. 6 Report yet not received NA NA Awareness among general departmental staff regarding safety in every safety meeting
117 AMR Dron,Sadiqbhai Kalubhai Chauhan 12.10.16 NFHO As per statement of victim relative he is mentally disturbed and inadvertently climbed up to the transformer centre situated at village Dron near bus stand and touched the TC DO so get electrocuted and resulting in non-fatal accident. All electrical networks checked and found ok. Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 7 Report yet not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha
118 AMR Delvada,Maheshbhai Lakhabhai Makvana(Contractor) 26.12.16 FHO While conversion from LVDS to HVDS by isolation do fuse of this group, stringing work was in progress. Work of two conductors stringing with pin binding completed. While stringing third conductor; it was obstructed in babul tree. So while snatching this conductor forcefully; it bounce and accidently touches to live line of 11KV Shyamkund JGY feeder passing over 11kv Delwada AG feeder and victim fallen on ground. He immediately shifted to hospital where he declared dead. Exist JGY feeder is provided with t joint to increase height. Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 8 Report yet not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha
119 AMR Sultanpur,Rahulbhai Rameshbhai Vaghela(Contractor) 27.02.17 FHO Victim was going to start work on transformer centre without use of safety tools and before any permission of authorized person at that time he came in contact with live conductor and got electric shock. Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 9 Report yet not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha
120 AMR Shanavankiya,1-Buffallo Of Shri Keshubhai Ranabhai Dalvadiya 05.03.17 FA Due to tree branches fallen on line , conductor  of 11 KV Shanadungar ag is snapped down and  buffalo came in contact with  live  broken HT  wire at about 01:00 pm near Shitla Mandir of Sanavakiya village that cause buffalo gets electric shock and died on place and Fatal animal accident was occurred.  Report not received NA NA Detailed HT line maintenance carried out & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 10 Report yet not received NA NA Detailed HT line maintenance carried out
121 AMR Lasa,Rajubhai Chhaganbhai Tadvi 07.03.17 FHO Victim was a labour of farmer Shri Arjanbhai Bhadabhai Kotadiya at village Lasa. While doing tree cutting work standing on ground and under ag. LT Line without prior permission / intimation to utility, tree branches fall on LT live line and broke the conductor and accidently live conductor fall on victim’s mouth and got shocked. After accident victim shifted to civil hospital Khambha for further treatment where he declared dead. So accident took place due to victim careless activity under PGVCL network. Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 11 Report yet not received NA NA Awareness among general public regarding safety in every khedut shibir/gramsabha
122 SNR Joravarnagar, Owner Of Buffalo Of Shri Devkaranbhai Gagjibhai Chotiya 21.11.16 FA A fatal accident occurred to a buffalo due to wet area surrounding LT PSC pole and on the pole live parts of street light fixture joint came into the contact of earthing wire of PSC pole where a buffalo came in the contact of earthing wire which is resulted into the fatal accident to a buffalo. Report not received NA NA New wiring of street light done by Nagar Palica & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 1 Awaited NA NA New wiring of street light done by Nagar Palica. 
123 SNR Bharad, Owner Of Buffalo Of Shri Natubhai Banesang Parmar 12.04.17 FA At villag Bharad on HT pole of JGY feeder one phase conductor of line slipped from Pin Binding & hold on V-Cross Arm at that time feeder was not tripped so leakage current passed through earth wire of HT Pole & buffalo passing near the pole came in contact with earth wire and electrocuted. Report not received NA NA Earthing reactivation of pole done & Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 2 Awaited NA NA Earthing reactivation of pole done.
124 SNR Muli, Shri. Dudabhai Galabhai Zala 23.01.17 FHO On date 24-01-2017 at approximately 9:00 Hrs. JE Shri M D PRAJAPATI was informed from police station that fatal electrical accident has occurred to Shri. Gugabhai Galabhai Zala No any person from the village or relatives of the deceased informed MULI PGVCL regarding the accident. The person was doing to take unauthorized single phase supply from 11 KV Mandavray AG fdr and that time Mandvaray AG fdr was in three phase supply and the person was hooking with that 11 KV line to capture power from line for use of unauthorized power supply and he was contact with the 11 KV line of hooking wire and got electric shock and immediately death occurs. Report not received NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly 3 Awaited NA NA Awareness among general public regarding electrical safety during khedut-shibir & village meeting regularly
411