Performa – SoP 002: Action taken report for safety measures complied for the accidents occurred
Sr Circle Location of
Accident and
details of the victim
Date of
occurrence
Type of
Accident
Cause of Accident Findings
of CEI / EI / AEI
Remedies suggested
by CEI /EI / AEI in
various cases
Whether the
remedy
suggested
is complied
Action taken to
avoid recurrence
of such Accident
1 RCC Kubaliyapara, Chunarwada Chowke,Rajkot,                                Shivkumar Shambhubhai Chudasma 09.4.2014 NFHOS While Victim was siting on muffing of 11KV Thorala Feeder pole no.DUD/THO/079/L-003/DT.25 at that time suddenly squerrel come in contact of DO fuse of near by another 5KVA DT and due to short circuted current was passed through existing running earth wire on line and victim got shock. Report yet not received NA NA Proper Maintenance Carried out
2 RCC Raiyagam, Nr Sitaram Floor mill, Nr Parmar Nivas,Raiya Road, Rajkot,          Cow of Shri. Tihabhai Bharatbhai Labariya 21.04.2014 FA Because of continuous erosion of insulation of single phase service wire by touching the guy wire in vicinity, it has resulting in open & as cyclonic wind was observed on the evening of 20-4-2014, guy wire has come in contact with open phase & leakage current from service phase to guy to ground through cow body passed resulted in electric shock. Report yet not received NA NA 1. Replacement of deteriorated service line 2. Tightening of loose guy.
3 RCC B/H Meera Udhyog 4 x 6 Corner, in wokla ne Tecnocast,Rajkot,                    Sanjaybhai Devrajbhai Huletiya 12.05.2014 FHOS Due to heavy wind pressure and rain,a tree branches which were nearer to LT Line broken and fallen on AG LT line conductor and due to that on conductor of AG LT Line was broken and fallen on ground (West Land-Wokla) on next day ,victim may come in contact with broken Live AG LT Line conductor during collecting industrial west and he got electric shock. Report yet not received NA NA Open conductor replaced by providing AB cable and maintenance of LT Line is carried out.
4 RCC Kailash Park, Morbi Road,Rajkot,               Cow of Sri Bagvanji Bachubhai Matia  16.06.2014 FA  At LT pole No 021 piece of 1 feet (approx) of remaining portion of removed “lungar” wire was hanging and live conductor of this wire come in touch with guarding wire so leakage current pass to next pole through guarding wire. At this next pole through earthing wire leakage current passed to earth and surrounding land of the pole get electrically charged ,so as soon as the cow came in the vicinity of the pole get electric shock due to step voltage and met fatal accident.  Report yet not received NA NA 1. One should not fix un authorized "Lunger".  2.  LT line maintenance.  
5 RCC Ganshyamnagar Main Road, Opp Swastik School,Rajkot                                          Cow of Sri Hareshbhai Kanabhai Dholakiya 10.07.2014 FA  On date 10-07-14 accident took place near HT line girder pole No 032 in which leakage current was found passing through it. Guarding to the HT pole provided continuous from previous ploes at which HT and LT line erected on comman poles. On investigation and by switching “OFF” power of near by T/c leakage current in HT pole stopped and then on switching “ON” power of the T/c leakage current not fount in HT pole .So thus it concluded due windy and rainy condition earth wire of HT-LT line common pole may touch live part of LT line live wire and caused momentary leakage current in earth wire and as 11 KV guarding  fitted on this common pole leakage  current passed  in guarding wire and through it in HT line pole at which accident took place. So as soon as cow comes in vicinity of the pole got electric shock and met fatal accident. Report yet not received NA NA 1) Proper fitting of earth wire 2) Providing of A.B. cable in LT line
6 RCC B/H Rajkamal Petrol Pum, Punitnagar Main Road,Rajkot,                                           Cow of Surabhai Sagrambhai Chavda 13.07.2014 FA On date 13-07-14 Accident took place near T/C center PUN/SUP/039/DT-31. As message of accident received by the fault center line staff and Deputy Engineer immediately visited the site. At site a cow found laying dead near transformer center. At time of visit it was found that no any leakage current passing through T/C earthing, pole or in any near by LT pole. It was rainy and windy atmosphere at time of accident. So it concluded that due to momentary touching of Phase wire with neutral wire leakage current may passed in T/C earthing. So as soon as Cow comes in vicinity of T/C may got electric shock and met fatal accident. Report yet not received NA NA T/C earthing reactive with PVC rigid pipe.
7 RCC Velnathpara,Morbi Road,Rajkot,          Artiben Vijaybhai  Sitapara 31.07.2014 NFHOS Accident took place at LT line pole at which street light fixture fitted and was short-circuited so leakage current was passing through PSC pole .As soon as victim came in contact with the pole got electric shock and met with non fatal accident .Inspection of site carried out in present of Asst Electrical inspector and R.M.C. staff  Report yet not received NA NA informed to Dy. Engi. East division RMC, about this lacuna and for necessary action.
8 RCC Manharpur-1, Jamnagar Road, Rajkot, Bhupatbhai Chakubhai Parajiya 03.08.2014 FHOS Accident took place while victim cutting the tree branches by “Dhariyu” a metal tree cutting tool in front of his house while that it come in contact with dish cable wire which was hanging by metal G.I. wire and end of this metal wire was fitted at LT line PSC pole at which illegal streetlight fixture was fitted which was short circuited so leakage current was passing through it to metal wire of disc cable  so as soon as victim’s metal tree cutting tool (“dhariyu”) come in contact this wire got electric shock and met with fatal accident  Report yet not received NA NA Removal of disc cable having iron wire and short circuited st. light fixture.
9 RCC Shakti Society, Navagam,Rajkot,      Amitbhai Devjibhai Rathod 14.08.2014 NFHOS Accident took place while victim throw away old telephone wire which was hanging across the street near the transformer centre at that time it touched  the DO fuse  of transformer  and got electric shock and met Non fatal accident  Report yet not received NA NA Write letter to telephone depat. For necessary maintenance and precaution in future.
10 RCC Nana Mava Main Road, Laxminagar road Corner,Rajkot,                                       Samir Salimbhai Dodhiya 18.09.2014 NFHD Victim and other line staff were at the site for stringing of broken guard wire from existing pole. Victim was fall down from tower ladder due to slip of leg and fall down on road. So injury occurred in head Report yet not received NA NA All the line staffs are instructed to carry out work under the supervision of competent staff and by using all safety equipment.
11 RCC Ganteshwar Village, Nr. SRP Campus, Jamnagar Road, Rajkot,                         Kiran Vaghsinh Bariya  29.09.2014 NFHOS Accident took place while victims were Dismentalling 11KV GO Switch from idle (without 11KV line) PSC pole of 11KV Raiyadhar WW feeder. They were climbing down after removing GO Switch from the pole at that time somehow dish cable which was hanged on same idle pole and across the 132KV D/C Nyara-Vajdi and Nyara-Vikram line come in induction zone of live 132KV Nyara-Vajdi line. Hence, both victims got electric shock and met with Non Fatal accident Report yet not received NA NA 1) Removal of Dish Cable      2) one should be careful while working on line and not start work in absent of supervisor
12 RCC Ganteshwar Village, Nr. SRP Campus, Jamnagar Road, Rajkot,                       Babrik Chanabhai Baria 29.09.2014 NFHOS Accident took place while victims were Dismentalling 11KV GO Switch from idle (without 11KV line) PSC pole of 11KV Raiyadhar WW feeder. They were climbing down after removing GO Switch from the pole at that time somehow dish cable which was hanged on same idle pole and across the 132KV D/C Nyara-Vajdi and Nyara-Vikram line come in induction zone of live 132KV Nyara-Vajdi line. Hence, both victims got electric shock and met with Non Fatal accident Report yet not received NA NA 1) Removal of Dish Cable      2) one should be careful while working on line and not start work in absent of supervisor
13 RRC PANELI & Sumit bhai Babubhai Degama 23.04.14 FHOS Victim went on terrace to catch pigeon on his neighbor’s terrace from his terrace. He jumped over from small parapet between  his house and neighbor’s house. While crossing the small parapet he loosen his balance. Though no any protection wall on terrace of his neighbor, he caught live wire to avoid him self to fallen down from balcony to “Vokala”.  Resultantly he caught  11 kV live wire situated 1 feet away from his balcony and approximately 4 feet away from his wall. Thus he got an electric shock and expired.
       
14 RRC MOTI VAVDI & BUFFALOW  12.05.14 FA On Dt.- 12.5.14 There was heavy wind pressure. Due to this disc insulator got damaged  and conductor was broken of 11 kv Mahadev JGY feeder of DT-06. Buffalow and a calf was fasten under the 11 kv line by owner.. When the conductor snapped it directly fallen down on the buffalow standing under the line and got an electric shock, At the same time calf which was fasten near the buffalow came in contact with snapped conductor and got an electric shocked and both died.        
15 RRC MOTI VAVDI & A CALF OF SHRI KARSHANBHAI AALABHAI MORI  12.05.14 FA On Dt.- 12.5.14 There was heavy wind pressure. Due to this disc insulator got damaged  and conductor was broken of 11 kv Mahadev JGY feeder of DT-06. Buffalow and a calf was fasten under the 11 kv line by owner.. When the conductor snapped it directly fallen down on the buffalow standing under the line and got an electric shock, At the same time calf which was fasten near the buffalow came in contact with snapped conductor and got an electric shocked and both died.        
16 RRC RAYDI & SHRI DILIPBHAI JASMATBHAI AKBARI 04.05.14 NFHD DEPARTMENTAL NONFATAL MECHANICAL ACCIDENT OCCURRED TO SHRI D.J.AKBARI (ELECT. ASST.) AT VILLAGE RAYDI ON DT.;-4.5.14 AT 04:00 PM. 11 KV TARAVADA JGY FEEDER WAS ON FAULT AT 3:15 P.M. D.J.AKBARI WAS INFORMED BY 66KV RAYDI SS OPERATOR AS WELL AS CONSUMER FOR NOT GETTING POWER SUPPLY FROM 11 KV TARAVADA JGY FEEDER. SO HE HAS TAKEN LINE CLEAR FROM HIS MOBILE OF 11 KV TARAVADA JGY FOR JUMPERING WORK AT LOCATION NO.- RYD/TRD/007 AFTER THAT HE CLIMBED ON THAT PSC POLE DURING THIS PEROID HE LOST HIS BODY BALANCE FALLEN DOWN FROM THE TOP OF THE POE TO THEW GROUND AND THIS DEPT. NNON FATAL ACCIEDENT OCCURED.        
17 RRC Chavandi & 1 NOS OF BUFFALO OF Shri. Jetabhai Babubhai Devipujak 17.05.14 FA Animal fatal accident occurred to a 1 buffalo & 2 cow at village chanvandi ag area. One  Y phase HT Line conductor was broken from disc anchor at ag transfromer location no NVG/POL/142/R064/DT65 when one buffalo & two cow passes near this snapped 11 kv conductor they all came in contact with this live wire and got electrocuted        
18 RRC Chavandi & 1 COW OF Shri. Mahavirsinh Amarsang Chauhan
17.05.14 FA Animal fatal accident occurred to a 1 buffalo & 2 cow at village chanvandi ag area. One  Y phase HT Line conductor was broken from disc anchor at ag transfromer location no NVG/POL/142/R064/DT65 when one buffalo & two cow passes near this snapped 11 kv conductor they all came in contact with this live wire and got electrocuted        
19 RRC Chavandi & 1 COW OF Shri. Natubha Agarsang Chauhan 17.05.14 FA Animal fatal accident occurred to a 1 buffalo & 2 cow at village chanvandi ag area. One  Y phase HT Line conductor was broken from disc anchor at ag transfromer location no NVG/POL/142/R064/DT65 when one buffalo & two cow passes near this snapped 11 kv conductor they all came in contact with this live wire and got electrocuted        
20 RRC PATYADI & SHRI R.K.GORWADIYA(ELECT. ASST.) 27.05.14 NFHD ON DT:- 27.5.14 ACCIDENT OCCURRED ON AG TRANSFORMER OF PATYADI AG AREA OF 11KB AMBALIYADA AG FEEDER. FROM THE SITE SITUATION AND STATEMENT OF 1ST SEEING MR. R.K.GORWADIYA IS DOING TRANSFORMER REPAIRING WORK ON TC LOCATION NO.;-KOL/AMB/048/R118/DT41. DURING THE BINDING WORK OF JUMPER OF 11 KV SIDE SUDDENDLY HE GOT SHOCK AND SHOUTED LOUDLY AND FALLEN DOWN ON DO ANGLE.ON DT.-27.5.14 LINE CLEAR OF 11KV AMBALYADA AG WAS TAKEN BY ALM SHRI. G.J.JADEJA TO ATTEND COMPLAINT.11KV TAPPING AB SWTCH WAS ALSO CUT FOR MORE PROTECTION AND ALSO LINE WAS DISCHARGE.LINE CLEAR WAS TAKEN AT 7:00 PM AND 1 LOCATION WAS ALSO ATTENDED BUT WHEN LINE WORK OF 2 ND LOACTION WAS IN PROGRESS AROUND 07:30 PM SUDENDLY POWER CAME FROM UNKNOWN SOURCE DETAIL INVESTIGATION IS UNDER PROGRESS.         
21 RRC NAVANARANKA & ARVINDBHAI DEVABHAI PARMAR 10.06.14 NFHD WHILE VICTIM WAS DOING REPAIRING WORK AT VILLAGE TC OF NAVANARANKA HE HAD EXPERINCED ELECTRIC SHOCK WHILE REMOVING THE DO FUSE OF THE ABOVE TC WITH THE USE OF PLIER WITHOUT HANDGLOVES AFTER ISOLATING THE LINE BUT WITHOUT DISCHARGING THE LINE.SO GOT ELECTRIC SHOCK.          
22 RRC RAMOD & NANJIBHAI THANABHAI PARGHI 03.06.14 NFHD WHILE VICTIM WAS ATTENDING THE COMPLAINT OF GHABSHYAM MULU AG GROUP TC HE CLIMBED ON TC AFTER TAKING THE HANDTRIP FROM THE SUBSTATION ON THAT DAY THERE WAS HEAVY WIND PRESSURE AND LIGHTING STROKE.WHILE HE WAS ATTENDING THE SERVICE COMPLAINT LIGHTUNG STROKE  OCCURED NEAR ACCIDENT LOCATION AND VICTIM GOT THREATNED AND FALLEN DOWN FROM TC STRUCTURE AND DEPT. MECHANICAL ACCIDENT OCCURED.        
23 RRC TRAMBA & DIPAKBHAI ISHWARBHAI MAKVANA 23.06.14 NFHD SINCE FEEDER NAMED RAJKOT LODHIKA SANGH SHOWING ONE PHASE DIM, SO VICTIM WAS DOING GROUND PATROLLING OF THE FEEDER AND ALSO LINE CLEAR OF THE FEEDER WAS NOT TAKEN. HOWEVER DUE TO ANY REASON THE VICTIM CLIMBED ON THE FEEDER GANG SWITCH AND CAME IN CONTACT WITH THE LIVE PART OF THE LINE AND GOT ELECTRIC SHOCK AND FALLEN DOWN AND MET WITH NON FATAL ACCIDENT.        
24 RRC AMBARDI & PRAVINBHAI KALUBHAI KAMEJALIYA 05.07.14 NFHOS VICTIM CLIMBED UNAUTHORISED ON TRANSFORMER CENTRE AND TRY TO CLOSE THE D.O.FUSE BY HIS LEFT  HAND AT THE SAME TIME 1-PHASE POWER SUPPLY WAS LIVE ON 11KV NAVAGAM AG FEEDER.SO VICTIM CAME IN CONTACT WITH LIVE UPPER PART OF D.O FUSE AND GOT ELECTRIC SHOCK AND NON-FATAL ACCIDENT OCCURED.        
25 RRC MAHIKA & BUFFALO OF SHRI. DHALABHAI HIRABHAI SIYAL 13.07.14 FA THERE WAS HEAVT RAIN ON DT.:- 13.7.14 AT VILLAGE MAHIKA. THE AREA SURROUNDING THE DHORA VALU TRANSFORMER CENTRE WAS WET AND THERE WAS LEAKAGE CURRENT PASSING THROUGH THE EARTH WIRE. THE BUFFALO PASSES UNDER THAT T/C BETWEEN THE D.P AND CAME IN CONTACT WITH THE EARTH WIRE AND GOT ELECTROCUTED.        
26 RRC MOTADADVA & BHIKHUBHAI POLABHAI CHOTHANI 14.7.14 FHOS As per PAR of SDO Atkot information regarding this accident was received on date 28.07.2014 from police station and police panchnama done on Dt.:-26.7.14.previously eyewitness shown the accident place in KotdaSangani S.Dn & DE Kotda took eyewitness statement at that site and also police panchnama was carried out at that site. Afterwards police panchnama was carried out on new site under Atkot S.Dn area & DE Atkot visited site and taken statement of eyewitness and owner of sighted T/C.As per statement of eyewitness Sh.Dhirubhai Gela Chavda accident was occured due to victim came in contact with HT line on T/C while doing unauthorize work on T/C.But on site visit no avidence or symptoms of accident found on T/C , wire , structure or psc poles and our PGVCL network found healthy. Detail cause of accident is under investigation.        
27 RRC NAVAGAM & BHAVNABEN RAJUBHAI TALSANIYA 04.07.14 FHOS THE SDO MADHAPAR HAD INFORMED SDO KUVADAVA ON DT.:- 4.7.14 AT 7:57 P.M ON HIS MOBILE REGARDING THE OCCURRENCE OF THE ACCIDENT.AS PER THEIR JOINT INVESTIGATION THE ACCIDENT OCCURRED ON THE TERRECE OF THE SUCHIT SHED OF SH. BHARATBHAI GHOGHABHAI MAKVANA WHICH IS ILLEGALLY EXTENDED TO THE ROAD SIDE HENCE THE DISTANCE BETWEEN THE WALL OF THE TERRECE AND THE NEAR BY 11KV KHIJADIYA FEEDER LINE REDUCED TO APPROX. 1.5 FTS ONLY. AS PER THE STATEMENT OF THE EYEWITNESS ON THE ACCIDENT DAY THE VICTIM CLIMBED ON THE TERRECE OF THE SAME PREMISES AND HER "CHUNARI" BLOWN OFF DUE TO THE WIND TOWARDS THE HT LINE AND WHEN SHE TRIED TO COLLECT THE SAME SHE ACCIDENTLY CAME IN LIVE CONTACT OR THE VICINITY OF 11KV CONDUCTOR STRINGED BETWEEN POLE LOCATIONS NAV.KHI/JGY/108 AND NAV/KHI/JGY/109 AND GOT ELECTRIC SHOCK THE AMBULANCE 108 CALLED AND SHE ADMITTED TO HOSPITAL WHERE SHE DIED.        
28 RRC PADDHARI & KIRANBEN SHAYARBHAI POMANI 12.07.14 FHOS AS INVESTIGTED THE PRILIMINARY REASON OF THE ACCIDNET IS THAT ON THE ACCIDENT NIGHT THE VICTIM KUM. KIRANBEN SHAYARBHAI POMANI WAS PLAYING NEAR HER HOUSE WHERE THE LT LINE PSCPOLE NO.:- 665/28.08.2009 IE ERECTED. THE STREET LIGHT FIXTURE PROVIDED ON THE SAID POLE WAS SHORTED AND HENCE THE POLE IS SHORTED THROUGH THE GI  EARTHING WIRE OF THE POLE. THE PVC RIGID PIPE IS NOT PROVIDED IN EARTHING. HENCE THE VICTIM CAME IN CONTACT WITH WIRE OR POLE GOT ELECTRIC SHOCK AND DIED. THE DETAILED INVESTIGATION REPORT AND THE PM REPORT IS AWAITED.         
29 RRC VEKRI & BUFFFALO OF SHRI. MATHUR HARJI SORATHIA  04.073.1 FA BUFFALO WAS PASSING NEAR TO OLD LT LINE ROUND TUBULAR POLE IN VEKRI VILLAGE , INSULATION OF NEUTRAL WIRE OF ONE SERVICE CONNECTION WAS OPENED DUE TO SALINITY.DUE TO WIND IT WAS TOUCHED TO LT METAL ANGLE , SAME TIME BUFFALO TOUCHED THE TUBULAR POLE AND GOT ELECTROCUTED.        
30 RRC Rupavati & SHE BUFFALO OF SHRI. THOBHAN MAYA TOLIA 01.08.14 FA A DEAD CHAMELEON WAS THERE ON THE LT POLE TOUCHING THE PHASE WIRE AND "C" CLAMP. SO IN CONTINUOS RAIN & HUMID ATMOSPHERE LEAKAGE CURRENT WAS FLOWING THROUGH EARTHING & TOUCH POTENTIAL PRODUCED NEAR TRANSFORMER EARTHING PIT & AS THE BUFFALO PASSED IN BETWEEN TWO POLES OF TRANSFOMER CENTER AND TOUCHED THE EARTH WIRE GOT ELECTRIC SHOCK AND ELECTROCUTED RESULTANTLY.        
31 RRC HADALA & SHE BUFFALO OF SHRI HAKABHAI GANDUBHAI BHARVAD 02.08.14 FA THE VICTIM BUFALO WAS PASSING THROUGH THE ROAD AND IT CAME IN CONTACT WITH THE SNAPPED LT LINE WIRE AT LOCATION KAG/AND/L163 DT 18 OF RAMJIBHAI BHURABHAI VALU AG GROUP AND GOT ELECTRIC SHOCK AND DIED.THE PM REPORT AND DETAIL INVESTIGATION REPORT IS AWAITED.        
32 RRC SAL PIPALIYA & 1) FATAL HUMAN SH. KISHANBHAI JASABHAI RATHOD                      06.08.14 FHOS AS REPORTED BY THE SDO PADDADHARI THE INFORMATION ABOUT THE ACCIDENT HAS BEEN VIEWED ON THE LOCAL EVENING NEWSPAPER "AAJ KAL" ON DT.:- 7.08.14 AND HENCE THE SDO VISITED THE ACCIDENT SITE ON DT.:- 8.8.14 AT 8:00 A.M. AND INVESTIGATED ABOUT THE ACCIDENT IN CONFIRMATION WITH THE LOCAL POLICE STATION. THE VICTIMS WERE WORKING FOR THE TV CABLE STRINGING WORK UNAUTHORISED ON PGVCL PROPERTY 11KV SALPIPALIYA JGY FEEDER BETWEEN THE LOCATIONS MKHZ/SAL/JGY/041 AN /042. WHILE STRINGING THE CABLE THEY ACCIDENTLY CAME IN CONTACT WITH THE LIVE HT WIRE OF THE FEEDER AND GOT ELECTRIC SHOCK. ONE OF THE VICTIM DIED AT THE SITE ITSELF AND OTHER HAS BEEN ADMITTED IN CIVIL HOSPITAL RAJKOT.FURTHER INVESTIGATION AND DOCUMENTATION UNDER PROCESS.         
33 RRC SAL PIPALIYA & 1) NON FATAL HUMAN SH. JATINBHAI KAMLESHBHAI VISHNU 06.08.14 NFHOS AS REPORTED BY THE SDO PADDADHARI THE INFORMATION ABOUT THE ACCIDENT HAS BEEN VIEWED ON THE LOCAL EVENING NEWSPAPER "AAJ KAL" ON DT.:- 7.08.14 AND HENCE THE SDO VISITED THE ACCIDENT SITE ON DT.:- 8.8.14 AT 8:00 A.M. AND INVESTIGATED ABOUT THE ACCIDENT IN CONFIRMATION WITH THE LOCAL POLICE STATION. THE VICTIMS WERE WORKING FOR THE TV CABLE STRINGING WORK UNAUTHORISED ON PGVCL PROPERTY 11KV SALPIPALIYA JGY FEEDER BETWEEN THE LOCATIONS MKHZ/SAL/JGY/041 AN /042. WHILE STRINGING THE CABLE THEY ACCIDENTLY CAME IN CONTACT WITH THE LIVE HT WIRE OF THE FEEDER AND GOT ELECTRIC SHOCK. ONE OF THE VICTIM DIED AT THE SITE ITSELF AND OTHER HAS BEEN ADMITTED IN CIVIL HOSPITAL RAJKOT.FURTHER INVESTIGATION AND DOCUMENTATION UNDER PROCESS.         
34 RRC CHOKI & 1) FATAL HUMAN SH. SOMABHAI PALABHAI ZAPADA 11.08.14 FHOS THE VICTIMS WERE GRAZING THEIR ANIMALS NEAR PIPALVA ROAD WHERE AN IRON WIRE WAS TEID UP WITH TOP OF THE TREE BRANCHAND DUE ANY REASON BOTH VICTIMS PULLED DOWN THAT WIRE AT THAT MOMENT THE WIRE BROKEN DOWN AND SLIPPED AWAY FROM THE TREE BRANCH AND CAME IN CONTACT WITH THE 11 KV PIPALVA AG FEEDER PASSING NEAR THE TREE. THUS GOT ELECTRIC SHOCK AND RESULTING INTO 1 FATAL AND 1 NONFATAL ACCIDENT        
35 RRC CHOKI & NON FATAL HUMAN  SH. GOPALBHAI VAJABHAI ZAPADA  11.08.14 NFHOS THE VICTIMS WERE GRAZING THEIR ANIMALS NEAR PIPALVA ROAD WHERE AN IRON WIRE WAS TEID UP WITH TOP OF THE TREE BRANCHAND DUE ANY REASON BOTH VICTIMS PULLED DOWN THAT WIRE AT THAT MOMENT THE WIRE BROKEN DOWN AND SLIPPED AWAY FROM THE TREE BRANCH AND CAME IN CONTACT WITH THE 11 KV PIPALVA AG FEEDER PASSING NEAR THE TREE. THUS GOT ELECTRIC SHOCK AND RESULTING INTO 1 FATAL AND 1 NONFATAL ACCIDENT        
36 RRC GUNDALA(JAS) & SH. KALYANBHAI MOHANBHAI JOGRAJIYA 04.08.14 NFHOS THIS ACCIDENT CAME TO KNWOLEDGE FROM OUR J.E SH. H.B.SAJKA WHILE CIRCLE CHECKING DRIVE WAS GOING ON AT VILLAGE GUDALA (JAS). THE VICTIM TRT TO REMOVE THE ILLEGAL LUNGAR WIRE WHICH WAS BYPASSING THE METER FROM LT BUSHING OF TRANSFORMER CENTER UNAUTHORISE WAY.POWER SUPPLY OF THE FEEDER WAS ON AND VICTIM CAME IN CONTACT WITH THE LIVE 11 KV LINE AND GOT ELECTRIC SHOCK AND NON FATAL ACCIDENT OCCURED. THE ABOVE CONSUMER IS BOOKED UNDER THEFT AND DISCONNECTED AND F.I.R LAUNCHED BY SDO VINCHHIYA.        
37 RRC JASDAN & COW OF (1) SH. MAHESHBHAI UKABHAI GALIYA  02.09.14 FA ON THE DATE OF ACCIDENT THERE WAS HEAVY RAIN AND WIND PRESSURE, THE VICTIM ANIMALS WERE PASSING ON THE ROAD AND THAT TIME THEY CAME IN CONTACT WITH SNAPPED LT LINE CONDUCTOR AND GOT ELECTROCUTED.        
38 RRC JASDAN & COW OF (1) SH. MAHESHBHAI UKABHAI GALIYA  02.09.14 FA ON THE DATE OF ACCIDENT THERE WAS HEAVY RAIN AND WIND PRESSURE, THE VICTIM ANIMALS WERE PASSING ON THE ROAD AND THAT TIME THEY CAME IN CONTACT WITH SNAPPED LT LINE CONDUCTOR AND GOT ELECTROCUTED.        
39 RRC JASDAN & CALF  ofSH. INDU SANGRAM VAKATAR 02.09.14 FA ON THE DATE OF ACCIDENT THERE WAS HEAVY RAIN AND WIND PRESSURE, THE VICTIM ANIMALS WERE PASSING ON THE ROAD AND THAT TIME THEY CAME IN CONTACT WITH SNAPPED LT LINE CONDUCTOR AND GOT ELECTROCUTED.        
40 RRC Gokhalana & Pratpbhai Nanjibhai Khetariya 21.09.14 NFHOS As per statement of victim’s father victim unauthorized climb on the LT pole (pole no DT-14 L1/3) and got electric shocked and non fatal accident was occurred.        
41 RRC Faldang & Sh.Bhupatbhai Gokalbhai Kihla 28.09.14 FA  On date 28.09.2014 in morning time 66 KV Faldang SS near Faldang village buffalo’s herd was going toward agriculture area with  owner for grazing. At that time due to any reason one buffalo out of them went near the bore type earthing pit of LSTC of 11 KV Rafala AG feeder. This feeder was in 1 ph. Power supplied and in earthing strip power was on. Hence this buffalo was came in contact with that strip and got electric shock and this accident occurred.

       
42 RRC Veraval & Sh.Vijaybhai  Ramniklal  Chavda 14.09.14 NFHD industrial consumer M/S Blossom Kitchenware consumer No.81907-00118-2 lodged the complain no.03 for low voltage complain. Hence the victim Sh.Vijaybhai Ramniklal Chavda (ALM) along with the Sh.K.N.Jadav (Electrical Assistant) went to the said industries to attend the complain. After verifying the transformer, the victim Sh.V.R.Chavda (ALM) climbed on the plastic roof of the shed to check the service cable which is lying on the said roof but accidentally the old deteriorated plastic sheet broken and he fell down from the roof of height about 20 feets and met with a mechanical accident. The victim then admitted to the  wockhardt hospital for further treatment.        
43 RRC Ardoi & Sh. Jaysukhbhai Pravinbhai Bagda 13.09.14 NFHOS On dated 13-Sep-2014, at time approx. 14:03 Hrs an electrical accident has occurred to a boy at Kotda-Ardoi road, opposite to the farm of Pravinbhai Bhikhabhai Bagda, at Ardoi village.
A boy aged about 7-yrs-old due to any reason climbed on the tree from where 11kv Ardoi ADOM feeder is passing nearing to it. Accidentally, victim came in contact with 11 KV line live conductor and got electrical shock and met with non-fatal human electrical accident. There were two eyewitness named, (1)Dineshbhai Devabhai Bagda, (2)Ramjibhai Desha Bhai Bagda of ardoi village who were present at opposite location of accident site.
For further treatment victim was transferred at Government hospital Rajkot. On site, there were black spot found on the conductor of 11kv Ardoi ADOM feeder. A statement of eyewitness was taken and site Rojkam was done and also local police station was informed for above incident. 
       
44 RRC Navagadh & Babubhai Bhikhabhai  15.09.14 FA Victim Buffalo was passing near Rachna vadi valu TC,Dt No-20, 100 KVA ,Village-Navagadh and at that time leakage current was flowing through earth wire and buffalo came in contact with earth wire of transformer center, according it got electric shock and electrocute, resulting into animal fatal accident.        
45 RRC Dhoraji  AG Area & Sh. Hemantbhai Jentibhai Parmar 27.09.14 NFHOS Jentibhai Gangabhai Parmar was given the Work order for fail TC replacement wide W.O.No. DD/T-1/7054 Dt. 25.09.14. Victim Shri Hemnatbhai Jentibhai Parmar ( Contractor’s Labour)  was gone to replace failed T/C at Location No: DRJ/DRJ/082/R002,DT No.27 in 11 Kv Dhoraji AG feeder. Victim has taken line clear permit of 11 KV Datarwadi AG feeder instead of 11 KV Dhoraji AG feeder through Line Inspector Shri V.A.Muchhadiya. Power supply of 11 KV Dhoraji AG feeder is continue in single phase duration. Victim has started activity of T/C replacement without confirm power supply was off or not? Victim has not taken any kind of safety precaution and climb on T/C Structure and touched to left side DO fuse. Due to continuity of power supply victim got electric shock. Also no any supervisor was present at the time of TC replacement work. Hence Non fatal accident occurred. The detail investigation follows.
 
       
46 RRC Nani Marad & Sh . Gobarbhai Alabhai Kodiyatar 29.09.14 FA A Fatal Accident occurred to a buffalo owner Shri Gobar Ala Kodiyatar at village :- Nani Marad. From Site Visit it was found that  Water logged surrounding said transformer due to near pond. At that time Buffalo was passed near transformer center and came in contact with wet place and same time died due to any reason. During investigation switching " ON " the power supply of said T/C. No any leakage current found on whole T/C. The Said accident  may be happened due to minor leakage current of  T/C but actual reason for accident is to be known after receiving P.M. report. Detail Investigation follows.        
47 Morbi GHUNTU
Buffalo of
 Nareshbhai Gangarambhai Soriya
21.04.2014 FA A conductor of 11KV Ghuntu JGY feeder detached from pin point of location# GHU/GHU/070 & fell on ground. Given the conductor was live & the victim buffalo while passing by it came in contact, the victim animal electrocuted. The evening before the accident day there being extreme wind & storm like weather which may have resulted into detachment of the conductor from pinpoint.  Report yet not received NA NA Span has been restrung & guarding has been provided.
48 Morbi SARTANPAR
Vijaybhai Vashrambhai Bahukiya 
25.04.2014 FHD The victim had been attending jumper of 11KV Motto Ind feeder. The feeder’s LC was duly permitted. The victim was restoring jumper of the feeder by climbing over the DP structure location# SRP/MOT/005/R-05. In mean time one of the HT connections in the feeder namely M/S Ador ceramic pvt LTD with consumer# 25789 was in the process of changing over to DG set. The malfunction/ fault in one of the changeover mechanism led to reverse flow of supply of DG set into feeder. Although this may be momentary but was intense enough to cause fatal accident to the victim. Report yet not received NA NA NOTICE ISSUED TO ALL HT CONSUMERS REGARDING PERIODICAL MAINTENANCE & INSPECTION OF DG SET. Further, FIR# 0037/2014 against the directors of ADORE ceramics has been registered which should set deterrent example among consumer fraternity using DG set without effective  protective devices to guard reverse power phenemenon. Also supervisors namely H.K.Chauhan (L.I.) & G.K.Goswami (L.M) have been meted out disciplinary action in transfer & suspension. In addition to disciplinary action, an inquiry is pending against Chargsheet# EE/Wanka/Confidential/HR/DA/HKC/87 & EE/Wanka/Confidential/HR/DA/HKC/88 on 07.06.2014 issued to H.K.Chauhan (L.I.)  & G.K.Goswami (L.M) respectively. Also inquiry panel has been established. A reminder letter# EE/Wanka/Tech/2/5511 on 19.09.2014 has been sent to the concerned Police Sub Inspector inquiring about status quo of registered FIR against the directors of ADORE ceramics. Further, through the letter we have asked whether the concerned accused have been arrested .
49 Morbi DALDI
Gajendrasingh Dausingh
26.05.2014 NFHOS The victim is hired as a labourer by contractor undertaking PGVCL line work. The victim was into line maintenance work of 11KV Kashipar AG feeder emanating from 66KV Daldi S/S. The line clearance permit of the concerned feeder was duly taken by line inspector before commencing the maintenance work of this feeder. Further as a safety/ protective compliance, all 3 phases had been shorted & earthed before commencement of the aforesaid work. However, technician of the 66KV Daldi S/S switched ON the 11KV Kashipar feeder even though line clear permit was not returned. Hence, the victim suffered electric shock and fell down on the ground from the TC center & met with non-fatal electrical accident.  Report yet not received NA NA The personnel who by mistake powered on the feeder depite its LC was not returned had been terminated with immediate effect. The SIMS engineering agency had been awarded the contract to maintan concerned substation on behalf of GETCO. Therefore the Wankaner- EE has wrote letter# EE/WKR/TECH2/5557 on 20.9.2014 to EE (TR) GETCO, 132KVSS insisting to black list the SIMS engineering agency.
50 Morbi BHAVANIGADH
Buffalo
Ghusabhai Sondabhai Koli
03.06.2014 FA The earth wire of the village T/C was cut. The victim buffalo while passing by
came in contact with this earth wire & electrocuted.
Report yet not received NA NA As pasrt  of maintanance the earth wire has been replaced, PVC pipe provided & earthing has been reactivised
51 Morbi MATHAK
Cow of
Jayvantsinh Gumansinh Zala
18.07.2014 FA The live conductor of 3 phase 4 wire LT line snapped & touched the victim cow passing by & thus the cow electrocuted. Report yet not received NA NA The conductor has been replaced. Code Meaning
52 Morbi MORBI
Cow of
Sh Kalu Viha Toriya
25.07.2014 FA The LT Line (Aerial bunch LT) Girder pole# SCY/DT002/C2/016 bearing street light fixture became live as the street light fixture was shorted. The two victim cows passing by this pole electrocuted & accident occurred. Report yet not received NA NA The notice has been issued to the Chief Officer of Nagarpalika to regularly carry out maintenance of all street light fixtures to avoid such accidents in future. FHD Fatal Human Departmental
53 Morbi MORBI
Cow of
 Sh Bhala Kadva
25.07.2014 FA The LT Line (Aerial bunch LT) Girder pole# SCY/DT002/C2/016 bearing street light fixture became live as the street light fixture was shorted. The two victim cows passing by this pole electrocuted & accident occurred. Report yet not received NA NA The notice has been issued to the Chief Officer of Nagarpalika to regularly carry out maintenance of all street light fixtures to avoid such accidents in future. NFHD Non Fatal Human Departmental
54 Morbi Rafaleshwar
Shubhash Manganbhai Bariya
28.07.2014 NFHOS The victims were working on the JGY feeder, when the said feeder was powered on. Report yet not received NA NA The stern notice has been issued to the contractor because his hired men did not follow instructions of PGVCL's supervisor. The contractor has been reprimended that if this is repeated ever then his contract shall be terminated. A show cause notice has been issued to the contractor by concerned EE about why he should not be blacklisted. FHOS Fatal Human Outsider
55 Morbi Rafaleshwar
Rajeshbhai Chhaganbhai Bariya
28.07.2014 NFHOS The victims were working on the JGY feeder, when the said feeder was powered on. Report yet not received NA NA The stern notice has been issued to the contractor because his hired men did not follow instructions of PGVCL's supervisor. The contractor has been reprimended that if this is repeated ever then his contract shall be terminated. A show cause notice has been issued to the contractor by concerned EE about why he should not be blacklisted. FA Fatal Animal
56 Morbi Rafaleshwar
Kapasibhai Sonabhai Bariya
28.07.2014 NFHOS The victims were working on the JGY feeder, when the said feeder was powered on. Report yet not received NA NA The stern notice has been issued to the contractor because his hired men did not follow instructions of PGVCL's supervisor. The contractor has been reprimended that if this is repeated ever then his contract shall be terminated. A show cause notice has been issued to the contractor by concerned EE about why he should not be blacklisted. NFHOS Non Fatal Human Outsider
57 Morbi KHAMPALIYA
Buffalo of
Vasubhai Khimabhai Rabari
30.07.2014 FA The Khampaliya village TC had leakage current flowing into earth. Since it was raining while the accident took place, the induction zone enhanced in & around TC structure. The buffalo while passing near this TC must have come into induction zone created by leakage current & thus electrocuted. Report yet not received NA NA LT AB cable has been replaced by 16mm cable; TC earthing reactivised.
58 Morbi UNCHI MANDAL
Buffalo of
Ajitsinh Gandubhai Mori
16.08.2014 FA The victim buffalo somehow tangled his horn with the guy wire of DP structure of Madhuvan AG feeder bearing Location# 14. The victim buffalo in its struggle to free its horns from the guy wire seems to have broken the guy wire near the ground & this broken loose guy wire then contacted the jumper of AB switch on the DP structure. Thus the buffalo electrocuted. Another buffalo standing by & touching the victim buffalo was also electrocuted.  Report yet not received NA NA The snapped Guy wire has been removed.
59 Morbi UNCHI MANDAL
Buffalo of
Ajitsinh Gandubhai Mori
16.08.2014 FA The victim buffalo somehow tangled his horn with the guy wire of DP structure of Madhuvan AG feeder bearing Location# 14. The victim buffalo in its struggle to free its horns from the guy wire seems to have broken the guy wire near the ground & this broken loose guy wire then contacted the jumper of AB switch on the DP structure. Thus the buffalo electrocuted. Another buffalo standing by & touching the victim buffalo was also electrocuted.  Report yet not received NA NA The snapped Guy wire has been removed.
60 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
61 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
62 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
63 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
64 Morbi PANCHASAR
Buffalo of
Thobhanbhai Butabhai Bharvad
10.09.2014 FA LT conductor having slipped/ detached from shackle insulator, touched “C” clamp & thereby leakage current was passing into LT pole’s GI earth wire. The victim buffalo coming in its contact & thereby electrocuted.  Report yet not received NA NA LT Line Maintenance carried out, which included removal of earth wire from LT pole as it is surrounded by water currently. Further TC maintenance too has been carried out.
65 Morbi TANKARA
Buffalo of
 Daudbhai Jumabhai Ghanchi
21.09.2014 FA One of the three victim buffaloes was scratching itself to guy wire of 3-phase 4 wire LT pole. Due to scratching intensity of the buffalo onto the guy wire, the tension was built over pole which resulted into snapping of one of 3 phases’ bare conductor of this LT line. The snapped conductor fell down on the victim buffaloes & thereby the buffaloes electrocuted.  Report yet not received NA NA The conductor has been replaced.
66 Morbi TANKARA
Buffaloes of
Rasul Mamad Chaudhari 
21.09.2014 FA One of the three victim buffaloes was scratching itself to guy wire of 3-phase 4 wire LT pole. Due to scratching intensity of the buffalo onto the guy wire, the tension was built over pole which resulted into snapping of one of 3 phases’ bare conductor of this LT line. The snapped conductor fell down on the victim buffaloes & thereby the buffaloes electrocuted.  Report yet not received NA NA The conductor has been replaced.
67 Morbi TANKARA
 Buffalo of
Hanif Rahim Sherashiya
21.09.2014 FA One of the three victim buffaloes was scratching itself to guy wire of 3-phase 4 wire LT pole. Due to scratching intensity of the buffalo onto the guy wire, the tension was built over pole which resulted into snapping of one of 3 phases’ bare conductor of this LT line. The snapped conductor fell down on the victim buffaloes & thereby the buffaloes electrocuted.  Report yet not received NA NA The conductor has been replaced.
68 Morbi Sapakda
Adarsh Vasudevbhai Makwana
28.09.2014 FHOS Few children were playing on tractor trolley parked under the feeder. While playing, the victim must have touched the live bare conductor of the feeder & thus electrocuted.  Report yet not received NA NA New PSC pole has been erected for 11KV line & the span has been restrung. Show cause notice issued to the SDO for lach of timely periodic maintenance.
69 Morbi RAVAPAR
Kamlesh Dharamshibhai Sonagra
28.09.2014 FHOS Illicit construction structure was being built by the owner of the premises. This construction was not only encroaching outside his privately owned plot but was also immediately under 11KV Bahumali Urban feeder. The structure being built seems to be of security office. The victims were hired for building this structure. However while working at height over the roof of this structure to build trolley lift, some metal portion used for building this trolley lift touched overhead live bare conductor of the said feeder. Thus, the accident occurred.  Report yet not received NA NA FIR# 181/12 has been lodged against Mavji Premji Kanjariya, the party responsible for constructing illegal structure below 11KV line.
70 Morbi RAVAPAR
Rakesh Gumansing Adivasi
28.09.2014 FHOS Illicit construction structure was being built by the owner of the premises. This construction was not only encroaching outside his privately owned plot but was also immediately under 11KV Bahumali Urban feeder. The structure being built seems to be of security office. The victims were hired for building this structure. However while working at height over the roof of this structure to build trolley lift, some metal portion used for building this trolley lift touched overhead live bare conductor of the said feeder. Thus, the accident occurred.  Report yet not received NA NA FIR# 181/12 has been lodged against Mavji Premji Kanjariya, the party responsible for constructing illegal structure below 11KV line.
71 Morbi RAVAPAR
Kumsing Meghaji Adivasi
28.09.2014 NFHOS Illicit construction structure was being built by the owner of the premises. This construction was not only encroaching outside his privately owned plot but was also immediately under 11KV Bahumali Urban feeder. The structure being built seems to be of security office. The victims were hired for building this structure. However while working at height over the roof of this structure to build trolley lift, some metal portion used for building this trolley lift touched overhead live bare conductor of the said feeder. Thus, the accident occurred.  Report yet not received NA NA FIR# 181/12 has been lodged against Mavji Premji Kanjariya, the party responsible for constructing illegal structure below 11KV line.
72 PBR PADODAR AND
DILIPBHAI KANABHAI SANJVA
01.04.14 FHOS Drop out fuse was blown of Transformer centre known as Jagmal Naran Sanjva valu TC.
Vill. Padodar. Sh. Dilipbhai Kanabhai Sanjva was trying to fix it with help of wooden bamboo. The bamboo was wet, when it came in live contact of 11KV supply, he got shocked. The above information is received by eye witness Sh. Punjabhai Jagmalbhai Sanjva. 
Report yet not received NA NA Public Awareness
73 PBR SHEPA AG
AREA AND VINUBHAI ARJANBHAI TANK
25.04.14 NFHD A  Non  Fatal  Human   Departmental   Accident  Occurred  to  Electrical  Assistant    
Sh. Vinubhai  Arjanbhai  Tank   Age 52  Years  On  Date  25.04.2014  at  10.40  A.M.   in 11  KV Satmarag  Ag  Feeder  Emanating  from 66  KV    bhudhecha   S/S  Due  to  by  mistake  victim  climbed on  The T/C D.P.  Of   Live Line  of  11  KV   Satmarag  Ag Feeder.  Line  Clear  was  Taken  of  11  KV  Chakivav  Ag  Feeder  Instead  of  11  KV  Satmarag  Ag Feeder.
Report yet not received NA NA Necessary instruction given to all line staff & K B Desai was transferred & Chargesheet issue vide MGRL/HR/SHOWCAUSE/KBD/281,DT-08.08.2014 and C V Chapadiya - DE(Tech)-
Keshod Div appointed as inquiry officer vide SEP/HR/3/Dept Inquiry/570,05.09.14.
74 PBR BARVANESS AND KISHORBHAI DASABHAI KODIYATER 10.05.14 FHOS
Accident is occurred due to 1 phase service wire hitted by truck owner( truck no.GJ 25 T 9998) and service wire entangled on matel cage made of MS Angle and G.I. Pipe at the top of the truck which is parked in the open land.insulation of 1 phase service wire broken and removed due to tension on both the ends of service wire. Thus due to open phase wire came in contact with metal cage of truck and truck body charged. victim came in contact with charged truck body and got shocked and electrocuted
Report yet not received NA NA Proper Maintanace Done
75 PBR KHODADA AND BULLOCK OF KANABHAI SUDABHAI GALCHAR 14.05.14 FA An animal bullock accident occurs at village- Khodada (Ness) and the owner of cattle is
Sh. Kanabhai Sudabhai Galchar due to fault of Lightning Arresters. The Lightning Arrester's top part fall down on land and lightning arrester's jumper touch the 11KV line channel so leakage current is there in the earth, at that time bullock passes nearer to the Transformer D.P. structure around the induction zone and bullock fall down on land and than after in few minutes bullock died.
Report yet not received NA NA Proper Maintanace Done
76 PBR NANDARKHI AND HANUFBHAI DAUDBHAI VARAM 01.06.14 FHOS  Accident occurs to shree. contractor yusuf  ismail jivan person
shree,hanifbhai  daudbhai varam resident,mangrol age-21 year approx work at nandarkhi village ag area for replacement of deteriorated psc pole for 11 kv farngta ag feeder .the line clear was taken of  11 kv   farngta ag feeder and 11 kv shill feeder eminating both feeder 66 kv shil substation . the contractor gang(team) work compled of dismantling and erection of new pole and fixed  v-crossm with pin  the victim  has complted  binding  of two numers of phases and  thred phase pin binding carrying out.he come across with electric shock at time he was failedand sticked with v-crossm and was lowerdown by coworkers with help of rope.
Report yet not received NA NA Proper Maintanace Done & MEMO issue to JE-MGRL/RSDN/HR/CONFI/120,DT-07.06.2014
FIR LODGED AT SHIL POLICE STATION AGAINST FARMER DAYABHAI LAKHABHAI BHARDA VIDE FIR NO-I/17/2014,DT-13/06/2014
H B Mori - DE - Show Cause Notice Issue vide SEP/HR-III/DA/HBM/221 Dt-07-07-2014 & Draft C
77 PBR AKHODAR AND JAYSHUKHBHAI MANJIBHAI KATHAD 04.06.14 NFHOS The victim was removing support of newly constructed slab of house and "head" of victim touched to the 11KV live wire of Khirasara JGY Feeder. Report yet not received NA NA Proper Maintanance Done & Public Awareness
78 PBR AGATRAI AND KANTILAL BHODABHAI BHARDA 11.06.14 NFHD Victim had completed maintenance work on HT Pole, while de climbing (getting down), his leg slipped and fall down on ground and got injured.  Report yet not received NA NA Necessary instruction given to all line staff & VICTIM WAS UNDER MEDICAL TREATMENT
& TILL ON LEAVE AFTER THE JOIN OF DUTY DEPARTMENTAL ACTION WILL BE INITIATED INFORMED BY CONCERNED DE VIDE LETTER KSD-2/ACCD/TECH/1711,DT-09.09.14
79 PBR PANKHAVA AND BULLOCK OF KHIMABHAI VIRAMBHAI RAVALIYA 11.06.14 FA Conductor of 11 kv Dudhada Ag feeder was snaped from top insulator  and was
lying on top fitting angle ,Through earthing leakage current flow in route of tree which was nearby pole,a buffallo was tied with stem of tree with iron chain,Thus fatal accident occured.
Report yet not received NA NA Proper Maintanace Done
80 PBR SHEPA AND FARUKHBHAI HUSENBHAI KALVAT 14.06.14 FHOS  It might not be due to snaping of conductor  but may be due to wet tools tackle utilize for repairing  ceiling of  room came  in contact with 11 kv langodra  ag feeder conductor.&   electrocuted. Report yet not received NA NA Public Awareness
81 PBR SHEPA AND DAUDBHAI HUSENBHAI KALVAT 14.06.14 NFHOS  It might not be due to snaping of conductor  but may be due to wet tools tackle utilize for repairing  ceiling of  room came  in contact with 11 kv langodra  ag feeder conductor.&   electrocuted. Report yet not received NA NA Proper Maintanance Done 
82 PBR BHOGSAR AND BUFFALO SHE OF GOGANBHAI MANDABHAI MORI 16.06.14 FA DUE TO HEAVY RAIN & WIND LEAKAGE CURRENT PASSES THROUGH EARTH WIRE
OF LT LINE POLE & DUE TO WATER LOGGING NEAR THAT POLE & SHE-BUFFALO OF SH GOGAN MANDA MORI COMES IN CONTACT WITH THAT LEAKAGE CURRENT AND GOT ELECTROCULATED.
Report yet not received NA NA Proper Maintanace Done
83 PBR KHORASA AND RAGHAVBHAI PAVANBHAI KODIYATAR 03.07.14 FHOS A   fatal  accident occurred to a boy in survoyday hostel at khorasa village. By preliminary investigation,
it is found that a boy - shri rahav pavan kodiyatar has mischievously or by intestinally touch 11kv conductor through wooden road passing nearby tares of said hostel and came in contact with live 11kv gayatri jgy feeder & got electrocuted.
Report yet not received NA NA Proper Maintanace Done & Publice awareness
84 PBR KHAMIDHANA AND BUFFALO SHE OF KANTILAL THAKARSHIBHAI GAJERA 18.07.14 FA The buffalo came in live contact of leakage power in earthing of transformer centre known
as water works valu TC. vill. Khamidana and got electric shock.
Report yet not received NA NA Proper Maintanace Done
85 PBR RANAVAV AND BUFFALO-SHE OF KHIMABHAI POLABHAI GARCHAR 21.07.14 FA BUFFALO-SHE WAS PASSING NEAR TRANSFORMER
CENTRE AND LIGHT RAIN WAS COIMING AT THAT TIME AND METAL ROD WAS FULL OF LIGHT WATER. SO IT MAY BE EARTH LEACKAGE FROM TRANSFORMER CENTRE AND BUFFALO-SHE MIGHT BE COME IN ZONE AND GOT ELECTROCULATED DUE TO WET SPACE.
Report yet not received NA NA Proper Maintanace Done
86 PBR KADAYA AND GORDHANBHAI BHIKHABHAI RATHOD 25.07.14 NFHOS When a labour of contractor working on Dhanej Ag Fdr during line erection work
11 kv shackle pole was broken from top and below  guy clamp thats cause labour of contractor falled down on earth the and injured his legs, hands and body parts.
Report yet not received NA NA NOTICE ISSUED TO CONTRACOTR & NECESSARY INSTRUCTION GIVEN TO ALL LINE STAFF & CONTRACTORS.
87 PBR KESHOD AND BUFFALO SHE OF VANPARIYA JENTIBHAI NANJIBHAI 05.08.14 FA At the  visit of accident site due to heavy rain and wind an ab cable phase wire touches
to tail end  moistured pole,leackage current passes through pole to wet soil at that time buffello passes near by area of electrocuted pole and got shocked.
Report yet not received NA NA Proper Maintanace Done
88 PBR LAMBHORA AND BUFFALO SHE OF JADAV ARSHIBHAI VALABHAI 10.08.14 FA Due to service wire one phase  open &open phase touch guy clamp which is 
supported   to pole  so phase curent  pass through guy calmp to earth  there is lot of water arond they pole due to rain so cureent  pass thorogh water and then   buffalo  come nearr and  contact with the phase lekage  current  an around the induction zone and  buffalo fall down to land and then after few minutes buffalo  died age 7 year as per  partiis.      
Report yet not received NA NA Proper Maintanace Done
89 PBR KATRASA AND VATSALKUMAR SAILESHBHAI DODIYA 11.08.14 NFHOS  Accident occured due to coconut tree leave(pan) touched and burnt with conductor of 11 kv Ambalgadh jgy line beetween location no.97 and 98 due to thats cause 11 kv conductor broken and victim came in contact and his grand father sh.meramanbhai tries to save his grandson and both got electric shock . Report yet not received NA NA Proper Maintanance Done & Public Awareness
90 PBR KATRASA AND BABUBHAI MERAMANBHAI DODIYA 11.08.14 NFHOS  Accident occured due to coconut tree leave(pan) touched and burnt with conductor of 11 kv Ambalgadh jgy line beetween location no.97 and 98 due to thats cause 11 kv conductor broken and victim came in contact and his grand father sh.meramanbhai tries to save his grandson and both got electric shock . Report yet not received NA NA Proper Maintanance Done & Public Awareness
91 PBR KUTIYANA AND BUFFALO SHE OF BADHA BHAVAN RAIGA 15.08.14 FA Due to heavy wind leakage current passes through  support wire inside of lt line pole &
due to water logging near that pole & she buffalo of shree Badha Bavan Raiga comes in contact with that leakage current and got electrocuted. 
Report yet not received NA NA Proper Maintanace Done
92 PBR BARULA AND BUFFALO SHE OF KARSHANBHAI PARBATBHAI JOHRA 30.08.14 FA A   fatal  accident occurred to buffalo passing near by LT line and LT conductor
broken from joint and came in contact with live LT Wire & buffalo got electrocuted.
Report yet not received NA NA Proper Maintanace Done
93 PBR CHORWAD AND UMESHBHAI MULJIBHAI SEVRA 02.09.14 FHOS A   fatal  accident occurred to a boy in jarari vistar nr. Bandar road at chorwad village.
By preliminary investigation, it is found that a boy - shri umesh mulji sevra has mischievously or by intestinally touch 11kv conductor through wooden road / iron raod while getting thread of kite passing nearby tares of Shri dinesh ramji pandit and came in contact with live 11kv chorwad jgy feeder & got electrocuted.
Report yet not received NA NA Proper Maintanace Done & Publice awareness
94 PBR AGATRAI AND BUFFALO SHE OF HIRABHAI ALABHAI KHAMBHALA 03.09.14 FA A fatal electrical accident occurred to a buffalo of Sh. Hirabhai Alabhai Khambhala
due to breakage of LT schakle insulator and leakage current passes through GI wire (earthing wire) and buffalo came in contact and got electrical shock and died.
Report yet not received NA NA Proper Maintanace Done
95 PBR VADLA AND BULLOCK OF DAYABHAI RAJABHAI KODIYATAR 07.09.14 FA The person was going with his bullock at that time the live LT conductor was broken and laying down on earth and this bullock come in contact with this live wire and get electric shock and dies at site. Report yet not received NA NA Proper Maintanace Done
96 JAMNAGAR Hansthal,Shyam Arjan Chavada 25-4-14 NFHOS while boy was catching almond from tree with an iron rod,somehow iron rod touched to line jumper of transformer center and got electric shock PENDING N.A NO AWARENESS IN PUBLIC FOR KEEP SAFE DISTANCE FROM LINE
97 JAMNAGAR Govana,Lalsang Harisang Chauhan 15-5-14 FHOS Contractor asked for Line Clear Permit of 11 kv Govana Ag feeder for providing Jumper of newly erected SPA sanctioned work but actually the existing feeder was 11 kv Valor ag feeder After taking LCP of 11 KV Govana Ag feeder instead of 11 kv Valor Ag Feed CEI REPORT AWAITED N.A N.A Strict instructions passed on to all concerns to be very vigilant while taking LCP 
98 JAMNAGAR Nandana,Somat Natha Gojiya 30-5-14 FHOS Victim has gone to seen the new construction room at his brothers premises on the roof of the newly constructed room on which 11 kv bhalara-JGY line passes above as well as across the roof of the newly consructed room vertical distance between roof of roo CEI REPORT AWAITED N.A N.A Frequent public meeting for awarness about the hazards of construction beneath the lines are being arranged at filed level.
99 JAMNAGAR Meghpar Jashapar,Pramod Parshotambhai Sonagara 4-6-14  NFHD Pin Insulator faulat occurred during night in 11 kv Balambha feeder but due to some how breaker of that feeder at 66 kv keshiya s/s was not triped hence PIN was fired & brusted so conductor was fall down on V-cross arm. This PSC pole was burnt due to cont AWAITED AWAITED NA GETCO authority is informed to solve above technical problem by a letter to D.E. 132 KV S/S Dhrol
100 JAMNAGAR Jamnagar,A Cow of Razakbhai Ismailbhai Khafi 16-6-14  FA Live phase of 1Ph sevrive wire was teared off and got damged and due to rain and heavy wind.There for it came in contact with GI wire of service line it self. This GI wire along with service line was touched with nearby existing telephone tabular pole due N.A N.A N.A Nacessary maintenance is carried out new psc pole erract to reduce lenth of service wire and replace faulty service wire.
101 JAMNAGAR chokhanda,Arvindbhai Naranbhai Dhokiya 18-6-14 FHOS The victim was working unauthorisely on last L.T line pole of Lakha Allarakha ag connection of 63 KVA Hamir Markhi AG group at village chokhnada for restringing of conductor by isolating 11 KV DO fuse from TC The Jumper of AG feeder was under shutdown for CEI REPORT AWAITED N.A N.A People are being educated to avoid unauthorized operation of lines by arranging safety meetings at various villages.
102 JAMNAGAR Dhrol,Prakash R Consumara 23-6-14  NFHD During maintance of TC at village area our LM fall down form TC due to Giddines and his left leg got injured after taking primary treatment at dhrol Government hospital he  is transffered to Jamnagar AWAITED AWAITED NA No any remedial action is required to be taken.
103 JAMNAGAR hanjarapar,Mulji Devshi Kanzaria 24-6-14 FHOS Fatal Accident occurred to an outsider man at LT line of Tc at mathuranagar village on 11 kv dhandhusar JGY feeder of vadatra s.dn due to snapping of conductor  PENDING N.A NO DETAIL JINVESTIGATION UNDER PROCESS.
104 JAMNAGAR Gadhaka,Jiviben Devarajbhai Parmar 6-7-14 NFHOS Woman Was cleaning ground around LT line ,accidently conductor of LT line brokedown and touched her body and got electric shock PENDING N.A NO L.T.AB CABLE WORK COMPLETED IN WHOLE VILLAGE NETWORK.
105 JAMNAGAR Kota ag,A Camel of Shree Jesha sura Gangar 8-7-14  FA A Camel came in contact with live electircal wire of 11 kv dharampur ag dom to pile of soil and got electrocuted PENDING N.A NO NECESSRY MAINT. WORK CARRIED OUT BY S/DN.
106 JAMNAGAR Jamnagar,A cow of Jadeja Yashrajshinh Vanraj sinh(Unknown Brown Cow) 13-7-14  FA Due to hevay wind pressure and rain service wire insulation in the LT pole became weak and came in contact with its GI support wire.in turn the pole angle became shorted and the leakage current passed through the earthing wire of that pole Meanwhile a cow N.A N.A N.A Nacessary maintenance is carried out providing bus bar at pole. 
107 JAMNAGAR Jamnagar,A cow of Bhojabhai Nagshibhai Gadhave 13-7-14  FA Due to hevay wind pressure and rain service wire insulation in the LT pole became weak and came in contact with its GI support wire.in turn the pole angle became shorted and the leakage current passed through the earthing wire of that pole Meanwhile a cow N.A N.A N.A Nacessary maintenance is carried out providing bus bar at pole. 
108 JAMNAGAR Laloi ,Manjuben Vithalbhai Bhalara  24-7-14 NFHOS Victim growing bee in own farm.at that time fault occurred in 11 kv pin of laloi AG feeder on pole no 126 one phase conductor of line was broken at pin point conductor of line was nbot fall down on land but hangiing at tatpping  and loose down the span at CEI REPORT AWAITED N.A N.A All concerns are instructed to carry out periodical qualitative maintenance activity so as to avoid such incidents in future.
109 JAMNAGAR Jamnagar,Manishaben Hasmukhbhai Bhatt 26-7-14 NFHOS The victim who is belived to be mentally retarted jumped from the second floor of her house for any reason and while falling the victim came in contact with the 3-phase 5 wire LT Line passing near by to the house and then felldown on the ground and was se N.A N.A N.A Not Reported.
110 JAMNAGAR Khambhalia,A bullock(5Yrs) of shree Anupsinh Nagubha Sodha  and one chile bullock(2 yrs)  of shree Natubha Jitubha Jadeja 26-7-14  FA as par statement of eye witness & owners of animals fatal accident occurred due to street light cable phase got shocked &leakage current flow in wet psc pole at that time both animals came in contact & got electrocuted. PENDING N.A NO NECESSRY MAINT. WORK CARRIED OUT BY S/DN.
111 JAMNAGAR Nagarsim,Buffalow of Jusab Juma Safiya 5-8-14  FA Due to snapping of LT line conductor and came in contact with neck and right leg of buffalow and fatal accident occurred NO NO NO Next day on (N.A6/N.A8/2N.A14) Rama Sina’s T/C group all LT line &  connection maintenance work carried out and detoriated conductor replaced.
112 JAMNAGAR Badanpar,A she Buffalo of pababhai Sondabhai Zapada 5-8-14  FA Leakage current passing through GI wire which comes from LV side Neutral of Transformer animals are more sensitive with minor leakage current and as a buffalo came in contact with GI wire and it met with an electrical accident AWAITED AWAITED NA Periodically maintenance work carried out by SDO at regular interval.
113 JAMNAGAR Jasapar,A Bufflaow Hemashibhai Polabhai Malani 7-8-14  FA Victim got electroculated at about 9.00 A.M on 07.08.14 while grassing nearby substation she buffalo has inserted right horne in the distribution box of existing kanabhai Vadi Group AWAITED AWAITED NA Proper re-earthing with PVC pipe was done of this TC and proper maintenance of that dist. Box is done by the deputy engineer ofr non occurance of such type accident.
114 JAMNAGAR Jamnagar,A male Got of Sarifaben W/O Adam Muniya 8-8-14  FA Leakage current occurred by return power occurance from near by existing LT pole of the transformer centre a fatal accidnet occurred to A mele Goat near by TC due to earth leakage current ,exact cause of leakage current is not found  N.A N.A N.A Continuous instalation & cheking work done. And Nacessary Lt Line maintenance is carried out.
115 JAMNAGAR Bhinda,Sankar S Pargi 9-8-14  NFHD As per fault center complaint for break down of 11 KV jumper on TC above DO fuse while victim climbed on TC todo jumper fault after taking LCP from 66 kV Bhadthar SS but by mistake Mr. B.L, Gosai (LM) taken LC of Bhinda AG feeder and other crossing feeder PENDING N.A NO CHARGE SHEET ISSUESD TO CONCER LINEMAN AND DEPTT INQUIRY UNDER PROCESS. ALSO STRICT INSTRUCTION GIVEN FOR USE OF SAFETY GADGETS .
116 JAMNAGAR Jamnagar,A cow Unclaimed 10-8-14  FA As per the the telephonic  messg the site was visited were water logging nearby TC ,primary reason is not found However due to any other unknown source leakage current is suspected at water logging near TC due to water logiing earth leakage current passin NO NO NO On very next day i.e  on 11/N.A8/2N.A14 that transformer shifted at safe place and new earthling connection provided and also all LT bare conductor replaced by AB cable.
117 JAMNAGAR Jamnagar,A cow of Tinabhai Khimabhai Aambaliya 11-8-14  FA As per the the telephonic  messg the site was visited were water logging nearby TC ,primary reason is not found However due to any other unknown source leakage current is suspected at water logging near TC due to water logiing earth leakage current passin NO NO NO On very same day i.e on Dt (11/N.A8/2N.A14) that transformer shifted at safe place and new earthling connection provided and also all LT bare conductor replaced by AB cable
118 JAMNAGAR Jamnagar,A male got of Ismail Kadar Manek 15-8-14  FA Due to arrangement of meter by pass at consumer premises named babulal Madhavji bedi gam con no 32202016325 main service wire insulation was broken by the consumer near the meter box and extra wire was connected to the main service for to By pass the mete N.A N.A N.A Continuous instalation & cheking work done
119 JAMNAGAR Gorakhdi,A Buffalo of Trikam Gangdas Vasoya 17-8-14  FA The buffalo came in contact of the broken LT Conductor (Main Side)and leakage current flew in bufllow body and got electric shock and died CEI REPORT AWAITED N.A N.A All field offices are instructed to replace old deteriorated conductor and to carry out maintenance of lines by resagging loose span, tightening of loose guys, etc.
120 JAMNAGAR Dared,A Buffalow of Hahabhai Jungabhai Gujariya 24-8-14  FA Due to the PIN fault occurred on location no BSS/CHELA/58/R025 hence conductor was snapped and touched to the lower part of Buffalow and fatal accident occurred NO NO NO Same day on (24/N.A8/2N.A14) maintenance carried out and replace the faulty pin departmentaly
121 JAMNAGAR Jamnagar,A buffalow of Lilabhai Malde abha Keshavala 26-8-14  FA Due to unauthorised live electic  fencing of iron wire to  cover ag land of shree vijay Rambhai Keshavala for keeping animal away and protect the agriculture land. with same fencing the buffalo while passing near the fencing its tail came in contact with  NO NO NO FIR is launched in local police station against Shree Vijaybhai Rambhai Keshavala vide letter no. RSD/TECH/2698/3N.A.8.14 and also his AG connection Consumer No. 32557/N.AN.A461/8 had disconnected.
122 JAMNAGAR Amara,Jayesh Lalitbhai  Parekh  27-8-14  NFHD As per the telephonic information given by line staff on Dt. 27.08.2014 to undersigned   has visited accident site on next day i.e on 28.8.2014 and he has found that victim Shri J L Parekh was working on Ag Transformer center and  suddenly victim came in  NO NO NO Necessary maintenance work had been taken up and against this accident all line staff has got aware has to not repeat such type of incidence in future.

123 JAMNAGAR Khandhera,Two Buffalo ofNathabhai Shivabhai Vaghela 1-9-14 NFHOS The accident occurred at the time of snapping of LT conductor from LT Pole of Jethabhai L Hirpara in Laxmipur AG feeder while buffalo came in contact with the live wire and met with accident .this LT Conductor was snap due to rain. The above matter is dis AWAITED AWAITED NA Public awaareness campaign is carried out during fairs and in news papers for accident prevention
124 JAMNAGAR Rangpar,2 Buffalo of Kara Paba Gagiya 2-9-14  FA 2 buffalo got electric shock due to hevay wind pressure amd rain snapping of LT line conductor which fall on two buffalo both came in contact with live conductor and got a electric shock and died NO NO NO The maintenance of the location was carried out On Dt. N.A1.1N.A.2N.A14 properly after the accident done through Department.
125 JAMNAGAR Jamnagar,Kishor Ramji  Kanzaria 5-9-14  NFHD On the Staggering Day Various kind of maintanance works were arranged along with noted carried out temporary works during the week long period at GIDC-III and GIDC-II Dared So shree C L Parmar and K R Kanjaria E.A had to attend the maintanace works of 63  NO NO NO           Notice will be issue to the kishor Kanzariya for very sensitive mistake.
126 JAMNAGAR madhapar,Ranjanben Kumarbhai Vikani 9-9-14 NFHOS Victim was taking  soaked clothes on terrace one corner of this teraace is built under 11 KV Bodaka JGY feeder and the victim s right hand burned and finger got demaged  AWAITED AWAITED NA Public awaareness campaign is carried out during fairs and in news papers for accident prevention
127 JAMNAGAR Jamnagar,Piyush Sureshbhai Rathod 12-9-14 FHOS Victim was moving on terrace may extended his body parts towards 11 KV line Passing near the parafit of thos terrace, This was the extended body part of the victim may come in contect of this live 11 kv line which leads the path of current through victims N.A N.A N.A Notice sent to house owner smt. Salmaben samabhai to remove un authorised extension of terrace towards the 11kv overhead line & keep & maint. The horizontal clearnace from this projected over head 11kv line.
128 BHUJ Siracha, 1 Buffalo, Bhavubha Bhurubha CHAUHAN 3.7.14 FA CONDUCTOR OF 11 KV SHIRACHA AG FDR SNAP DOWN TO EARTH. WHILE PASSING THROUGH EMPTY RIVER BODY OF 3NOS BUFFALO COME IN CONTACT WITH CONDUCTOR & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
129 BHUJ Two  Goat of no owner 22.4.14 FA While investigatation it is found in the preliminary stage, the accident occurred near DHROBANA village. The Two GOAT was moving underneath the 11 KV DHARAMSHALA JGY feeder in DHROBANA VILLAGE Due to pin fault, the top (groove) of the pin broken and the conductor snapped and while falling on ground the TWO GOAT underneath came in contact with live conductor resulted into fatal accident. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
130 BHUJ Two  Goat of no owner 22.4.14 FA While investigatation it is found in the preliminary stage, the accident occurred near DHROBANA village. The Two GOAT was moving underneath the 11 KV DHARAMSHALA JGY feeder in DHROBANA VILLAGE Due to pin fault, the top (groove) of the pin broken and the conductor snapped and while falling on ground the TWO GOAT underneath came in contact with live conductor resulted into fatal accident. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
131 BHUJ Cow of  Devshi Manji Pindoriya 24.4.14 FA A cow passing through the sim area behind sukhpar(roha) village might have came in direct contact of (load side) snapped conductor of 11kv Khirasara ag and got electrocuted.There was no tripping observed during the time period at ss end.                                                                                                                      Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
132 BHUJ 1 BUFFALO  OWNER NAME SHRI RANABHAI REVABHAI BHARAVAD  23.5.14 FA as per telephonic compalin launched by shree butabhai merabhai bharavad to the line office PGVCL adipur s/dn regarding snapping of conductor and line wire fall down on earth near to the to container yard, ioc road side machunagar area village khari rohar and at the same time the one . Buffalo passsing near the snapped conductor and came to this she got electrocatal and resulting in to fatul accident.     note No any tripping occured on 11 kv  11 KV ioc feeder after snapped down the conductor ands came in contace with the earth till acciednert occured  Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
133 BHUJ COW FEMALE AND BUFFALLOW 11.5.14 FA DUE TO HEAVY WIND AND RAIN LT LINE CONDUCTOR IS BROCKEN AT  LATE NIGHT &NO TRIPPING TRIPPING IS OBSERVED AT NIGHT .AT EARLY MORNING ,COW & BUFFALLOW  PASSED THROUH THIS  LOCATATION & COME IN CONTACT WITH BROCKEN CONDUCTOR AND GET ELECROCUTED AND DIED Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
134 BHUJ COW FEMALE AND BUFFALLOW 11.5.14 FA DUE TO HEAVY WIND AND RAIN LT LINE CONDUCTOR IS BROCKEN AT  LATE NIGHT &NO TRIPPING TRIPPING IS OBSERVED AT NIGHT .AT EARLY MORNING ,COW & BUFFALLOW  PASSED THROUH THIS  LOCATATION & COME IN CONTACT WITH BROCKEN CONDUCTOR AND GET ELECROCUTED AND DIED Report yet not received NA NA  
135 BHUJ Siracha, 1 Buffalo, Bhavubha Bhurubha CHAUHAN 3.7.14 FA CONDUCTOR OF 11 KV SHIRACHA AG FDR SNAP DOWN TO EARTH. WHILE PASSING THROUGH EMPTY RIVER BODY OF 3NOS BUFFALO COME IN CONTACT WITH CONDUCTOR & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
136 BHUJ Siracha, 1 Buffalo, Bhavubha Bhurubha CHAUHAN 3.7.14 FA CONDUCTOR OF 11 KV SHIRACHA AG FDR SNAP DOWN TO EARTH. WHILE PASSING THROUGH EMPTY RIVER BODY OF 3NOS BUFFALO COME IN CONTACT WITH CONDUCTOR & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
137 BHUJ Jangi,  Navnit S. Baranda 13.7.14 FHD ON DATED: 13.07.2014 THE 11KV JANGI FDR WAS IN FAULT AND VICTIM HAD GONE WITH LINE STAFF FOR ATTENDING WORK.AFTER COMPLETION OF FDER ATTENDING WORK VICTIM WENT TO JANGI SALT WORKS FOR ATTENDING TELEPHONIC COMPLAINT OF NOT GETTING THREE PHASE POWER OF SALT WORKS. AT TC OF SHRI KANJI VASAN MATA SALT WORK ONE JUMPER WAS FOUND FUSED SO LIMBACHIYA HAD GIVEN INSTUCTION TO A D VANKAR TO OPEN SWITCH. AFTER ISOLATION OF 11 KV SWITCH SHRI VANKAR HAD INFORMED TO SHRI LIMBHACHIYA THERE IS ONE JUMPER DIRECT OF SWITCH BUT CONCERN NOT TAKE IT SERIOUS . VICTIM CLIMED ON TC HAVING LIVE ONECONDUCTOR OF 11 KV JANGI FDR. AND SUDDENLY HE CAME IN CONECT WITH LIVE CONDUCTOR AND GOT SHOCKED AND FELL DOWN AND WAS DECLARED EAD. THUS FATAL HUMAN CCIDENT OCCURED. Report yet not received NA NA All are instructed to utilize safety gadgets.
138 BHUJ  Bhuj,Cow , MAHESHBHAI MARAJ 17.7.14 FA COW WAS PASSING THROUGH THE HOUSE AND DUE TO WIRING PROBLEM IN THE CONSUMER PREMISES THE POWER COMES TO THE WALL OUT SIDE OF THE HOUSE THE COW CAME IN CONTACT TO THE WALL AND GOT ELECTROCUTED AND DIED. Report yet not received NA NA in consumer premises, after verification and test report power supply given. 
139 BHUJ Kanpar, 1 Goat , GOVIND LADHA CHARANIYA 18.7.14 FA 3 NOS OF GOATS PASSING THORUGH THE KANPAR SIM AREA NEAR KANPAR VILLAGE CAME IN CONTACT OF SNAPPING OF CONDUCOTOR OF 11KV ANANDSAR AG DUE TO PIN FAULT AND GOT ELECTROCUTED . Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
140 BHUJ Kanpar, 1 Goat , GOVIND LADHA CHARANIYA 18.7.14 FA 3 NOS OF GOATS PASSING THORUGH THE KANPAR SIM AREA NEAR KANPAR VILLAGE CAME IN CONTACT OF SNAPPING OF CONDUCOTOR OF 11KV ANANDSAR AG DUE TO PIN FAULT AND GOT ELECTROCUTED . Report yet not received NA NA  
141 BHUJ Kanpar, 1 Goat , GOVIND LADHA CHARANIYA 18.7.14 FA 3 NOS OF GOATS PASSING THORUGH THE KANPAR SIM AREA NEAR KANPAR VILLAGE CAME IN CONTACT OF SNAPPING OF CONDUCOTOR OF 11KV ANANDSAR AG DUE TO PIN FAULT AND GOT ELECTROCUTED . Report yet not received NA NA  
142 BHUJ Samagoga, Parmaben A. Seda 20.7.14 FHOS LT LINE CONDUCTOR OF RAJDE SUMAR (G6 ) TC GRUP SNAP DOWN TO FENCING OF FARM.VICTIM CAME IN CONTACT WITH FENCING LINE & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA All conductor & Fabrication of the LT line of the X’mer centre are  replaced .
143 BHUJ Gandhidham,1 ox 18.7.14 FA 2 ox and 1 ox child were standing under the LT line, LT-shakle at LT pole was broken, due tio which LT  conductors from its both side snapped down while snapping conductor came into contact with three ox and fatal animal acciden occurred . Report yet not received NA NA Arial bunch cable provided at accident palace.
144 BHUJ Gandhidham,1 ox 18.7.14 FA 2 ox and 1 ox child were standing under the LT line, LT-shakle at LT pole was broken, due tio which LT  conductors from its both side snapped down while snapping conductor came into contact with three ox and fatal animal acciden occurred . Report yet not received NA NA Arial bunch cable provided at accident palace.
145 BHUJ Gandhidham,1 Calf 18.7.14 FA 2 ox and 1 ox child were standing under the LT line, LT-shakle at LT pole was broken, due tio which LT  conductors from its both side snapped down while snapping conductor came into contact with three ox and fatal animal acciden occurred . Report yet not received NA NA Arial bunch cable provided at accident palace.
146 BHUJ Moti Undoth, Goat , ISMAIL IBRAHIM MANGALA 21.7.14 FA WHENEVER 11 KV POWER PASSING IN PADAMPUR AG FDR ON THAT TIME PIN WAS PUNCHERED AND CONDUCTOER WAS SNAPPED FROM UPPER SIDE OF PIN.ON THA TIME GOAT WAS PASSED FROM THERE AND GOAT TOUCHED WITH LIVE  SNAPPED CONDUCTOR.SO,ACCIDENT WAS OCCURRED. Report yet not received NA NA Maintenance done of this pole with faulty pin replacement and conductor restringing.
147 BHUJ Adersar,Sanava, Pratapsinh A. Baraiya 24.7.14 FHOS AFTER REPLACEMENT OF FAIL TRANSFORMER , THE VICTIM HAD CLIMD ON THE TC STRUCTURE FOR RELEASING THE CHAIN CAMPO SEALING , DURING THE WORK CCIDENTLY HE HAD FELT DOWN ON THE GROUND FROM THE TOP OF THE TC STRUCTURE. AFTER FELLING HE HAS GOT SERIOUS ON HIS HEAD AND MOUTH AND DIED AT SITE.THERE WAS NO ANY EVIDENCE  FOUND  OF CURRENT FLOW AND GOT ELECTOCUTED.  Report yet not received NA NA All vendors have instructed to all workors must be use safety gadgets.
148 BHUJ Anjar,  1 cow 24.7.14 FA DUE TO PUNCTURE IN LT SHACKLE INSULATOR, LEAKAGE CURRENT CAME INTO GURDER POLE AND COW AND OX NEAR TO THE GURDER POLE GETS ELECTROLUTED AND DIED. Report yet not received NA NA By replacement of shackle insulator.   
149 BHUJ Anjar, 1 ox,  24.7.14 FA DUE TO PUNCTURE IN LT SHACKLE INSULATOR, LEAKAGE CURRENT CAME INTO GURDER POLE AND COW AND OX NEAR TO THE GURDER POLE GETS ELECTROLUTED AND DIED. Report yet not received NA NA By replacement of shackle insulator.   
150 BHUJ Vayor, 1 Buffalo , DILUBHA JETHUBHA JADEJA 25.7.14 FA Durinng passing on road side buffalo touched the guy wire which was live as AB cable insulation was broken due to frictoin and died. Report yet not received NA NA detoriated ABC cable replaced and maintanance work carried out.
151 BHUJ Dhrobana,  1 cow 29.7.14 FA   Report yet not received NA NA After the accident took place on Dt 29/7/14 the faulty 11Kv pin insulator was replaced and snap conductor also replaced on same day and power supply was restored. Then on 30/7/2014 the maintenance of 11kv Dharamsala JGY feeder was arranged and restring of all the loose spans was done & at three location pole under line was also erected 7 no. of disc insulators were also replace while maintenance
152 BHUJ Dhrobana, 1 cow 29.7.14 FA   Report yet not received NA NA After the accident took place on Dt 29/7/14 the faulty 11Kv pin insulator was replaced and snap conductor also replaced on same day and power supply was restored. Then on 30/7/2014 the maintenance of 11kv Dharamsala JGY feeder was arranged and restring of all the loose spans was done & at three location pole under line was also erected 7 no. of disc insulators were also replace while maintenance
153 BHUJ Sayra, 1 Cow, MAHESHWARI DADU PACHAN 31.7.14 FA AT village sayara, Due to rain the surface ground is wet & water is filled near the PSC pole. A LT line conductor binding was snapped
due to heavy wind and rain and touch with LT cross arm. The leakage current flow through LT cross arm to GI wire of pole earthing and create potential near PSC pole. At that time cow passing near pole came in contact with GI wire and got electric shock and died.
Report yet not received NA NA maintanace cariied out to this place.
154 BHUJ Samagoga, Omkarsing Mansing 5.8.14 FHOS TRAILER LOADED WITH PIPES IS PARK UNDER 11 KV KAPAYA JGY LINE.VICTIM THROW THE CHAIN FROM ONE SIDE TO ANOTHER SIDE OF TRAILER TO BIND THE PIPES.CHAIN TOUCH THE LIVE CONDUCTOR WHICH PASSES ABOVE THE TRAILER .HENCE  CONDUCTOR ONE PHASE BROKEN & FALL ON VICTIM.SO VICTIM FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA Awarness to people for not Park the vehicle under 11 KV or LT network & don’t do such type of work. 
155 BHUJ Mandvi, Anil Yadav 5.8.14 NFHOS WHENEVER CONSTRUCTION WORK WAS CARRIED OUT BY VICTIM UNDER 11 KV CITY FEEDER.DURING CONSTRUCTION WORK VICTIM WAS SITTING ON WOODEN SUPPORT.ON THAT TIME HIS LEFT HAND TOUCHED 11 LINE CONDUCTOR R-PHASE.SO NON FATAL ACCIDENT OCCURRED. Report yet not received NA NA Issue notice for stop construction work.
156 BHUJ hareshbhai khimabhai koli 9.6.14 NFHOS on the 9.06.14 during morning approcimetely 7:30 hrs victim shri hareshbhai khimabhai koli aged 12 year come in contect witrh lie wire of 11 kv GIDC feeder. due to technical fault the wire hed brocken from the shakle pole near the pin and wire connected to the jumper hence conductor sug has increaed and conductor was about 7 ft from the ground level. The victim went there along with his parterner shri dilidp valjibhai rathod for collecting iron srcrap from the brokenpole lying benecth the line. the victim unawre that he will get shock he tried to cutch the wire with his right hand and got electric shock ( as per the statement of the victim) on investigation it is faund that the line clearence from the ground noremal wire broken and hanging with the jumper the clearenc with the grond was appere 7 ft ( as per the statement of the line staff who attend the line was attend looking to the burnes in the hand of the victim he might have technical the live wire either with iron rod or jumper and tried to pull the wire and leakege current hence had passed from hand to the ground  CONNECTED TO THE SUMPLE, HENCE THE CONDUCTOR SUG HAS INCREASED AND CONDUCTOR WAS ABOUT 7 FT FROM THE  Report yet not received NA NA maintanace cariied out to this place.AND diffective parts was removed to avoid acccident in future.
157 BHUJ M.M.Khombhal 19.4.14 NFHD Shri M.M.Khombhal climb up the LT pole for attending the service line complain. During this  by mistake  his hand came in contact with live part of sercive wire and got electric  shock .  He  fall down on land & got minor injury. Report yet not received NA NA Show cause notice issed to avoid utilize of safety gadgets
158 BHUJ Sinugra, Hasmukh J. Solanki 8.8.14 NFHD IN 11 KV RAMCO JGY FEEDER, WHILE DOING BURNT JUMPER WORK, CONDUCTOR OF SINUGRA AG FDR( CROSSING) TOUCH TO IT & DUE TO SHOCK, VICTIM FALL DOWN Report yet not received NA NA By using AB Cable specially near crossing and keeping proper clearance between
two feeders  are prevents  this type of accident.
159 BHUJ Bayath,  A. C. Kasta
A. G. Matang
10.8.14 NFHD WHENEVER PADAMPUR AG FEDDER CONDUCTOR WAS BROKEN ON THAT TIME ONE ELE.ASI WAS WORKED ON SHACKLE POINT POLE AND REPAIR CONDUCTOR AND ANOTHER ELE.ASSI.WAS WORKED AT LST TC STRUCTURE ON,DO JOINT CONDUCTOR AT DISC.ANY HOW CURRENT BOTH SIDE.SO NON FATAL HUMAN ACCIDENT OCCURRED BOTH EMPLOYEE. Report yet not received NA NA Maintenance done of this pole with old conductor replacement and conductor restringing of padampur Ag feeder at point of LST TC structure of shackle point.
160 BHUJ Bayath, 
A. G. Matang
10.8.14 NFHD WHENEVER PADAMPUR AG FEDDER CONDUCTOR WAS BROKEN ON THAT TIME ONE ELE.ASI WAS WORKED ON SHACKLE POINT POLE AND REPAIR CONDUCTOR AND ANOTHER ELE.ASSI.WAS WORKED AT LST TC STRUCTURE ON,DO JOINT CONDUCTOR AT DISC.ANY HOW CURRENT BOTH SIDE.SO NON FATAL HUMAN ACCIDENT OCCURRED BOTH EMPLOYEE. Report yet not received NA NA  
161 BHUJ Ler, 1 Cow, Rabari Megha Kana 24.8.14 FA DUE TO RAIN , DISC INSULATOR PUCTURED AND BROKEN DOWN , FEEDER NOT TRIPPED , ONE COW COME WITH CONTACT WITH POLE AND GOT ELECTROLUTED. Report yet not received NA NA To avoid this type of accident disk insulator was replaced and JE GETCO was inform about nonworking of 11kv panel relay of 11KV Laheriya Ag Feeder, 66 KV Bhujodi S/S. On dtd 24/08/2014 at 19:00 hours. 
162 BHUJ Dayapar, Ranmalji M. Jadeja 27.8.14 FHOS A fatal accident occurred to shree Ranmalji Modji Jadeja human outsider of village Mudhan at location Mudhan ag vistar under 11 kv Ghaduli AG feeder dated 27/08/2014. During visit at site it is concluded that 11 kv conductor is broken at tc center. There may be chance of fatal accident due to snapping of conductor but there is no any spark at land where snapped conductor fall near by accident place and no any human body parts like skin etc found in broken conductor. Cause of death wiil be found after further investigation and P.M.report received. Report yet not received NA NA as per investigation and P.M report
163 BHUJ RAJDEEPSINH VIKRAMSINF JADEJA 20.6.14 FHOS WHILE PLANNING ON THE TERRACE OF UNDER CONSTRUCTION HOUSE VICTIM CAME IN CONTACT WITH LT LINE PASSING NEAR HUSE. Report yet not received NA NA STOP CONSTRUCTIONWORK AT THIS PLACE
164 BHUJ Nagalpar Moti, Virmaram Idamram 31.8.14 FHOS While Victim has parked hydraulic type truck ( Dumper) under 11 kv sinogra Ag fdr line and trolley of truck was lifted upper side by hydraulic and touch to live 11kv wire and direct current pass through metallic body and driver met with fatal accident on driver sheet. Report yet not received NA NA Awareness regarding safe use of electricity and safety rules are prevents  this type of accident
165 BHUJ Gandhidham, 1  Cow 1.9.14 FA Transformer centre located nr plot no 273 ward 10/A under 11kv gurukul feeder, it was raining interminently on  dt 1.9.2014. and leakage current of neutal via earth was observed on visit to site and as it was raining, fault current flowed through neutral earth wire near TC and one cow while passing near the pole & TC which was waterlogged at that time came into direct contact with earthwire which was having leakage current and this live contact led to electrocution of cow.  Report yet not received NA NA Maintanance and earthing work  carried out this location. 
166 BHUJ Maska,1   Cow (Hasan H. Sumra) 3.9.14 FA THERE WAS ONE COW WITH HER OWNER WAS PASSING FOR DRINKING THE WATER IN FORNT OF TRANSFORMER CENTER AND SHE WAS ABOUT 15 FEET FAR FROM T/C AS PER OWNER'S STATEMENT . THE PHASE WIRE OF 3 RD LT SPAN AFTER THE T/C WAS BROKEN AND IT WAS CAME IN CONTACT WITH NEUTRAL WIRE SO,RETURN POWER WAS CAME IN TRANSFORMER CENTER EARTHING.SO,WHEN THE COW WAS PASSING.SHE WAS ATTRACTED TOWARDS THE TRANSFORMER CENTER AND GET ELECTROCUTED AND DIED. Report yet not received NA NA Maintanance and earthing work  carried out this location. 
167 BHUJ Vandhiya,1  Cow,  LALJI RANCHHOD DEVDA 9.9.14 FA  On dated 9.9.14 .approx  at 06.00 hours due to heavy rain fall and heavy wind pressure the tree branch of Neem falls down to LT line conductor. So, the LT Iive conductor got snapped and falls on the cow passing through stree  under and came in
contact with the live conductor & got electric shock and the cow died on the spot.
Report yet not received NA NA LT Arial Bunch provided at both span restringing done, earthing pipe new jumper 
     done at this place. 

168 BHUJ Khedoi, 1 Cow , RAJENDRA SING GANUBHA JADEJA 22.9.14 FA while cow passes under 11 KV line at that time line conductor Brocken and fallen on cow and animal fatal accident occurred Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
169 Junagadh SHRI VASIMBHAI RAJUBHAI BLOACH  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH 41756 NFHOS VICTIM CLIMBED ON TRANSFORMER CENTRE TO CATCH HIS PET BIRD (PIGEON) AND DURING THIS HE SOME HOW CAME IN CONTACT WITH LIVE PART AND MET WITH NON FATAL ELECTRICAL ACCIDENT. Not yet received Not yet received Not yet received FIR done against the victim 
170 Junagadh SHRI BHAGAVAN RAMBHAI BABARIA / KAMLESH KARABHAI BABARIA  VILLAGAE: VERVA   TALUKA:MANAVADAR 41774 FHOS VICTIM WAS SITTING ON TRUCK WHICH WAS FULLY LOADED WITH COTTON AND OVER HEIGHT AND TOUCHED WITH LIVE 11 KV FEEDER LINE WHILE HE WAS REMOVING CABLE & SERVICE WIRE WHICH WAS OBSTACLES TO THE COTTON GOODS AND MET WITH THE FATAL ACCIDENT, DETAIL INVESTIGATION UNDER PROCESS.

Not yet received Not yet received Not yet received FIR done against the victim 
171 Junagadh SHRI ASFAK ALLIMAHMAD SORTHIA (RENTAL)  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH 41778 NFHOS VICTIM WHILE OPENING THE BALCONY OF HIS BUILDING SOME HOW CAME IN CONTACT WITH 11 KV LINE AND CAME IN EITHER DIRECT OR INDIRECT CONTACT WITH 11 KV LINE AND GOT ELECTROCUTED AND MET WITH NON FATAL ELECTRICAL ACCIDENT. THE BALCONY IS TOTALLY ILLEGAL.

Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
172 Junagadh SHE BUFFALO OF SHRI DEVAJIBHAI DAYABHAI RATHOD      VILLAGE: BARVALA   TALUKA: BHESAN 41790 FA BUFAALO WHILE GRASSING CAME IN CONTACT WITH FENCING OF MOBILE TOWER  AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT.  Not yet received Not yet received Not yet received Proper maintenance done in the same group.
173 Junagadh SHE BUFFALO OF SHRI ABUBHAI  MULADAD  BLOCH      VILLAGE: JAVANTRI   TALUKA: TALALA 41803 FA DUE TO CYCLONIC PRESSURE IN ARABIAN SEA, HEAVY WIND PRESSURE WAS THERE AND AS A RESULT SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS CONDUCTOR AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
174 Junagadh SHE BUFFALO OF SHRI GANDA BHAI RAMBHAI KANALA      VILLAGE: JAVANTRI   TALUKA: TALALA 41803 FA DUE TO CYCLONIC PRESSURE IN ARABIAN SEA, HEAVY WIND PRESSURE WAS THERE AND AS A RESULT SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS CONDUCTOR AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
175 Junagadh COW (INDIAN) OF SHRI SAMATBHAI RAMBHAI VANIYA      VILLAGE: JAVANTRI   TALUKA: TALALA 41803 FA DUE TO CYCLONIC PRESSURE IN ARABIAN SEA, HEAVY WIND PRESSURE WAS THERE AND AS A RESULT SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS CONDUCTOR AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
176 Junagadh KUMARI DIVYABEN JITENDRABHAI LALVANI  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH 41805 FHOS DURING HEAVY RAIN VICTIM CAME IN CONTACT WITH DETERIORATED LIVE PART OF INTERNAL HOUSE WIRING AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
177 Junagadh LEOPARD OF  FOREST DEPARTMENT        VILLAGE: UMERETHI   TALUKA: TALALA 41819 FA DUE TO FAILURE OF PIN INSULATOR CONDUCTOR SNAPPING TOOK PLACE AND DURING THIS NO TRIPPING WAS OBSERVED DUE TO SINGLE PHASING OF FEEDER. AT 7:15 THE FEEDER WAS CHARGED FOR GIVING THREE PHASE POWER AND AS IT WAS NOT GETTING CHARGED SO TRIES WERE GIVEN AS PER NORMS AND DURING THIS LEPORD MIGHT HAVE COME IN CONTACT WITH SNAPPED CONDUCTOR AND MIGHT HAVE MET WITH FATAL ACCIDENT. DETAIL INVESTIGATION UNDER PROCESS. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
178 Junagadh CALF OF  KANTILAL  MOHANBHAI PARMAR      VILLAGE: GANTHILA   TALUKA: VANTHALI 41806 FA A FATAL ACCIDENT OCCURRED TO A MALE CALF DUE TO LEAKAGE CURRENT FROM THE EARTHING AT TRANSFORMER. CALF CAME IN DIRECT CONTACT WITH LEAKAGE CURRENT OF EARTHING CURRENT AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
179 Junagadh SHRI RAMBHAI  JESINGBHAI MALIVAD  VILLAGAE: MENDERDA   TALUKA:MENDERDA 41830 NFHD A MECHANICAL ACCIDENT OCCURRED TO SHRI RAMBHAI JESHINGBHAI MALIVAD DUE TO SLIPPING DURING LT MAINTENANCE ACTIVITY.

Not yet received Not yet received Not yet received Action taken agaisnt the employee for careless ness in work.
180 Junagadh      VILLAGAE: DOLATPARA   TALUKA:JUNAGADH 41831 FA DUE TO RAIN AND WATER LOGGING NEAR TRANSFORMER CENTRE IN SPITE OF PROVIDING PVC RIGID PIPE TO THE EARTHING WIRE, COW GRASSING NEAR THE TRANSFORMER CAME IN CONTACT WITH LEAKAGE EARTHING CURRENT AND GOT ELECTROCUTED AND MET WITH FATAL ANIMAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
181 Junagadh SHRI KANTIBHAI RUDABHAI BAGDA  VILLAGAE: RAVANI(K)   TALUKA:VISAVADAR 41846 FHD VICTIM MAY CLIMBED ON 11 KV DP OF AG FEEDER HAVING GO SWITCH TO OBSERVE JUMPER DUE TO COMPLAIN OF DEEM VOLTAGE TO Ag. CONSUMERS, AT THAT TIME HE MIGHT BE SUDDENLY CLIMBED ON MORE HEIGHT AND HIS HANDS MAY GOT INDUCTION SHOCK AND  FALL DOWN FROM HEIGHT AND DUE TO MECHANICAL INJURY IN HIS BODY ACCIDENT IS CONVERTED INTO FATAL. THERE IS NO DIRECT EYEWITNESS OF THIS ACCIDENT. FURTHER INVESTIGATION IS UNDER PROCESS. P.M. REPORT IS AWAITING.THERE IS NO TRIPPING ON 11KV SUKHPUR AG FEEDER NEAR ABOUT THE TIME OF ACCIDENT PERIOD. Not yet received Not yet received Not yet received Shaw cause notice issued to Deputy Engineer.
182 Junagadh SHE BUFFALO OF SHRI MULUVALA RANAVALA VALA      VILLAGE: NAVAGAM   TALUKA: JUNAGADH 41848 FA IN LT LINE CONDUCTOR OF PRABHU NA PIPADA VALU GROUP OF 11 KV KHADIA AG FEEDER CONDUCTOR SNAPPED AND FALLING DOWN ON THE GROUND (RETURN CONDUCTOR)AND  BUFFELO GETTING LIVE CONTACT WITH CONDUCTOR. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
183 Junagadh SHE BUFFALO OF SHRI DEVABHAI  RAJABHAI  DODIYA      VILLAGE: ANANDPARA   TALUKA: SUTRAPADA 41850 FA DUE TO LEAKEAGE CURRENT NEAR WATER LOGGING AREA NEAR TRANSFORMER LEAKEAGE CURRENT FROM TRANSFOMER. DUE TO THIS LEAKEAGE CURRENT THE BUFFALO GOT ELECTROCUATED AND MET WITH FATAL ANIMAL ACCIDENT.DETAIL INVESTIGATION IS UNDER PROCESS. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
184 Junagadh GOAT OF SHRI JAGABHAI DEVSHIBHAI MEVADA      VILLAGE: GOVINDPUR   TALUKA: VISAVADAR 41850 FA FENCING OF FARM WAS DIRECTLY CONNECTED TO THE LT POLE EARTH WIRE. GOAT CAME IN DIRECT CONTACT WITH THE LEKEAGE CURRENT IN EARTH WIRE CAME IN CONTACT THROUGH THE FENCING AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
185 Junagadh SHE BUFFALO OF SHRI NIZAR KASAM SORATHIYA      VILLAGE: CHITRAVAD   TALUKA: TALALA 41853 FA DUE TO HEAVY WIND & RAIN TREE BRANCH FELL DOWN  ON THE LT LINE CONDUCTOR, DUE TO THIS SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS FALLEN LIVE WIRE AND  IT GOT ELECTROCUTED & MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
186 Junagadh COW (INDIAN) OF SHRI RAJSHI  HAMIR BHOLA      VILLAGE: LODHAVA   TALUKA: SUTRAPADA 41854 FA THERE WAS A MINOR LEAKEAGE CURRENT NEAR WATER LOGGING AREA NEAR  LT POLE OF TRANSFORMER CENTRE . THE COW CAME IN CONTACT WITH THIS LEAKEAGE CURRENT GOT ELECTROCUATED AND MET WITH FATAL ANIMAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
187 Junagadh SHE BUFFALO OF SHRI RAJSHI  HAMIR BHOLA      VILLAGE: LODHAVA   TALUKA: SUTRAPADA 41854 FA THERE WAS A MINOR LEAKEAGE CURRENT NEAR WATER LOGGING AREA NEAR  LT POLE OF TRANSFORMER CENTRE . THE BUFFALO CAME IN CONTACT WITH THIS LEAKEAGE CURRENT GOT ELECTROCUATED AND MET WITH FATAL ANIMAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
188 Junagadh COW (INDIAN) OF SHRI DEVABHAI JADAVBHAI VADHER      VILLAGE: PANDVA   TALUKA: VERAVAL 41864 FA DUE TO HEAVY WIND & RAIN, LT LINE CONDUCTOR SNAPPED FROM INSULATOR AND WAS HANGING ON "C" CLAMP WHICH RESULTED IN EARTH LEAKEAGE. ANIMAL GRASSING NEAR LT POLE CAME NEAR TO THIS AFFECTED POLE ANS GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
189 Junagadh SHE BUFFALO OF SHRI DEVABHAI JADAVBHAI VADHER      VILLAGE: PANDVA   TALUKA: VERAVAL 41864 FA DUE TO HEAVY WIND & RAIN, LT LINE CONDUCTOR SNAPPED FROM INSULATOR AND WAS HANGING ON "C" CLAMP WHICH RESULTED IN EARTH LEAKEAGE. ANIMAL GRASSING NEAR LT POLE CAME NEAR TO THIS AFFECTED POLE ANS GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
190 Junagadh SHE BUFFALO OF SHRI  SARMANBHAI   HIRABHAI  SINDHAL      VILLAGE: JUNAGADH   TALUKA: JUNAGADH 41866 FA DUE TO HEAVY WIND & RAIN, LT LINE CONDUCTOR SNAPPED FROM INSULATOR AND WAS HANGING ON "C" CLAMP WHICH RESULTED IN EARTH LEAKEAGE. ANIMAL GRASSING NEAR LT POLE CAME NEAR TO THIS AFFECTED POLE ANS GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
191 Junagadh LEOPARD OF SHRI FOREST DEPARTMENT        VILLAGE: MADHUPUR   TALUKA: TALALA 41873 FA LEOP[ORD CLIMBED ON AG DP OF TRANSFORMER APPROX 15 FEET ABOIVE THE GROUND LEVEL AND CAME IN CONTACT WITH DO WIRE/JUMPER AND GOR ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received No action taken as animals fault.
192 Junagadh SHRI DILIPBHAI PARBATBHAI JETHAVA  VILLAGAE: SANTALPUR   TALUKA:VANTHALI 41873 NFHOS A NON FATAL ACCIDENT OCURRED TO VICTIM WHILE HE WAS IN PROCESS OF CLEANING HIS TERRACE. DURING THE CLEANING PROCESS HE CAME IN CONTACT WITH NEAR BY LINE PASSING AND GOT ELECROCUTED AND MET WITH NON FATAL ELECRICAL ACCIDENT.  Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
193 Junagadh SHRI  BHAVESHBHAI  PRABHUDAS  AGRAVAT  VILLAGAE: TALALA   TALUKA:TALALA 41872 NFHOS BOTH VICTIMS WERE WORKING IN NAGAR PALIKA TALALA IN STREET LIGHT BRANCH AND WERE INVOLVED IN STREE TLIGHT REPAIRING WORK WITHOUT ANY LINE CLEAREANCE OR PERMISSION. AND WHILE REPARING THE STREET LIGHT THEY CAME IN CONTACT WITH JUMPER OF NEAR BY TRANSFORMER AND GOT ELECTROCUATED & MET WITH NON FATAL ACCIDENT. Not yet received Not yet received Not yet received Letter written to nagarpalika for the same.
194 Junagadh SHRI JUMABHAI  HASAN BHAI  DAL  VILLAGAE: TALALA   TALUKA:TALALA 41872 NFHOS BOTH VICTIMS WERE WORKING IN NAGAR PALIKA TALALA IN STREET LIGHT BRANCH AND WERE INVOLVED IN STREE TLIGHT REPAIRING WORK WITHOUT ANY LINE CLEAREANCE OR PERMISSION. AND WHILE REPARING THE STREET LIGHT THEY CAME IN CONTACT WITH JUMPER OF NEAR BY TRANSFORMER AND GOT ELECTROCUATED & MET WITH NON FATAL ACCIDENT. Not yet received Not yet received Not yet received Letter written to nagarpalika for the same.
195 Junagadh SMT  SHANTABEN  MADHABHAI  RATHOD  VILLAGAE: GOLADHAR   TALUKA:JUNAGADH 41879 NFHOS VICTIM ON TERRACE WAS INVOLVED IN PLUCKING OF VEGETABLE FROM STEMS. DURING THIS WORK AND DUE TO DEW A LIGHT ELECTRIC SHOCK FROM NEARBY 11 KV WAS FELT TO VICTIM AND WAS FALLEN DOWN AND MET WITH NON FATAL  ACCIDENT. THE ROOF HOUSE WAS BUILT UP ILLEGALLY.

Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
196 Junagadh SHE BUFFALO OF SHRI  KANABHAI  KHODABHAI   MAKWANA      VILLAGE: MAJEVADI   TALUKA: JUNAGADH 41880 FA DUE TO HEAVY WIND & RAIN THERE WAS A SHORT CIRCUIT ON THE LT LINE CONDUCTOR, DUE TO THIS SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS FALLEN LIVE WIRE AND  IT GOT ELECTROCUTED & MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
197 Junagadh SHE BUFFALO OF SHRI  SURESHBHAI   BHIKHABHAI  KHUMAN      VILLAGE: NAVI CHAVAND   TALUKA: VISAVADAR 41886 FA DUE TO HEAVY WIND & RAIN THERE WAS A SHORT CIRCUIT ON THE HT LINE CONDUCTOR, DUE TO THIS SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS FALLEN LIVE WIRE AND  IT GOT ELECTROCUTED & MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
198 Junagadh SHRI  RAJESHBHAI   PITHABHAI  RANVA  VILLAGAE: SHAPUR   TALUKA:VANTHALI 41884 FHOS  VICTIM CAME IN DIRECT CONTACT WITH 11 KV VELNATH JGY LIVE WIRE. VICTIM ILLEGALLY CONSTRUCTED THE BUILDING WHICH WAS ILLEGAL IN NHAI AND PGVCL NORMS, AND WHILE STANDING ON THE ROOF/WALL VICTIM SOME HOW CAME IN DIRECT CONTACT WITH LIVE CONDUCTOR AND GOT ELECTROCUATED AND MET WITH FATAL HUMAN ACCIDENT. Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
199 Junagadh SHRI LAKHMANBHAI SURABHAI BAMANIYA  VILLAGAE: KANAVADLA   TALUKA:VISAVADAR 41894 NFHD AFTER REPLACEMENT OF TRANSFORMER CENTRE OF WATER WORKS ,VICTIM WAS BINDING D.O FUSE WITH THE HELP OF PLIER AND THAT TIME LINE CLEAR WAS RETURNED.AS A RESULT HE GOT ELECTRIC JERK AND MET WITH NON FATAL ACCIDENT.  Not yet received Not yet received Not yet received Explaination asked from EE and DE for the same.
200 Junagadh SHRI  KIRITKUMAR   DHIRAJLAL  PANDYA  VILLAGAE: BHALGAM   TALUKA:VISAVADAR 41897 NFHD VICTIM WAS PERFORMING JUMPERING WORK WITH LINE CLEAR AND DURING THIS PERIOD POWER WAS FEED FROM UNKNOWN POWER SUPPLY AND HE GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT.  Not yet received Not yet received Not yet received Explaination asked from EE and DE for the same.
201 Junagadh SHRI  SATISHBHAI  RAMBHAI  JASVANI  VILLAGAE: VERAVAL   TALUKA:VERAVAL 41900 NFHOS ACCIDENT TOOK PLACE DUE TO BLASTING OF CTPT UNIT OF HT CONNECTION OF M/S GOPAL SEA FOODS. DUE TO BLAST OF CT PT UNIT VICTIM CAME IN CONTACT WITH HOT OIL OF THE UNIT AND MET WITH BURNT INJURIES. Not yet received Not yet received Not yet received As its an incident no action taken.
202 Junagadh SHRI  SURESHBHAI  PREMDAS  MESVANIA  VILLAGAE: VADLA   TALUKA:VANTHALI 26-09-14 NFHD VICTIM WAS PERFORMING JUMPERING WORK WITH LINE CLEAR AND DURING THIS PERIOD POWER WAS FEED FROM UNKNOWN POWER SUPPLY AND HE GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT.  Not yet received Not yet received Not yet received Explaination asked from EE and DE for the same.
203 Junagadh SHE BUFFALO OF SHRI BHAYABHAI GOVINDBHAI GAMARA      VILLAGE: BHESAN   TALUKA: BHESAN 18-08-14 FA LT LINE CONDUCTOR BROKEN FROM FAULTY SHACKLE INSULATOR,  BUFFALO CAME IN DIRECT CONTACT WITH SNAPPED CONDUCTOR AND GOT ELECTROCUTED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
204 Bhavnagar Royal  -  Buffalo &  Ghohabhai Savajibhai Parmar- ( Owner ) 21-04-14 FA Non-Fatal Human & Fatal Animal accident occured due to Cyclonic high Wind flow, LT Conductor snapped & fell on fencing wire of farm and Buffalo tied near the fencing wire & got electrocuted & same time Victim Smt. GG Parmar tried to save his animal ( buffalo ), so she also got the electric shock  Report yet not received NA NA lt conductor restringing done and treecutting with complete maintanance carried out.
205 Bhavnagar Royal  -  Gomatiben Ghoghabhai Parmar 21-04-14 NFHOS Non-Fatal Human & Fatal Animal accident occured due to Cyclonic high Wind flow, LT Conductor snapped & fell on fencing wire of farm and Buffalo tied near the fencing wire & got electrocuted & same time Victim Smt. GG Parmar tried to save his animal ( buffalo ), so she also got the electric shock  Report yet not received NA NA lt conductor restringing done and treecutting with complete maintanance carried out.
206 Bhavnagar Navagam  -  Rohitbhai Velabhai Rathod 01-05-14 FHOS Gross negligency & Violation of sefty measures  during Victim was  Standing  on compound Wall with Iron Rod approx 17.5 ft long  & at the time upper side of iron Rod came in contact with 11 KV line & got electric shock and met with Fatal accident. Report yet not received NA NA Gross negligency by victim & Public awarness
207 Bhavnagar Bhavnagar  -  Pravinbhai Devajibhai Maru -EA 08-06-14 FHD While Working on girder pole, the pole broke down from bottom & Victim along with girder fell on the ground & succumbed to head injuries. Report yet not received NA NA Done Survey of all Girder pole and replaced deteriorated pole from bottom,If required muffing done after fabrication,Support pole provided to tension pole,Reactivated Guy wire to avoid recuuence of such accident.
208 Bhavnagar Navagam  -  Gopalbhai Natavarbhai Umaraliya - I/c Sr.Tech 18-06-14 NFHD Departmental Non-Fatal accident ( electrical burnts ) occurred during CTPT Unit installed at Consumer Premises & suddenly blast and highly flame generated and both of employees got electrical flame & burnt. Report yet not received NA NA CTPT replaced & Now onward more Vigilant during works
209 Bhavnagar Navagam  -  Sanskarbhai Sondabhai Kojani-EA 18-06-14 NFHD Departmental Non-Fatal accident ( electrical burnts ) occurred during CTPT Unit installed at Consumer Premises & suddenly blast and highly flame generated and both of employees got electrical flame & burnt. Report yet not received NA NA CTPT replaced & Now onward more Vigilant during works
210 Bhavnagar Bhavnagar  -  Kaushikbhai Hareshbhai Makawana 09-07-14 FHOS Fatal Human accident occurred due to LT Leakage Current flow from Removed Cotton Tape Open Joint Service Wire to GI Earth Wire. Due to rain & Wind the Soil become muddy & Wet, so he got electric Shock Report yet not received NA NA Earthings are reactivated & rigid PVC pipe is provided.Removed service joints and provided new twin core service.
211 Bhavnagar Ukharala ( Mamsa GIDC)  -  Sanjaybhai Dhirubhai Jadav 10-07-14 FHOS Fatal & Non -Fatal Human accident occurred during both of Victims were tried to bring out under ground Water tank by tripoleStand ( Ghodi ), near / below the 11 KV line at the time,  the Iron Rod of tripole stand touche to 11 KV line & got electric Shock Report yet not received NA NA Ground level below 11 KV line lover down by factory owner 
212 Bhavnagar Ukharala ( Mamsa GIDC)  -  Roshniben Akbarbhai Saiyad 10-07-14 NFHOS Fatal & Non -Fatal Human accident occurred during both of Victims were tried to bring out under ground Water tank by tripoleStand ( Ghodi ), near / below the 11 KV line at the time,  the Iron Rod of tripole stand touche to 11 KV line & got electric Shock Report yet not received NA NA Ground level below 11 KV line lover down by factory owner 
213 Bhavnagar Bhikada  -  Himmatbhai Devajibhai Kansara 12-07-14 FHOS Fatal Human accident occurred during victim was trying to repaired D.O fuse by using wet bamboo in his hand, without taking any permission from PGVCL authority  Report yet not received NA NA Gross negligency by victim & Public awarness
214 Bhavnagar Shivamnagar  -  Uvesh Mustubhai Saiyad 12-07-14 NFHOS Non- Fatal accident occurred due to leakage current passed through TV Cable by Joint of illigal PVC Cable wire & TV Cable by consumer for theft of electricty.    The Deputy Engineer, Gariyadhar-1 Registered Police Complaints on  Illigally  Network Disturbance. Report yet not received NA NA such type cable tv wire remove and booked under theft.
215 Bhavnagar Shivamnagar  -  Mahek Mustubhai Saiyad 12-07-14 NFHOS Non- Fatal accident occurred due to leakage current passed through TV Cable by Joint of illigal PVC Cable wire & TV Cable by consumer for theft of electricty.    The Deputy Engineer, Gariyadhar-1 Registered Police Complaints on  Illigally  Network Disturbance. Report yet not received NA NA such type cable tv wire remove and booked under theft.
216 Bhavnagar Bhavnagar  -  Aryan Arvindbhai Jethava ( Dhobi ) 14-07-14 FHOS Fatal Human accident occurred during Victim was playing & Stand on bricks which are near the PSC Pole and Contact with GI earthing wire and GI wire was already energized with LT leakage current which flow from pole SMC due to insulated tape of red phase of 3-phase cable was damaged. Report yet not received NA NA PVC Cable replace by LT ABC 
217 Bhavnagar Ranparada    -  Buffalo-She & Pathubhai Golanbhai Kamaliya - Owner 18-07-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time buffalo may pass near by transformer centre at came in contact & got electric Shock Report yet not received NA NA TC maintanance done and new earthing provided with pvc rigid pipe
218 Bhavnagar Sanala ( NAVA )  -  Pravinsinh Bhikhubha Sarvaiya 26-07-14 FA Fatal Animal accident occurred due to LT leakage current flow from Transformer Nuetral to Earthing Wire and also due to Rain the leakage current spread near the Transformer Center, and Buffalo may be came in contact with this leakage current &  Potential difference and got electric shock  Report yet not received NA NA TC maintanance done and new earthing provided with pvc rigid pipe
219 Bhavnagar Ratol  -  Buffalo -She & Bachubhai Punabhai Bhaliya - Owner  01-08-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time buffalo may pass near by transformer centre at came in contact & got electric Shock Report yet not received NA NA TC maintanance done and new earthing provided with pvc rigid pipe
220 Bhavnagar lapadiya  -  Buffalo -She &  Pachabhai Bhagvanbhai Vaghela -Owner 02-08-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time buffalo may pass near by transformer centre at came in contact & got electric Shock Report yet not received NA NA transformer center maintanance done and new earthing and new fuse provided.
221 Bhavnagar Kumbhan  -  Cow ( Indian ) &  Anandbhai Rambhai Gamara - Owner 05-08-14 FA Due to Wheather effect Joint Opened between LT Line dropper & Consumer Service & it's touched to Guy wire which have no Guy insulator provided so leakage current flow  from Joint to Guy wire and when Cow passing nearby it, she got electric shock and met with Fatal accident Report yet not received NA NA new stay is provided , also guy insulator provided 
222 Bhavnagar Lilvan  -  Shantubha Kanubha Vala 06-08-14 NFHOS Non-Fatal Human accident occurred during Vicitm stand on tarrace with babared wire in his hand due to gross negligency, the babared wire came in 11 KV Line Induction Zone & got electrical Shock  Report yet not received NA NA required maintainanace carried out at site
223 Bhavnagar Valukad  -  Cow ( Indian ) & Dineshbhai Bijalbhai Baraiya -Owner 08-08-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time Cow ( Indian )  passed near by transformer centre at came in contact with Wet Land and due to Potential difference, Cow got electric Shock & died Report yet not received NA NA transformer center maintanance done and new earthing and new fuse provided.
224 Bhavnagar Morchand  -  Bairajba Balvantsinh Gohil 16-08-14 FHOS Due to rain & Wind Pressure LT bare conductor broken and fall down on land and Vicitm may be contact with LIVE Conductor and got electric Shock and  met with Fatal accident Report yet not received NA NA LT line maintenance carried out
225 Bhavnagar Tantaniya  -  Buffalo -She & Vithalbhai Labhubhai Lakkad - Owner 25-08-14 FA Fatal animal accident occurred due to heavy wind & Rain, neutral Conductor of LT line was broken from middle of span & fell on ground at the time buffalo may came in contact with neutral conductor & got electric shock. Report yet not received NA NA AG group maintannce done , also deteriorated conductor replaced and new conductor provided
226 Bhavnagar Kalela  -  Buffalo - She & Babubhai Virabhai Aradu 01-09-14 FA Fatal animal accident occurred buffloes ( Minor & Major ) due to service line GI Wire was brokean & hanging from pole to earth and also it was contact to LT Conductor & Leakage Current flow through GI Wire to Earth. When both  are came in contact with this energised GI wire, they are got electric shock Report yet not received NA NA broken GI wire removed ,Necessory maintainance carried out
227 Bhavnagar Kalela  -  Buffalo - She & Babubhai Virabhai Aradu 01-09-14 FA Fatal animal accident occurred buffloes ( Minor & Major ) due to service line GI Wire was brokean & hanging from pole to earth and also it was contact to LT Conductor & Leakage Current flow through GI Wire to Earth. When both  are came in contact with this energised GI wire, they are got electric shock Report yet not received NA NA broken GI wire removed ,Necessory maintainance carried out
228 Bhavnagar Dihor  -  Lakabhai ( Laxmanbhai ) Bhimabhai Chosala 13-09-14 FHOS One Side guarding wire got snapped between TC  & Pin point , The One Side broken guarding wire was lying beside the river bed, which is not easily approachable From the both the side of river, but As per statement of victims relative ,who reached the site at  around about 5.30 PM, the victim was lying on  river bed, besides the broken guarding wire. The villagers inform village helper ,  he immediately reached at Site and found that no power was Flowing Through Guarding Wire , also there was least  possibility of touching the  live 11 KV line with Guarding Wire, As there is minimum clearance of two feet, so actual reason of this incidence is not found,  How the victim got electric shock. After P.M. report actual reason of this incidence can be known. Report yet not received NA NA re-guarding done properly and complete maintanance carried out of accident place.
229 Bhavnagar Bagadana  -  Lakhabhai Arjanbhai Chavada 26-09-14 NFHOS Non-Fatal Human accident occurred due to Binding of LT Conductor was re-Opened & Conductor was fall into C-Clamp and C-Clamp earthed through GI Wire, So its leakage current to earth but at the time Victim was stand on nearby LT pole in  flood irregation ( Water Canel - Dhoriya ) and contact with leakage current and got electrical Shock  Report yet not received NA NA LT maintannce with all shakal rebinding and new earthing to all poles provided with pvc rigid pipe
230 Bhavnagar Alang  -  Buffalo - She & Budhabhai Vithalbhai Solanki 28-09-14 FA LT Line conductor got damaged in middle part due to babool tree near to the line, & conductor snapped from the middle part, the buffalo when passes through that area where broken wire was lying & came in contact with wire & met with Fatal accident. Report yet not received NA NA lt conductor restringing done and treecutting with complete maintanance carried out.
231 BTD At Village Khopala  , COW OF Shree Devabhai Karshanbhai Bharwad 20.04.14 FA In Evenning 4:45 PM, mini cyclone and rain was falling. Unauthorized gram panchayat Khopala, loud speaker network’s co-axial cable supported by Iron wire was falten on earth and its supported wire touch fuse lead situated on PSC poles, about 6:30 PM owner of Deva bhai Karshanbhai Bharwad’s cow was came in contact with co-axial cable’s iron wire. Cow get the shock and fall down and died. Report Yet Not Received NA NA Required Instruction given to SDO.
232 BTD At village Derala, BUFFALLO OF Shri Vitthalbhai Vashrambhai Miyani 31.05.14 FA In morning 8:00 am,at premises of Shri Vithhalbhai Vashrambhai Miyani 1phase lighting connection,Main Service Twin Wire bind at Iron Hook of Beam situated above Main Iron Gate,the main service wire was break at this iron hook and phase was touched on this hook,leakage current was passed through this hook to beam and Main Iron Gate.Shri Vithhalbhai Vashrambhai Miyani’s Buffallow pass through that iron Main Gate and Came in contact & get the shock and fall down and died. Report Yet Not Received NA NA Rectification Done.
233 BTD At village Kariyani, Shree kantibhai Martabhai katara 18.05.14 NFHD Victim instructed to release new Ag connection of Shri Nagarbhai Gatorbhai of vill kariyani . Victim has installed the meter and to start the jumper work for release of new connection, victim has taken line clear for 11kv Samadhiyala -2 ag feeder instead of 11 KV vajeli ag feeder .due to such mistake of victim, he got electric shock during jumper work and fall down from pole. Report Yet Not Received NA NA (1) C.S. ISSUED TO K M KATARA VIDE NO: BTDN/HR/DA/213, DATED 28.08.14
(2) C.S. ISSUED TO J G MAKWANA (DE) VIDE NO: BZ/HR/DA/BTD/JGM/1303 DATED 31.07.2014 ---POINT 6(2) IN C.S.
(3) SHOW CAUSE NOTICE TO K H TRIVEDI (ALM). BTDN/HR/DISC/154, DATED 02.06.2014
234 BTD At village Haddad, Amit Sureshbhai Belani 20.06.14 NFHD Non-fatal accident occurred to Shri A S Belani, while working on DP structure (11 KV Haddad JGY), has met with electrical shock. The line clear was taken by Y H Multani (EA), and line was also earthed from incoming side, i.e. from is s/s end. Looking to the site position unknown power reflected to 11 KV Haddad JGY feeder at DP Structure. The investigation is going on and detail report submitted after scrutiny of MRI report of relevant AG crossing feeder. Report Yet Not Received NA NA Instructed to all Line staff, Earthing must be done both side of 11 KV Line before statrting of work on line.
235 BTD At village Raliyana, COW OF Shri Harjibhai Bhikhabhai Jogava 17.06.14 FA In afternoon 1:30 P.M., at Balmandir TC village: Raniyala, a cow of Shri Harjibhai Bhikhabhai Jogava’s was passing under TC. Due to wet ground and leakage current to transformer through TC earthing cow came in contact with earthing G.I. wire got shocked. Fall Down and died. Report Yet Not Received NA NA Earthing Reactiveted and Rectification done.
236 BTD At village Nana Paliyad, Buffallo of shri Mansukhbhai  Gordhanbhai 13.07.14 FA Due to heavy rain and wind village TC cable fired and live part of cable touch to guy wire below guy insulator thus current passes through guy wire and buffalo touch to guy wire and got electric shock. Report Yet Not Received NA NA TC Maintenance done.
237 BTD At village Viravadi, Buffallo of Madhabhai Arjanbhai Talvadiya 06.08.14 FA In After noon, mini cyclone and rain was falling. Due to heavy wind, LT Conductor was snapped out and falling down on earth, Buffalo of Shri Madhabhai Arjanbhai Talvadiya was passing nearby snapped conductor and his leg came in contact with live conductor, so, the buffalo got shocked and died. Report Yet Not Received NA NA LT Maintenance done.
238 BTD At village Dhola, Buffallo of shri Bhayabhai Ranabhai Galani 28.08.14 FA The buffalo was wandering to eat the grass and to drink the water near lack. After drinking water it climbs the boundary of lack. The boundary of the lack is at height of 8 feet.  The Langala JGY feeder is   passing over the boundary. The one pole of the feeder, was tilted due to guy was cut by the farmer. Due to height of boundary and tilted pole the distance between the line and the boundary is about 4 feet. The buffalo might have came in contact with conductor and it got shock and died Report Yet Not Received NA NA  
239 BTD At village Kumbhara, Shri Ghansyambhai  Govindbhai Saliya 27.09.14 FHOS When pole carting truck passing under 11 KV Paliyad JGY crossing of 55mm AB Conductor at that time, suddenly by unknown reason, conductor came in contact with pole lifting instrument and victim got electric shock and died.  Report Yet Not Received NA NA  
240 BTD At village Kumbhara, Shri Bharatbhai Mavubhai  Sarakadiya 27.09.14 NFHOS When pole carting truck passing under 11 KV Paliyad JGY crossing of 55mm AB Conductor at that time, suddenly by unknown reason, conductor came in contact with pole lifting instrument and victim got electric shock and died.  Report Yet Not Received NA NA  
241 AMRELI 1 NO OF UNKNOWN COW,RAJULA 14-04-14 FA WHILE REPAIRING WORK WAS DONE BY NAGARPALIKA FOR STREETLIGHT CONNECTION, ONE END (1/18 WIRE) WAS BROKEN AND AT THAT TIME ANIMAL CAME TOUCHED THIS LIVE WIRE AND GOT ELECTROCUTED.  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
242 AMRELI GIGABHAI VIHABHAI SOLANKI,TRAKUDA 16-04-14 FHOS THREE LINE STAFF OF PGVCL – KHAMBHA SUB DIVISION INCLUDING LINE INSPECTOR WERE WORKING ON FIRST D.P. OF 11KV TRAKUDA AG. FEEDER IN YARD OF SUBSTATION FOR REPAIRING ONE JUMPER ON D.P. THE FEEDER WAS MADE OFF AND BREAKER TROLLEY WAS TAKEN OUT BY S.B.O. AS PER INSTRUCTION OF LINE INSPECTOR. AT THE SAME TIME THE LINE INSPECTOR RECEIVED A CALL FROM CONTRACTOR PERSON REGARDING LINE CLEAR OF TRAKUDA AG. FEEDER FOR TAPPING OF AG CONNECTION. THE LINE INSPECTOR INFORMED HIM THAT FEEDER IS OFF & THEY ARE MAKING JUMPER WORK AT YARD & ALSO SAY TO CARRY OUT THEIR TAPPING WORK & INFORM TO HIM AFTER COMPLETION. IN BETWEEN DP JUMPER WORK COMPLETED LINE INSPECTOR FORGET ABOUT CONTRACTOR WORK & INSTRUCT SBO TO ON FEEDER RESULTING OCCURRENCE OF FATAL ACCIDENT.   SHORT CIRCUITING AND EARTHING THE LINE BEFORE EXECUTION OF WORK. THE CONTRACTOR PERSON GOT AN ELECTRIC SHOCK AND DECLARED DEAD AT CIVIL HOSPITAL KHAMBHA. PM REPORT AND DETAIL INVESTIGATION  FOLLOWS. THE CONTRACTOR DOES NOT MAKE LINE EARTH DURING WORK * LINE INSPECTOR HAS NOT TAKEN LINE CLEAR ALSO. -- -- -- LINE INSPECTOR FOUND RESPONSIBLE,HE WAS SUSPENDED AND EDUCATE ALL LINE STAFF DURING LINE WORK
243 AMRELI SHRI ATULBHAI BHIKHABHAI SIDHDHPURA(E.A.),MALAVIYA PIPALIYA 06-05-14 NFHD LIGHTENING STROCK OCCURED IN NEAR VICINITY AND DUE TO FEAR HANDS ARE OPENED AND FALLEN DOWN FROM THE POLE WHILE CLIMBING ON POLE AND MET TO NON FATAL ACCIDENT.  -- -- -- SAFETY AWARENESS AMONG STAFF MADE THROUGH TAINING.
244 AMRELI SHRI MANSUKHBHAI BHURABHAI DOBARIYA,VAVERA 09-05-14 NFHOS A. THE VICTIM CLIMBING ON 63 KVA T/C CENTER FOR REPAIRING OF D.O.FUSE AND TOUCH TO JUMPER LYING BETWEEN D.O.FUSE AND T/C , AND GOT ELECTROCUTED. THE VICTIM RELATIVE DOES NOT INFORM TO PGVCL EMPLOYEE OR OFFICE ABOUT SUCH ACCIDENT BUT SAME IS COME IN TO KNOWLEDGE IN DY.ENGINEER RAJULA RURAL VIDE  RAHULA POLICE STATION LETTE DT:-19.05.14.THE DY.ENGINEER RAJULA RURAL HAS ISSUE NOTICE TO VICTIM BROTHER FOR NON INFORMING PGVCL OFFICE ABOUT ACCIDENT. THE VICTIM BROTHER CONFESS IN HIS STATEMENT THAT VICTIM GOT ELECTROCUTED DUE TO HIS MISTAKE ONLY. THE ALL RELAVANT STATEMENT ATTACHED HERE WITH -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
245 AMRELI SHRI HARESHBHAI VALLABHBHAI VEGAD,LUNIDHAR 11-05-14 NFHOS THE ACCIDENT OCCURRED WHEN VICTIM TRY TO MAKE UNAUTHORIZED WORK ON TRANSFORMER AT HIS FIELD -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
246 AMRELI 1 BUFFALO OF SHRI KATHADBHAI BACHUBHAI GAVTARMOTA, MACHIYALA 11-05-14 FA THE BUFFALO TOUCH TO BROKEN LT LINE WIRE & GOT ELECTROCUTED  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
247 AMRELI B.J.SONDARAVA,UNA 17-05-14 NFHD DURING THE WORK OF  REPAIRING OF BURNT JUMPER OF 11 KV LINE , VICTIM LOOSE HIS BALANCE AND FALL DOWN FROM SHACKLE POLE . IN THIS MECHANICAL ACCIDENT  BOTH LEGS OF VICTIM HAS BEEN FACTURED.  -- -- -- VICTIM HIMSELF RESPONSIBLE AND STRICT DISCIPLINARY ACTION TAKEN FOR NEGLEGENCE OF SAFETY RULES AND REGULATION
248 AMRELI HASMUKHBHAI AMRUTLAL SAPARA,VADIA 22-05-14 FHOS THE ACCIDENT WAS OCCURRED WHEN  A MENTALLY RETIRED MAN CLIMB ON11 KV GIRDER POLE AT THAT TIME HE WAS SUDDENLY FALL DOWN ON GROUND  AND AFTER SOME TIME (APPROXIMATE 2 HRS) HE IS DIED.  -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
249 AMRELI SHRI RANJITBHAI BHARATBHAI KHUMAN(E.A.),ZANZARIYA 31-05-14 NFHD THE ACCIDENT WAS OCCURRED WHEN  VICTIM WAS ATTENDING 11 KV ADIPUR AG FEEDER WITH OTHER TWO LINE STAFF & LINE PETROLLING CARRIED OUT IN FAULTY SECTION OF 11 KV ADIPUR AG FEEDER IN AG AREA OF VILLAGE ZANZARIYA ON ROAD ZANZARIYA KAGADADI JUNA MARAG., NEAR TC OF MAGANBHAI KURJIBHAI SATASIYA THE CAUSE OF ACCIDENT IS SUSPECTED AS STATEMENT OF VICTIM & STATEMENT OF OTHER TWO LINE STAFF UNDER PROCESS. -- -- -- VICTIM HIMSELF RESPONSIBLE AND STRICT DISCIPLINARY ACTION TAKEN FOR NEGLEGENCE OF SAFETY RULES AND REGULATION
250 AMRELI 1 BULLOCK OF SHRI JATASHANKAR SHIVLAL CHAV,BABRA 05-06-14 FA WHEN BULLOCK WERE PASSING NEAR THE LT LINE OF MOTIBAPA VALU T/C OF 11 KV CHARAKHA AG FEEDER LINE,  AT THAT TIME  BROKEN LIVE WIRE WAS CONTACTED  WITH BULLOCK. HENCE ONE BULLOCK WAS DEAD ON THE SPOT. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
251 AMRELI SHRI DINESHBHAI BADHABHAI CHAUHAN(E.A.),JANBAI DERDI 12-06-14 NFHD VICTIM WAS WORKING OF 11 KV TAPPING LINE JUMPER. AT THAT TIME DUE TO BEARY WIND, 11 KV FEEDERS CROSSING TOUCH WITH NEARBY WIRE FOR INSTANT AND VICTIM GOT SHOCK AND FALL DON'N FROM THE POLE. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
252 AMRELI 1 COW OF SHRI BAGHABHAI BHAGVANBHAI LAKHNOTRA,BARPATOLI 13-06-14 FA RAIN IS FALLING IN NIGHT AND IN MORNING ,A COW PASSED BETWEEN TWO PSC POLE OF VILLAGE TC. CAME IN CONTACT OF LEAKAGE CURRENT & GOT ELECTROCUTED -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
253 AMRELI 1 COW OF SHRI GHELABHAI NATHABHAI,NABAPARA 15-06-14 FA ACCIDENT OCCURE  LAND IS WET AROUND THE TC LOCATION CENTRE DUE TO RAINY SEASON ,THE COW PASSED NEAR FROM THE TC LOCATION CENTRE CAME IN CONTACT OF EARTH LEAKAGE & GOT ELECTROCUTED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
254 AMRELI 1 COW OF KANCHANBEN DAYABHAI GOHIL,SANAKHADA 15-06-14 FA RAIN IS FALLING IN MORNING AT DUE TO LEAKAGE CURRENT PASSES THROUGH EARTHING. AT THAT TIME COW WAS PASSING UNDER THIS T/C, COME IN CONTACT WITH EARTHING & GOT ELECTROCUTED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
255 AMRELI 1 COW OF SHRI JASUBHAI KESHUBHAI GOHIL,SAMTER 16-06-14 FA DUE TO LEAKAGE CURRENT PASSES THROUGH EARTHING.AT THAT TIME COW WAS PASSING UNDER THIS T/C,COME IN CONTACT WITH EARTHING & BECAUSE OF WET LAND GET ELECTROCUTED AND DIED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
256 AMRELI 1 COW OF SHRI ABHABHAI JETHABHAI BABARIYA,PALADI 16-06-14 FA RAIN IS FALLING IN MORNING , LEAKAGE CURRENT PASSES THROUGH EARTHING FROM JOINT OF OUTGOIN CABLE OF DISTRIBUTION BOX AND LT LINE.AT THAT TIME COW WAS PASSING UNDER THIS T/C,COME IN CONTACT WITH EARTHING & BECAUSE OF WET LAND GET ELECTROCUTED AND DIED.PVC PIPE IS ALREADY PROVIDED WITH EARTHING WIRE -- -- -- DETAILED TC MAINTENANCE CARRIED OUT & DETERIORATED CABLE REPLACED
257 AMRELI 1 BUFFALO OF SHRI CHHAGANBHAI MOHANBHAI DEVANI,SALVA 16-06-14 FA THE ACCIDENT OCCURRED DUE TO LEAKAGE CURRENT OF TC WHEN BUFFALO PASSING NEAR FROM TC.  -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
258 AMRELI VIRABHAI URFE HIRABHAI BECHARBHAI CHOPDA(FH),CHAMARADI
11-07-14 FHOS THE LEAKAGE CURRENT WAS PASSED THROUGH LT POLE EARTHING WIRE.WHEN VIRABHAI URFE HIRABHAI BECHARBHAI CHOPDA AND HIS GRANDSON SAGAR MANJIBHAI SONDARVA PASSING NEAR BY LT POLE OF VILLAGE TC AT THAT TIME SAGAR MANJIBHAI SONDARVA CONTACT WITH EARTHING WIRE OF LT POLE & GOT ELECTROCUTED.. HIRABHAI BECHARBHAI CHOPDA HAS THROWN SAGAR IMMIDIATELY FROM POLE BUT HE GOT ELECTROCUTED & DIED HOWEVER SAGAR MANJIBHAI SONDARVA WAS INJURED AT HAND.  -- -- -- DETAILED LT & TC MAINTENANCE CARRIED OUT
259 AMRELI SAGAR MANJIBHAI SONDARVA,CHAMARADI 11-07-14 NFHOS THE LEAKAGE CURRENT WAS PASSED THROUGH LT POLE EARTHING WIRE.WHEN VIRABHAI URFE HIRABHAI BECHARBHAI CHOPDA AND HIS GRANDSON SAGAR MANJIBHAI SONDARVA PASSING NEAR BY LT POLE OF VILLAGE TC AT THAT TIME SAGAR MANJIBHAI SONDARVA CONTACT WITH EARTHING WIRE OF LT POLE & GOT ELECTROCUTED.. HIRABHAI BECHARBHAI CHOPDA HAS THROWN SAGAR IMMIDIATELY FROM POLE BUT HE GOT ELECTROCUTED & DIED HOWEVER SAGAR MANJIBHAI SONDARVA WAS INJURED AT HAND.  -- -- -- DETAILED LT & TC MAINTENANCE CARRIED OUT
260 AMRELI ASLAMBHAI ABDULBHAI PATHAN,VIJAPADI 18-07-14 FHOS WHEN VICTIM CLIMB ON TRUCK& CAME IN CONTACT WITH LIVE WIRE -- -- -- DETAILED HT MAINTENANCE CARRIED OUT AND GROUND CLEARANCE MADE AS PER NORMS
261 AMRELI DHARMESHKUMAR VILASBHAI MAKVANA,VEKARIYAPARA 20-07-14 FHOS VICTIM WAS COLLECTING CLOTHES WITH HIS MOTHER FROM TERRACE WITH THE USE OF METAL ROAD WHICH COMES IN DIRECT CONTACT WITH LIVE 11 KV LINE ONE WIRE PASSING BEHIND HIS HOUSE AND OVER HIS TERRACE WALL. VERTICAL DISTANCE BETWEEN WIRE AND ROOF OF HOUSE IS ABOUT 7.5 FEET.  -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
262 AMRELI 1 BUFFALO OF SHRI BAGHABHAI DANABHAI CHAUHAN,DEVALIYA 26-07-14 FA DUE TO LEAKAGE CURRENT OF TC CENTER EARTHING ACCIDENT OCCURS -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
263 AMRELI 1 WILD ANIMAL LEOPARD FEMALE,GADHIYA 30-07-14 FA ON DATE 30.7.2014, FARMER SHRI KANUBHAI GHOHABHAI VALA GOESTO HIS FARM AT 08:00AM AND AROUND 12:00PM HE SAW AN DIEDFEMALE LEOPARD ON THE TRANSFORMER CENTER WHICH IS ERECTED ONPSC POLE IN HIS FARM FOR AGRICULTURE CONNECTION UNDER 11KV
MADHUPUR AG FEEDER. AN FEMALE LEOPARD GOES TO ON THETRANSFORMER CENTER ON PSC POLE FOR ANY REASON & CONTACT WITHJUMPER ON HT SIDE ABOVE TRANSFORMER CENTER & GET ELECTRICSHOCK & DIED ON THE SPOT.
-- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
264 AMRELI 1 COW OF KALUBHAI KANABHAI BERANI,LALAKA 31-07-14 FA WHEN COW OF MR. KALUBHAI KANABHAI BERANI PASSING FROM LT POLE OF LALKA VILLAGE TC AT THAT TIME LEAKAGE CURRENT PASSING TO EARTH AND COW GOT SHOCKED AND COW DIED AT SPOT AS PER INFORMED BY BHARATBHAI KALUBHAI BERANI( SON OF KALUBHAI BERANI). AFTER  PLACE VERIFICATION IT WAS FOUND THAT PVC EARTHING PIPE IS PROPERLY INSTALLED AND FOUND THERE IS NO MARKING OFELECTRIC SHOCK  ON COW. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
265 AMRELI SHRI MADHUBHAI BHIKHABHAI BHAYANI(LM),SARAMBHADA 05-08-14 NFHD A NON FATAL ELECTRICAL ACCIDENT ACCOUR TO M B BHAYANI – LINEMAN RURAL SDN – AMRELI. SARAMBHDA AG FEEDER WAS IN PERMANENT FAULT. VICTIME GONE TO REPAIR DODP NEAR TC OF CHATUR VALLABH NASIT OF VILLAGE : SARAMBHADA BELEIVING THAT HIS LINE IS IN SARAMBHADA AG FEEDER. BUT , ACTUALLY IT IS A NEW AG TC AND IS FED FROM : MEDI AG FEEDER. DUE TO UN AWARENESS OF POWER IN THIS GROUP, HE CLIMED ON 11 KV LINE OF MEDI AG FEEDER, AND ALSO, NOT UTILISED ANY SAFETY GADGETS AND NOT ACERTAINED ABOUT POWER OFF OR NOT. HENCE GOT ELECTRIC SHOCK FROM LIVE MEDI AG FEEDER. -- -- -- VICTIM HIMSELF RESPONSIBLE AND STRICT DISCIPLINARY ACTION TAKEN FOR NEGLEGENCE OF SAFETY RULES AND REGULATION
266 AMRELI 1 BUFFALLO OF SHRI ANIRUDHDHA DILUBHAI,DHOLAVA 08-08-14 FA THE ACCIDENT OCCURRED DUE TO BUFFALO CAME IN CONTACT OF LIVE LT LINE WIRE. THE LT LINE WIRE WAS BROKEN & FALL DOWN ON LAND & BUFFALO CAME IN CONTACT WITH BROKEN WIRE & GOT ELECTROCUTED -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
267 AMRELI 1 BUFFALLO OF SHRI ANIRUDHDHA DILUBHAI,DHOLAVA 08-08-14 FA THE ACCIDENT OCCURRED DUE TO BUFFALO CAME IN CONTACT OF LIVE LT LINE WIRE. THE LT LINE WIRE WAS BROKEN & FALL DOWN ON LAND & BUFFALO CAME IN CONTACT WITH BROKEN WIRE & GOT ELECTROCUTED -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
268 AMRELI RAJESHBHAI JAGUBHAI BAMBHANIYA,JAFRABAD
16-08-14 FHOS THE ACCIDENT IS OCCURRED DUE TO VICTIM CAME IN CONTACT OF LEAKAGE CURRENT. THE V CROSS ARM OF LOCATION NO:JFD/JFR/CITY/084/016 IS BROKEN & B PHASE CONDUCTOR  IS TOUCH TO PIN ROD OF Y PHASE RESULTING FLOW OF LEAKAGE POWER THROUGH TRANSFORMER GI WIRE.THE VICTIM GO TO POLE FOR URINAL PURPOSE GET ELECTROCUTED.  -- -- -- DETAILED HT MAINTENANCE CARRIED OUT AND GROUND CLEARANCE MADE AS PER NORMS AND STRICT DISCIPLINARY ACTION AGAINST DEFAULTER
269 AMRELI SAGARBHAI KISHANBHAI SOLANKI,JAFRABAD 16-08-14 FHOS THE ACCIDENT IS OCCURRED DUE TO VICTIM CAME IN CONTACT OF LEAKAGE CURRENT. THE V CROSS ARM OF LOCATION NO:JFD/JFR/CITY/084/016 IS BROKEN & B PHASE CONDUCTOR  IS TOUCH TO PIN ROD OF Y PHASE RESULTING FLOW OF LEAKAGE POWER THROUGH TRANSFORMER GI WIRE.THE VICTIM GO TO POLE FOR URINAL PURPOSE GET ELECTROCUTED.  -- -- -- DETAILED HT MAINTENANCE CARRIED OUT AND GROUND CLEARANCE MADE AS PER NORMS AND STRICT DISCIPLINARY ACTION AGAINST DEFAULTER
270 AMRELI 1 BULLOCK OF SHRI SAMATBHAI ARJANBHAI SOLANKI,SOKHADA 26-08-14 FA LT COUNDUCTOR BROKEN  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
271 AMRELI 1 BULLOCK OF SHRI SAMATBHAI ARJANBHAI SOLANKI,SOKHADA 26-08-14 FA LT COUNDUCTOR BROKEN  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
272 AMRELI 1 BULLOCK OF SHRI ARJANBHAI KALABHAI MAKVANA,PALADI 31-08-14 FA ON DT.31.8.14, APP.3:00 PM ,A FATAL ACCIDENT OCCURRED TO 1 BULLOCK  OF SHRI ARAJANBHAI KALABHAI MAKAVANA AT VILLAGE PALADI  UNDER UNA.1S/DN.    A DTC FOR POWER TO VILLAGE AREA ON OLAVAN  TO PALADI ROAD IS EXIST ON 11 KV KESARIYA  JGY FEEDER. ACCIDENT OCCUR DUE TO RAIN FLOW WHEN LEAKAGE CURRENT FLOWS THROUGH  TRANSFORMER BODY EARTHLING WIRE  TO GROUND SAME TIME BULLOCK CAME IN CONTACT WITH VILLAGE TRANSFORMER BODY EARTHING WIRE HENCE CAUSE FETAL ANIMAL ACCIDENT OF BULLOCK WAS OCCURRED .  -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
273 AMRELI 1 BUFFALO OF SHRI VASHRAMBHAI BOGHABHAI BATADA,CHHATADIYA 31-08-14 FA ACCIDENT WAS OCCURRED IN HT POLE OF 11 KV CHHATADIYA AG LOCATED IN OWNER PRIMISES.DURING SITE INSPECTION V-CROSSARM,D-CLAMP,TOP CLAMP ,PIN INSULATER AND WIRING OF POLE WAS FOUND OK.EARTHING WIRE CONNECTED TO FABRICATION WAS RUNNING UPTO FIRST STEP OF POLE.POLE BOTTOM SIDE AND SURROUNDIG WAS CHECKED WHILE FEEDER IN  ON POSITION AND NO LEACKAGE CURRENT FOUND .ALSO THERE IS NO TRIPPING IN THIS FEEDER DURING ACCIDENT TIME PERIOD GIVEN BY OWNER .SO ACCIDENT IS NOT OCCURED DUE TO LEACKAGE CURRENT IN HT POLE OF 11 CHHATADIYA AG. -- -- -- DETAILED HT MAINTENANCE CARRIED OUT
274 AMRELI 1 COW OF SHRI DINESHBHAI HAMIRBHAI,JAGATIYA
03-08-14 FA WHEN 1 NOS. OF COW & 1 NOS OF CALF WERE PASSING NEAR THE GRAM PANCHAYAT WATER WORKS TRANSFORMER, THERE WAS TOO MUCH WATER SURROUNDING THE TRANSFORMER CENTRE LAND DUE TO THE HEAVY RAIN. ACCORDING TO EYE WITNESS THERE MIGHT BE LEAKAGE EARTHLING’S CURRENT FLOW THROUGH THE WATER, MEANWHILE THAT TIME TWO NOS. OF COWS CAME CONTACT WITH WATER NEAR TRANSFORMER CENTRE AND GOT SHOCKED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
275 AMRELI 1 CALF OD SHRI KHATUBHAI VIRABHAI,JAGATIYA 03-08-14 FA WHEN 1 NOS. OF COW & 1 NOS OF CALF WERE PASSING NEAR THE GRAM PANCHAYAT WATER WORKS TRANSFORMER, THERE WAS TOO MUCH WATER SURROUNDING THE TRANSFORMER CENTRE LAND DUE TO THE HEAVY RAIN. ACCORDING TO EYE WITNESS THERE MIGHT BE LEAKAGE EARTHLING’S CURRENT FLOW THROUGH THE WATER, MEANWHILE THAT TIME TWO NOS. OF COWS CAME CONTACT WITH WATER NEAR TRANSFORMER CENTRE AND GOT SHOCKED & DIED AT SPOT. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
276 AMRELI 1 COW OF SHRI RAMSINHBHAI SIDIBHAI JADAV,KODINAR 10-09-14 FA ACCIDENT OCCURE DUE TO SNAPPING OF 11 KV CONDUCTOR AT THAT TIME ONE COW CAME IN CONTACT WITH WIRE HENCE FATAL ANIMAL ACCIDENT OCCURE -- -- -- DETAILED HT MAINTENANCE CARRIED OUT
277 AMRELI 1 BULLOCK OF SONABEN VIRABHAI CHARANIYA,NALIYA MANDVA 10-09-14 FA THE LT LIVE CONDUCTOR WAS BROKEN & AT THE SAME TIME BULLOCK PASS ON CONDUCTOR RESULTING OCCURRENCE OF FATAL ANIMAL ACCIDENT. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
278 AMRELI 1 BUFFALO OF SHRI KADUBHAI URFE BHIKHUBHAI MALABHAI DODIYA,KODINAR 11-09-14 FA ACCIDENT OCCURE DUE TO LEAKAGE EARTH CURRENT OF  JALARAM VALU TC OF 11 KV KODINAR CT FEEDER HENCE FATAL ANIMAL ACCIDENT OCCURE -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
279 AMRELI 1 BUFFALLO OD SHRI BAGHABHAI RAMBHAI KATARIYA,GHANDALA 11-09-14 FA ACCIDENT AT LT CONDUCTOR TOUCH WITH  C CLAMP THE LEAKAGE CURRENT FLOW IN WET SOIL NEAR THE PSC POLE AND WHEN THE BUFFELLO PASS NEAR THIS POLE DUE TO LEAKAGE CURRENT FATAL ANIMAL ACCIDENT OCCURE. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
280 AMRELI RAKESHBHAI JITUBHAI BALAR,SAKHPUR 15-09-14 FHOS THE VICTIM WAS WORKED AT VALJIBHAI BHATTUBHAI  HOUSE GALLERY & FITTING IRON PIPE AT GALLERY FOR PERSONAL USE .AT THE TIME OF WORK  THE PIPE TOUCH TO 11 KV LINE PASSES NEAR THROUGH GALLERY  HENCE VICTIM GOT ELECTROCUTED & FATAL ACCIDENT OCCURED  -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
281 AMRELI JAYANTIBHAI BACHUBHAI THAVANI(ALM),SARASIYA 15-09-14 FHD THE AG SECTION OF 11 KV KHOKHARA FEEDER WAS IN FAULT HENCE VICTIM WAS CLIMB ON TRANSFORMER CENTER AFTER SECTIONALIZED THE D.O. FUSE TO CHECK WHETHER IT IS FAILED OR NOT? AFTER CHECKING OF TRANSFORMER, WHILE CLIMB DOWN HE FELL ON GROUND & FATAL ACCIDENT OCCURRED MIGHT BE DUE TO HEAD INJURY. AS NO EVIDENCE OF ELECTRICAL FATAL ACCIDENT FOUND FROM SITE. -- -- -- LETTER TO POLICE STATION TO LODGE FIR AGAINST FARM LABOUR BECAUSE OF UNAUTHORISE EXTENSIN OF NEUTRAL WIRE FROM ACCIDNET LOCATION
282 AMRELI 1 BUFFALO OF SHRI JAYSUKHBHAI SHAMBHUBHAI PANSURIYA,CHALALA 24-09-14 FA ON DATE 24.9.2014, AROUND 08:20AM A BUFFALO OF OWNER SHRI JAYSUKHBHAI SHAMBHUBHAI PANSURIYA PASS IN HIS FARM AT CHALALA & AT THAT TIME A BUFFALO TOUCH TO CABLE OF PRIVATE DIS-CABLE OPERATOR & AT THAT TIME THIS CABLE TOUCH TO LIVE 11KV LINE WIRE OF 11KV GAYATRI CITY URBAN FEEDER. SO THIS CABLE CHARGED & FIRED.
A BUFFALO CONTACT WITH THIS CABLE & GOT ELECTRIC SHOCK & DIED ON THE SPOT.
-- -- -- UN AUTHORISE HANGING OF TV CABLE,HENCE NOTICE ISUUED TO CABLE OPERATOR FOR UNAUTHORISE USE OF ELECTRIC POLE
283 SNRC Kum. Aartiben Jagdishbhai Thakor 26-04-14 NFHOS An electrical non fatal accident occur to above mention victim was contact with snapping of conductor due to pin insulator fired of 11 KV Dhama AG feeder emanating from 66 KV Dhama S/S Report yet not received NA NA Replaced Pin Insulator 
284 SNRC Shri Diwanbhai Humabhai 04-05-14 FHOS During construction work of bridge on road, victim came in direct contact with live conductor of 11 KV Ganjela JGY through an IRON ROD about 5 Mtr long in his hand and got electrocuted.  Report yet not received NA NA Victim Fault
285 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 05-06-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
286 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 05-06-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
287 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
288 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
289 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
290 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
291 SNRC Cow of Shri Janakbhai Ajani 18-Jun-14 FA Accident occurred to cow due to DTC meter cable cracked and might came in contact with DTC DP structure and due to raining leakage current flow through DP structure and cow might came in contact of DP structure and got electric shock Report yet not received NA NA Maint Done
292 SNRC Buffalo of Shri Chandu Thakarshi  19-Jun-14 FA Two nos. of HT pole & line Of 11 KV Fuleshwar feeder was broken by unknown person and this buffallow came in contact of live wire and get electrocuted. Report yet not received NA NA FIR Laundged & Rectification Done
293 SNRC  Buffalo of Shri Mavji Govind 19-Jun-14 FA Two nos. of HT pole & line Of 11 KV Fuleshwar feeder was broken by unknown person and this buffallow came in contact of live wire and get electrocuted. Report yet not received NA NA FIR Laundged & Rectification Done
294 SNRC  Buffalo of  Shri Ramnikbhai Himatbhai 19-Jun-14 FA Two nos. of HT pole & line Of 11 KV Fuleshwar feeder was broken by unknown person and this buffallow came in contact of live wire and get electrocuted. Report yet not received NA NA FIR Laundged & Rectification Done
295 SNRC Buffalo of Shri Popatbhai Saktabhai 1-Jul-14 FA An elctrical accident occurred to one buffalo due to DTC meter cable cracked & might came in contact with DTC DP Structure & due to raining leakage current flow through dp Strucutre & victim might came in contact with DP Strucutue and get electroculated.  Report yet not received NA NA Maint Done
296 SNRC Shri Maheshbhai Bolabhai 2-Jul-14 FHOS Accident occurred at 11KV Tavi JGY Feeder. Unauthorized construction was done by Gabhubhai Hirabhai sabhad and recently slab work was completed before @ 3 days. Victim was on the slab with other 2(Two) persons and he directly came in contact with the side phase of 11KV Tavi JGY feeder which was crossing at 5 Feet height from the slab and as a result accident occurred. As the construction is unauthorized below existing 11KV Tavi JGY, PGVCL is not guilty for the said accident. Report yet not received NA NA Victim Fault. As per party's application line shifting work done after payment
297 SNRC Cow of Shri Sureshbhai Khodabhai 10-Jul-14 FA LT conductor snapped of sejakpar village transformer and cow came in contact with this live snapped conductor and got electrocuted Report yet not received NA NA Maint Done
298 SNRC Shri Vinubhai M Baroliya 11-Jul-14 NFHD When victim called R M patel-ALM to take line clear of 11 KV Samadhiyala JGY feeder he sent SMS to 66 KV Vinchhiya SS for line clear at 14.36 Hrs. At 14.40 Hrs he orally talked with SBO and he informed him that the braker was reak out of 11 KV Samadhiyala JGy feeder so he informed to victim. When vicitm climbed on PSC pole of  11 KV Samadhiyala JGy feeder he experinced an electric shock and put down on ground.Meanwhile SBO has sent SMS for line clear taken to R M Patel-ALM mobile at 14.46 Hrs.  Report yet not received NA NA CS issued to Victim & Supervisor
299 SNRC Shri Manubhai Butabhai 15-Jul-14 FHOS As per information received from news paper Divya Bhaskar on dtd. 20.7.14, Victim was unauthorizedly built roof under 11 KV line of Somasar AG feeder meanwhile he throw iron wire on the roof and kept one side of il in his hand so it touched the live conductor of 11 KV Somasar AG feeder passing over the roof and live current may passed through this wire to the body of the victim and he experinced an electric shock. Report yet not received NA NA Victim Fault
300 SNRC Shri A G Solanki-EA 15-Jul-14 NFHD THE VICTIM SHREE  ARUNBHAI G SOLANKI WAS GOING TO ATTEND LTG COMPLAIN OF SHRI BHIMABHAI KEHABHAI VILL CHUDA AT MAFTIYAPARA WITH LINE INSPETOR SHRI KS PONDOR , WHILE ATTENDING THE SAID  LTG COMPLAIN VICTIM CLIMB ED  ON LT  PSC POLE BUT DUE TO RAINY ENVIRNMENT/CLIMATE HIS LEG WAS  SLIPPED  AND  HE WAS SLIPDOWN ON EARTH. DUE TO THIS REASON THIS MECH. ACCIDENT OCCURRED. NOTED THAT WHILE ATTENDING THE SAID COMPLAIN VICTIM WAS NOT USED SAFETY INSTRUMENT LIKE HELMET,GOOMBOOT,AND SAFETY BELT ETC….. Report yet not received NA NA CS issued to Supervisor & Warning issued to victim
301 SNRC A buffalo of Shri Bhagvanbhai Laxmanbhai 17-Jul-14 FA One jumper of LT line of village TC was loose and touched to the PSC pole earthing wire and leakage passes through GI earthing wire and current passed through body of buffalo. Accident message received from Sayla police station as on dtd.5.8.14. Report yet not received NA NA Maint Done
302 SNRC A HE Buffalo of Shri Vaghabhai Kamabhai 17-Jul-14 FA A HE buffalo touched to the GI earthing wire of village TC and leakage passed through GI earthing wire and got electric shock. Accident information received from Karadi Sarpanch. Report yet not received NA NA Maint Done
303 SNRC Cow of Shri Malabhai Hindubhai 17-Jul-14 FA Due to Heavy rain, poles of 11 KV Motabhadla Ag feeder  having Loc No. SUD/NAG/346-347-348 were broken and also other 3 Nos adjoining poles were broken and cow was at that time grazing under this location and came in contact with live wire and got electric shock. Report yet not received NA NA Maint Done
304 SNRC Shri Dineshbhai Bavalbhai 17-Jul-14 NFHOS 11 KV Tavi feeder was tripped at 18.25 PM. And at that time victim was climed on TC centre for binding of jumper of Ht line, meanwhile feeder charged at 18.35 PM and victim got shocked and fall down on the earth.  Report yet not received NA NA Victim Fault
305 SNRC Shri Kadvabhai Premjibhai 19-Jul-14 FA When buffalo was passing near guy wire of Kadva Premji AG TC, 11 KV DO broken and touched to angle and due to this return power from TC passing through PSC pole of TC centre and its guy and got electric shock on neck and died.   Report yet not received NA NA Maint Done
306 SNRC Shri Valjibhai Ranchhodbhai 24-Jul-14 FA Due to cyclone, street light fixture fixed on round pole got tilted and metal part of fixture came in contact of round pole. Report yet not received NA NA Municipality Fault. Notice Issued
307 SNRC Shri Bharatbhai Muljibhai  30-Jul-14 NFHD To attend 11 KV Vagadiya AG feeder which was in fault. During petrolling jumper of main line gang switch of Khakhrali village AG was found burnt. During rejumpering work on DP structure of gang switch he experinced  the momentary electric jerk on his hand. Shri B D Patel-ALM helped the victim to come down from DP structure   Report yet not received NA NA CS issued to Supervisor. Warning issued to DE & Victim
308 SNRC Shri Babubhai Raysangbhai 30-Jul-14 NFHOS A NFH accident occurred to outsider Shri BABUBHAI RAISANGBHAI SURELA ON DT15.07.14 00:05 HRS LOCATION UNDER SCSD-2,REASON OF THE ACCIDENT IS THAT HE HIMSELF CLIMB ON HT 4 POLE STRUCTURE  OF 11 KV JINTAN FEEDER & GOT ELECTRIC SHOCK Report yet not received NA NA Victim Fault
309 SNRC Smt Lilaben Rajubhai 30-Jul-14 NFHOS A non fatal electrical accident ocurred due to the connductor of 11kv Kankeshver Ag feeder slipped from shackle point, at that time victim came in contact with the live conductor and got electric shock. Report yet not received NA NA Manit Done. Overloaded Feeder. Load transferred to other feeder
310 SNRC Cow of Shri Vashrambhai Mayabhai 2-Aug-14 FA Due to strret light fixture choke short, aleakage current flow and cow passes near this pole nad got electric shock.  Report yet not received NA NA Municipality Fault. Notice Issued
311 SNRC Buffalo of Shri Kamabhai Vaghabhai 9-Aug-14 FA Buffalo was passing near manharpark society tc of 11 KV Jolly Urban feeder and there was a rain and wet atmosphere on dt.19.7.14, it came in contact of earthing wire and got electric shock.  Report yet not received NA NA SCN issued to SDO
312 SNRC Cow of Shri raiyabhai Masabhai 14-Aug-14 FA Fatal animal accident occurred due to short street light fixture Report yet not received NA NA Municipality Fault. Notice Issued
313 SNRC Buffalo of Shri Kamabhai Vaghabhai 30-Aug-14 FA Buffalo was passing near manharpark society tc of 11 KV Jolly Urban feeder and there was a rain and wet atmosphere on dt.30.7.14, it came in contact of earthing wire and got electric shock.  Report yet not received NA NA SCN issued to SDO
314 SNRC An OX of Shri Vajubhai Ranchhodbhai 2-Sep-14 FA Near TC DP leakage current passes through earth wire due to rain and current passed through OX body Report yet not received NA NA Maint Done
315 SNRC A buffalo of Shri Laghubhai Aalbhai 9-Sep-14 FA Near TC DP leakage current passes through earth wire due to rains and water logging near TC pole and at that time momentary leakage current passes through body of buffalo and got electrocuted. Report yet not received NA NA Maint Done