Performa – SoP 002: Action taken report for safety measures complied for the accidents occurred
Sr Circle Location of
Accident and
details of the victim
Date of
occurrence
Type of
Accident
Cause of Accident Findings
of CEI / EI / AEI
Remedies suggested
by CEI /EI / AEI in
various cases
Whether the
remedy
suggested
is complied
Action taken to
avoid recurrence
of such Accident
1 RCC Kubaliyapara, Chunarwada Chowke,Rajkot,                                Shivkumar Shambhubhai Chudasma 09.4.2014 NFHOS While Victim was siting on muffing of 11KV Thorala Feeder pole no.DUD/THO/079/L-003/DT.25 at that time suddenly squerrel come in contact of DO fuse of near by another 5KVA DT and due to short circuted current was passed through existing running earth wire on line and victim got shock. Report yet not received NA NA Proper Maintenance Carried out
2 RCC Raiyagam, Nr Sitaram Floor mill, Nr Parmar Nivas,Raiya Road, Rajkot,          Cow of Shri. Tihabhai Bharatbhai Labariya 21.04.2014 FA Because of continuous erosion of insulation of single phase service wire by touching the guy wire in vicinity, it has resulting in open & as cyclonic wind was observed on the evening of 20-4-2014, guy wire has come in contact with open phase & leakage current from service phase to guy to ground through cow body passed resulted in electric shock. Report yet not received NA NA 1. Replacement of deteriorated service line 2. Tightening of loose guy.
3 RCC B/H Meera Udhyog 4 x 6 Corner, in wokla ne Tecnocast,Rajkot,                    Sanjaybhai Devrajbhai Huletiya 12.05.2014 FHOS Due to heavy wind pressure and rain,a tree branches which were nearer to LT Line broken and fallen on AG LT line conductor and due to that on conductor of AG LT Line was broken and fallen on ground (West Land-Wokla) on next day ,victim may come in contact with broken Live AG LT Line conductor during collecting industrial west and he got electric shock. Report yet not received NA NA Open conductor replaced by providing AB cable and maintenance of LT Line is carried out.
4 RCC Kailash Park, Morbi Road,Rajkot,               Cow of Sri Bagvanji Bachubhai Matia  16.06.2014 FA  At LT pole No 021 piece of 1 feet (approx) of remaining portion of removed “lungar” wire was hanging and live conductor of this wire come in touch with guarding wire so leakage current pass to next pole through guarding wire. At this next pole through earthing wire leakage current passed to earth and surrounding land of the pole get electrically charged ,so as soon as the cow came in the vicinity of the pole get electric shock due to step voltage and met fatal accident.  Report yet not received NA NA 1. One should not fix un authorized "Lunger".  2.  LT line maintenance.  
5 RCC Ganshyamnagar Main Road, Opp Swastik School,Rajkot                                          Cow of Sri Hareshbhai Kanabhai Dholakiya 10.07.2014 FA  On date 10-07-14 accident took place near HT line girder pole No 032 in which leakage current was found passing through it. Guarding to the HT pole provided continuous from previous ploes at which HT and LT line erected on comman poles. On investigation and by switching “OFF” power of near by T/c leakage current in HT pole stopped and then on switching “ON” power of the T/c leakage current not fount in HT pole .So thus it concluded due windy and rainy condition earth wire of HT-LT line common pole may touch live part of LT line live wire and caused momentary leakage current in earth wire and as 11 KV guarding  fitted on this common pole leakage  current passed  in guarding wire and through it in HT line pole at which accident took place. So as soon as cow comes in vicinity of the pole got electric shock and met fatal accident. Report yet not received NA NA 1) Proper fitting of earth wire 2) Providing of A.B. cable in LT line
6 RCC B/H Rajkamal Petrol Pum, Punitnagar Main Road,Rajkot,                                           Cow of Surabhai Sagrambhai Chavda 13.07.2014 FA On date 13-07-14 Accident took place near T/C center PUN/SUP/039/DT-31. As message of accident received by the fault center line staff and Deputy Engineer immediately visited the site. At site a cow found laying dead near transformer center. At time of visit it was found that no any leakage current passing through T/C earthing, pole or in any near by LT pole. It was rainy and windy atmosphere at time of accident. So it concluded that due to momentary touching of Phase wire with neutral wire leakage current may passed in T/C earthing. So as soon as Cow comes in vicinity of T/C may got electric shock and met fatal accident. Report yet not received NA NA T/C earthing reactive with PVC rigid pipe.
7 RCC Velnathpara,Morbi Road,Rajkot,          Artiben Vijaybhai  Sitapara 31.07.2014 NFHOS Accident took place at LT line pole at which street light fixture fitted and was short-circuited so leakage current was passing through PSC pole .As soon as victim came in contact with the pole got electric shock and met with non fatal accident .Inspection of site carried out in present of Asst Electrical inspector and R.M.C. staff  Report yet not received NA NA informed to Dy. Engi. East division RMC, about this lacuna and for necessary action.
8 RCC Manharpur-1, Jamnagar Road, Rajkot, Bhupatbhai Chakubhai Parajiya 03.08.2014 FHOS Accident took place while victim cutting the tree branches by “Dhariyu” a metal tree cutting tool in front of his house while that it come in contact with dish cable wire which was hanging by metal G.I. wire and end of this metal wire was fitted at LT line PSC pole at which illegal streetlight fixture was fitted which was short circuited so leakage current was passing through it to metal wire of disc cable  so as soon as victim’s metal tree cutting tool (“dhariyu”) come in contact this wire got electric shock and met with fatal accident  Report yet not received NA NA Removal of disc cable having iron wire and short circuited st. light fixture.
9 RCC Shakti Society, Navagam,Rajkot,      Amitbhai Devjibhai Rathod 14.08.2014 NFHOS Accident took place while victim throw away old telephone wire which was hanging across the street near the transformer centre at that time it touched  the DO fuse  of transformer  and got electric shock and met Non fatal accident  Report yet not received NA NA Write letter to telephone depat. For necessary maintenance and precaution in future.
10 RCC Nana Mava Main Road, Laxminagar road Corner,Rajkot,                                       Samir Salimbhai Dodhiya 18.09.2014 NFHD Victim and other line staff were at the site for stringing of broken guard wire from existing pole. Victim was fall down from tower ladder due to slip of leg and fall down on road. So injury occurred in head Report yet not received NA NA All the line staffs are instructed to carry out work under the supervision of competent staff and by using all safety equipment.
11 RCC Ganteshwar Village, Nr. SRP Campus, Jamnagar Road, Rajkot,                         Kiran Vaghsinh Bariya  29.09.2014 NFHOS Accident took place while victims were Dismentalling 11KV GO Switch from idle (without 11KV line) PSC pole of 11KV Raiyadhar WW feeder. They were climbing down after removing GO Switch from the pole at that time somehow dish cable which was hanged on same idle pole and across the 132KV D/C Nyara-Vajdi and Nyara-Vikram line come in induction zone of live 132KV Nyara-Vajdi line. Hence, both victims got electric shock and met with Non Fatal accident Report yet not received NA NA 1) Removal of Dish Cable      2) one should be careful while working on line and not start work in absent of supervisor
12 RCC Ganteshwar Village, Nr. SRP Campus, Jamnagar Road, Rajkot,                       Babrik Chanabhai Baria 29.09.2014 NFHOS Accident took place while victims were Dismentalling 11KV GO Switch from idle (without 11KV line) PSC pole of 11KV Raiyadhar WW feeder. They were climbing down after removing GO Switch from the pole at that time somehow dish cable which was hanged on same idle pole and across the 132KV D/C Nyara-Vajdi and Nyara-Vikram line come in induction zone of live 132KV Nyara-Vajdi line. Hence, both victims got electric shock and met with Non Fatal accident Report yet not received NA NA 1) Removal of Dish Cable      2) one should be careful while working on line and not start work in absent of supervisor
13 RRC PANELI & Sumit bhai Babubhai Degama 23.04.14 FHOS Victim went on terrace to catch pigeon on his neighbor’s terrace from his terrace. He jumped over from small parapet between  his house and neighbor’s house. While crossing the small parapet he loosen his balance. Though no any protection wall on terrace of his neighbor, he caught live wire to avoid him self to fallen down from balcony to “Vokala”.  Resultantly he caught  11 kV live wire situated 1 feet away from his balcony and approximately 4 feet away from his wall. Thus he got an electric shock and expired.
       
14 RRC MOTI VAVDI & BUFFALOW  12.05.14 FA On Dt.- 12.5.14 There was heavy wind pressure. Due to this disc insulator got damaged  and conductor was broken of 11 kv Mahadev JGY feeder of DT-06. Buffalow and a calf was fasten under the 11 kv line by owner.. When the conductor snapped it directly fallen down on the buffalow standing under the line and got an electric shock, At the same time calf which was fasten near the buffalow came in contact with snapped conductor and got an electric shocked and both died.        
15 RRC MOTI VAVDI & A CALF OF SHRI KARSHANBHAI AALABHAI MORI  12.05.14 FA On Dt.- 12.5.14 There was heavy wind pressure. Due to this disc insulator got damaged  and conductor was broken of 11 kv Mahadev JGY feeder of DT-06. Buffalow and a calf was fasten under the 11 kv line by owner.. When the conductor snapped it directly fallen down on the buffalow standing under the line and got an electric shock, At the same time calf which was fasten near the buffalow came in contact with snapped conductor and got an electric shocked and both died.        
16 RRC RAYDI & SHRI DILIPBHAI JASMATBHAI AKBARI 04.05.14 NFHD DEPARTMENTAL NONFATAL MECHANICAL ACCIDENT OCCURRED TO SHRI D.J.AKBARI (ELECT. ASST.) AT VILLAGE RAYDI ON DT.;-4.5.14 AT 04:00 PM. 11 KV TARAVADA JGY FEEDER WAS ON FAULT AT 3:15 P.M. D.J.AKBARI WAS INFORMED BY 66KV RAYDI SS OPERATOR AS WELL AS CONSUMER FOR NOT GETTING POWER SUPPLY FROM 11 KV TARAVADA JGY FEEDER. SO HE HAS TAKEN LINE CLEAR FROM HIS MOBILE OF 11 KV TARAVADA JGY FOR JUMPERING WORK AT LOCATION NO.- RYD/TRD/007 AFTER THAT HE CLIMBED ON THAT PSC POLE DURING THIS PEROID HE LOST HIS BODY BALANCE FALLEN DOWN FROM THE TOP OF THE POE TO THEW GROUND AND THIS DEPT. NNON FATAL ACCIEDENT OCCURED.        
17 RRC Chavandi & 1 NOS OF BUFFALO OF Shri. Jetabhai Babubhai Devipujak 17.05.14 FA Animal fatal accident occurred to a 1 buffalo & 2 cow at village chanvandi ag area. One  Y phase HT Line conductor was broken from disc anchor at ag transfromer location no NVG/POL/142/R064/DT65 when one buffalo & two cow passes near this snapped 11 kv conductor they all came in contact with this live wire and got electrocuted        
18 RRC Chavandi & 1 COW OF Shri. Mahavirsinh Amarsang Chauhan
17.05.14 FA Animal fatal accident occurred to a 1 buffalo & 2 cow at village chanvandi ag area. One  Y phase HT Line conductor was broken from disc anchor at ag transfromer location no NVG/POL/142/R064/DT65 when one buffalo & two cow passes near this snapped 11 kv conductor they all came in contact with this live wire and got electrocuted        
19 RRC Chavandi & 1 COW OF Shri. Natubha Agarsang Chauhan 17.05.14 FA Animal fatal accident occurred to a 1 buffalo & 2 cow at village chanvandi ag area. One  Y phase HT Line conductor was broken from disc anchor at ag transfromer location no NVG/POL/142/R064/DT65 when one buffalo & two cow passes near this snapped 11 kv conductor they all came in contact with this live wire and got electrocuted        
20 RRC PATYADI & SHRI R.K.GORWADIYA(ELECT. ASST.) 27.05.14 NFHD ON DT:- 27.5.14 ACCIDENT OCCURRED ON AG TRANSFORMER OF PATYADI AG AREA OF 11KB AMBALIYADA AG FEEDER. FROM THE SITE SITUATION AND STATEMENT OF 1ST SEEING MR. R.K.GORWADIYA IS DOING TRANSFORMER REPAIRING WORK ON TC LOCATION NO.;-KOL/AMB/048/R118/DT41. DURING THE BINDING WORK OF JUMPER OF 11 KV SIDE SUDDENDLY HE GOT SHOCK AND SHOUTED LOUDLY AND FALLEN DOWN ON DO ANGLE.ON DT.-27.5.14 LINE CLEAR OF 11KV AMBALYADA AG WAS TAKEN BY ALM SHRI. G.J.JADEJA TO ATTEND COMPLAINT.11KV TAPPING AB SWTCH WAS ALSO CUT FOR MORE PROTECTION AND ALSO LINE WAS DISCHARGE.LINE CLEAR WAS TAKEN AT 7:00 PM AND 1 LOCATION WAS ALSO ATTENDED BUT WHEN LINE WORK OF 2 ND LOACTION WAS IN PROGRESS AROUND 07:30 PM SUDENDLY POWER CAME FROM UNKNOWN SOURCE DETAIL INVESTIGATION IS UNDER PROGRESS.         
21 RRC NAVANARANKA & ARVINDBHAI DEVABHAI PARMAR 10.06.14 NFHD WHILE VICTIM WAS DOING REPAIRING WORK AT VILLAGE TC OF NAVANARANKA HE HAD EXPERINCED ELECTRIC SHOCK WHILE REMOVING THE DO FUSE OF THE ABOVE TC WITH THE USE OF PLIER WITHOUT HANDGLOVES AFTER ISOLATING THE LINE BUT WITHOUT DISCHARGING THE LINE.SO GOT ELECTRIC SHOCK.          
22 RRC RAMOD & NANJIBHAI THANABHAI PARGHI 03.06.14 NFHD WHILE VICTIM WAS ATTENDING THE COMPLAINT OF GHABSHYAM MULU AG GROUP TC HE CLIMBED ON TC AFTER TAKING THE HANDTRIP FROM THE SUBSTATION ON THAT DAY THERE WAS HEAVY WIND PRESSURE AND LIGHTING STROKE.WHILE HE WAS ATTENDING THE SERVICE COMPLAINT LIGHTUNG STROKE  OCCURED NEAR ACCIDENT LOCATION AND VICTIM GOT THREATNED AND FALLEN DOWN FROM TC STRUCTURE AND DEPT. MECHANICAL ACCIDENT OCCURED.        
23 RRC TRAMBA & DIPAKBHAI ISHWARBHAI MAKVANA 23.06.14 NFHD SINCE FEEDER NAMED RAJKOT LODHIKA SANGH SHOWING ONE PHASE DIM, SO VICTIM WAS DOING GROUND PATROLLING OF THE FEEDER AND ALSO LINE CLEAR OF THE FEEDER WAS NOT TAKEN. HOWEVER DUE TO ANY REASON THE VICTIM CLIMBED ON THE FEEDER GANG SWITCH AND CAME IN CONTACT WITH THE LIVE PART OF THE LINE AND GOT ELECTRIC SHOCK AND FALLEN DOWN AND MET WITH NON FATAL ACCIDENT.        
24 RRC AMBARDI & PRAVINBHAI KALUBHAI KAMEJALIYA 05.07.14 NFHOS VICTIM CLIMBED UNAUTHORISED ON TRANSFORMER CENTRE AND TRY TO CLOSE THE D.O.FUSE BY HIS LEFT  HAND AT THE SAME TIME 1-PHASE POWER SUPPLY WAS LIVE ON 11KV NAVAGAM AG FEEDER.SO VICTIM CAME IN CONTACT WITH LIVE UPPER PART OF D.O FUSE AND GOT ELECTRIC SHOCK AND NON-FATAL ACCIDENT OCCURED.        
25 RRC MAHIKA & BUFFALO OF SHRI. DHALABHAI HIRABHAI SIYAL 13.07.14 FA THERE WAS HEAVT RAIN ON DT.:- 13.7.14 AT VILLAGE MAHIKA. THE AREA SURROUNDING THE DHORA VALU TRANSFORMER CENTRE WAS WET AND THERE WAS LEAKAGE CURRENT PASSING THROUGH THE EARTH WIRE. THE BUFFALO PASSES UNDER THAT T/C BETWEEN THE D.P AND CAME IN CONTACT WITH THE EARTH WIRE AND GOT ELECTROCUTED.        
26 RRC MOTADADVA & BHIKHUBHAI POLABHAI CHOTHANI 14.7.14 FHOS As per PAR of SDO Atkot information regarding this accident was received on date 28.07.2014 from police station and police panchnama done on Dt.:-26.7.14.previously eyewitness shown the accident place in KotdaSangani S.Dn & DE Kotda took eyewitness statement at that site and also police panchnama was carried out at that site. Afterwards police panchnama was carried out on new site under Atkot S.Dn area & DE Atkot visited site and taken statement of eyewitness and owner of sighted T/C.As per statement of eyewitness Sh.Dhirubhai Gela Chavda accident was occured due to victim came in contact with HT line on T/C while doing unauthorize work on T/C.But on site visit no avidence or symptoms of accident found on T/C , wire , structure or psc poles and our PGVCL network found healthy. Detail cause of accident is under investigation.        
27 RRC NAVAGAM & BHAVNABEN RAJUBHAI TALSANIYA 04.07.14 FHOS THE SDO MADHAPAR HAD INFORMED SDO KUVADAVA ON DT.:- 4.7.14 AT 7:57 P.M ON HIS MOBILE REGARDING THE OCCURRENCE OF THE ACCIDENT.AS PER THEIR JOINT INVESTIGATION THE ACCIDENT OCCURRED ON THE TERRECE OF THE SUCHIT SHED OF SH. BHARATBHAI GHOGHABHAI MAKVANA WHICH IS ILLEGALLY EXTENDED TO THE ROAD SIDE HENCE THE DISTANCE BETWEEN THE WALL OF THE TERRECE AND THE NEAR BY 11KV KHIJADIYA FEEDER LINE REDUCED TO APPROX. 1.5 FTS ONLY. AS PER THE STATEMENT OF THE EYEWITNESS ON THE ACCIDENT DAY THE VICTIM CLIMBED ON THE TERRECE OF THE SAME PREMISES AND HER "CHUNARI" BLOWN OFF DUE TO THE WIND TOWARDS THE HT LINE AND WHEN SHE TRIED TO COLLECT THE SAME SHE ACCIDENTLY CAME IN LIVE CONTACT OR THE VICINITY OF 11KV CONDUCTOR STRINGED BETWEEN POLE LOCATIONS NAV.KHI/JGY/108 AND NAV/KHI/JGY/109 AND GOT ELECTRIC SHOCK THE AMBULANCE 108 CALLED AND SHE ADMITTED TO HOSPITAL WHERE SHE DIED.        
28 RRC PADDHARI & KIRANBEN SHAYARBHAI POMANI 12.07.14 FHOS AS INVESTIGTED THE PRILIMINARY REASON OF THE ACCIDNET IS THAT ON THE ACCIDENT NIGHT THE VICTIM KUM. KIRANBEN SHAYARBHAI POMANI WAS PLAYING NEAR HER HOUSE WHERE THE LT LINE PSCPOLE NO.:- 665/28.08.2009 IE ERECTED. THE STREET LIGHT FIXTURE PROVIDED ON THE SAID POLE WAS SHORTED AND HENCE THE POLE IS SHORTED THROUGH THE GI  EARTHING WIRE OF THE POLE. THE PVC RIGID PIPE IS NOT PROVIDED IN EARTHING. HENCE THE VICTIM CAME IN CONTACT WITH WIRE OR POLE GOT ELECTRIC SHOCK AND DIED. THE DETAILED INVESTIGATION REPORT AND THE PM REPORT IS AWAITED.         
29 RRC VEKRI & BUFFFALO OF SHRI. MATHUR HARJI SORATHIA  04.073.1 FA BUFFALO WAS PASSING NEAR TO OLD LT LINE ROUND TUBULAR POLE IN VEKRI VILLAGE , INSULATION OF NEUTRAL WIRE OF ONE SERVICE CONNECTION WAS OPENED DUE TO SALINITY.DUE TO WIND IT WAS TOUCHED TO LT METAL ANGLE , SAME TIME BUFFALO TOUCHED THE TUBULAR POLE AND GOT ELECTROCUTED.        
30 RRC Rupavati & SHE BUFFALO OF SHRI. THOBHAN MAYA TOLIA 01.08.14 FA A DEAD CHAMELEON WAS THERE ON THE LT POLE TOUCHING THE PHASE WIRE AND "C" CLAMP. SO IN CONTINUOS RAIN & HUMID ATMOSPHERE LEAKAGE CURRENT WAS FLOWING THROUGH EARTHING & TOUCH POTENTIAL PRODUCED NEAR TRANSFORMER EARTHING PIT & AS THE BUFFALO PASSED IN BETWEEN TWO POLES OF TRANSFOMER CENTER AND TOUCHED THE EARTH WIRE GOT ELECTRIC SHOCK AND ELECTROCUTED RESULTANTLY.        
31 RRC HADALA & SHE BUFFALO OF SHRI HAKABHAI GANDUBHAI BHARVAD 02.08.14 FA THE VICTIM BUFALO WAS PASSING THROUGH THE ROAD AND IT CAME IN CONTACT WITH THE SNAPPED LT LINE WIRE AT LOCATION KAG/AND/L163 DT 18 OF RAMJIBHAI BHURABHAI VALU AG GROUP AND GOT ELECTRIC SHOCK AND DIED.THE PM REPORT AND DETAIL INVESTIGATION REPORT IS AWAITED.        
32 RRC SAL PIPALIYA & 1) FATAL HUMAN SH. KISHANBHAI JASABHAI RATHOD                      06.08.14 FHOS AS REPORTED BY THE SDO PADDADHARI THE INFORMATION ABOUT THE ACCIDENT HAS BEEN VIEWED ON THE LOCAL EVENING NEWSPAPER "AAJ KAL" ON DT.:- 7.08.14 AND HENCE THE SDO VISITED THE ACCIDENT SITE ON DT.:- 8.8.14 AT 8:00 A.M. AND INVESTIGATED ABOUT THE ACCIDENT IN CONFIRMATION WITH THE LOCAL POLICE STATION. THE VICTIMS WERE WORKING FOR THE TV CABLE STRINGING WORK UNAUTHORISED ON PGVCL PROPERTY 11KV SALPIPALIYA JGY FEEDER BETWEEN THE LOCATIONS MKHZ/SAL/JGY/041 AN /042. WHILE STRINGING THE CABLE THEY ACCIDENTLY CAME IN CONTACT WITH THE LIVE HT WIRE OF THE FEEDER AND GOT ELECTRIC SHOCK. ONE OF THE VICTIM DIED AT THE SITE ITSELF AND OTHER HAS BEEN ADMITTED IN CIVIL HOSPITAL RAJKOT.FURTHER INVESTIGATION AND DOCUMENTATION UNDER PROCESS.         
33 RRC SAL PIPALIYA & 1) NON FATAL HUMAN SH. JATINBHAI KAMLESHBHAI VISHNU 06.08.14 NFHOS AS REPORTED BY THE SDO PADDADHARI THE INFORMATION ABOUT THE ACCIDENT HAS BEEN VIEWED ON THE LOCAL EVENING NEWSPAPER "AAJ KAL" ON DT.:- 7.08.14 AND HENCE THE SDO VISITED THE ACCIDENT SITE ON DT.:- 8.8.14 AT 8:00 A.M. AND INVESTIGATED ABOUT THE ACCIDENT IN CONFIRMATION WITH THE LOCAL POLICE STATION. THE VICTIMS WERE WORKING FOR THE TV CABLE STRINGING WORK UNAUTHORISED ON PGVCL PROPERTY 11KV SALPIPALIYA JGY FEEDER BETWEEN THE LOCATIONS MKHZ/SAL/JGY/041 AN /042. WHILE STRINGING THE CABLE THEY ACCIDENTLY CAME IN CONTACT WITH THE LIVE HT WIRE OF THE FEEDER AND GOT ELECTRIC SHOCK. ONE OF THE VICTIM DIED AT THE SITE ITSELF AND OTHER HAS BEEN ADMITTED IN CIVIL HOSPITAL RAJKOT.FURTHER INVESTIGATION AND DOCUMENTATION UNDER PROCESS.         
34 RRC CHOKI & 1) FATAL HUMAN SH. SOMABHAI PALABHAI ZAPADA 11.08.14 FHOS THE VICTIMS WERE GRAZING THEIR ANIMALS NEAR PIPALVA ROAD WHERE AN IRON WIRE WAS TEID UP WITH TOP OF THE TREE BRANCHAND DUE ANY REASON BOTH VICTIMS PULLED DOWN THAT WIRE AT THAT MOMENT THE WIRE BROKEN DOWN AND SLIPPED AWAY FROM THE TREE BRANCH AND CAME IN CONTACT WITH THE 11 KV PIPALVA AG FEEDER PASSING NEAR THE TREE. THUS GOT ELECTRIC SHOCK AND RESULTING INTO 1 FATAL AND 1 NONFATAL ACCIDENT        
35 RRC CHOKI & NON FATAL HUMAN  SH. GOPALBHAI VAJABHAI ZAPADA  11.08.14 NFHOS THE VICTIMS WERE GRAZING THEIR ANIMALS NEAR PIPALVA ROAD WHERE AN IRON WIRE WAS TEID UP WITH TOP OF THE TREE BRANCHAND DUE ANY REASON BOTH VICTIMS PULLED DOWN THAT WIRE AT THAT MOMENT THE WIRE BROKEN DOWN AND SLIPPED AWAY FROM THE TREE BRANCH AND CAME IN CONTACT WITH THE 11 KV PIPALVA AG FEEDER PASSING NEAR THE TREE. THUS GOT ELECTRIC SHOCK AND RESULTING INTO 1 FATAL AND 1 NONFATAL ACCIDENT        
36 RRC GUNDALA(JAS) & SH. KALYANBHAI MOHANBHAI JOGRAJIYA 04.08.14 NFHOS THIS ACCIDENT CAME TO KNWOLEDGE FROM OUR J.E SH. H.B.SAJKA WHILE CIRCLE CHECKING DRIVE WAS GOING ON AT VILLAGE GUDALA (JAS). THE VICTIM TRT TO REMOVE THE ILLEGAL LUNGAR WIRE WHICH WAS BYPASSING THE METER FROM LT BUSHING OF TRANSFORMER CENTER UNAUTHORISE WAY.POWER SUPPLY OF THE FEEDER WAS ON AND VICTIM CAME IN CONTACT WITH THE LIVE 11 KV LINE AND GOT ELECTRIC SHOCK AND NON FATAL ACCIDENT OCCURED. THE ABOVE CONSUMER IS BOOKED UNDER THEFT AND DISCONNECTED AND F.I.R LAUNCHED BY SDO VINCHHIYA.        
37 RRC JASDAN & COW OF (1) SH. MAHESHBHAI UKABHAI GALIYA  02.09.14 FA ON THE DATE OF ACCIDENT THERE WAS HEAVY RAIN AND WIND PRESSURE, THE VICTIM ANIMALS WERE PASSING ON THE ROAD AND THAT TIME THEY CAME IN CONTACT WITH SNAPPED LT LINE CONDUCTOR AND GOT ELECTROCUTED.        
38 RRC JASDAN & COW OF (1) SH. MAHESHBHAI UKABHAI GALIYA  02.09.14 FA ON THE DATE OF ACCIDENT THERE WAS HEAVY RAIN AND WIND PRESSURE, THE VICTIM ANIMALS WERE PASSING ON THE ROAD AND THAT TIME THEY CAME IN CONTACT WITH SNAPPED LT LINE CONDUCTOR AND GOT ELECTROCUTED.        
39 RRC JASDAN & CALF  ofSH. INDU SANGRAM VAKATAR 02.09.14 FA ON THE DATE OF ACCIDENT THERE WAS HEAVY RAIN AND WIND PRESSURE, THE VICTIM ANIMALS WERE PASSING ON THE ROAD AND THAT TIME THEY CAME IN CONTACT WITH SNAPPED LT LINE CONDUCTOR AND GOT ELECTROCUTED.        
40 RRC Gokhalana & Pratpbhai Nanjibhai Khetariya 21.09.14 NFHOS As per statement of victim’s father victim unauthorized climb on the LT pole (pole no DT-14 L1/3) and got electric shocked and non fatal accident was occurred.        
41 RRC Faldang & Sh.Bhupatbhai Gokalbhai Kihla 28.09.14 FA  On date 28.09.2014 in morning time 66 KV Faldang SS near Faldang village buffalo’s herd was going toward agriculture area with  owner for grazing. At that time due to any reason one buffalo out of them went near the bore type earthing pit of LSTC of 11 KV Rafala AG feeder. This feeder was in 1 ph. Power supplied and in earthing strip power was on. Hence this buffalo was came in contact with that strip and got electric shock and this accident occurred.

       
42 RRC Veraval & Sh.Vijaybhai  Ramniklal  Chavda 14.09.14 NFHD industrial consumer M/S Blossom Kitchenware consumer No.81907-00118-2 lodged the complain no.03 for low voltage complain. Hence the victim Sh.Vijaybhai Ramniklal Chavda (ALM) along with the Sh.K.N.Jadav (Electrical Assistant) went to the said industries to attend the complain. After verifying the transformer, the victim Sh.V.R.Chavda (ALM) climbed on the plastic roof of the shed to check the service cable which is lying on the said roof but accidentally the old deteriorated plastic sheet broken and he fell down from the roof of height about 20 feets and met with a mechanical accident. The victim then admitted to the  wockhardt hospital for further treatment.        
43 RRC Ardoi & Sh. Jaysukhbhai Pravinbhai Bagda 13.09.14 NFHOS On dated 13-Sep-2014, at time approx. 14:03 Hrs an electrical accident has occurred to a boy at Kotda-Ardoi road, opposite to the farm of Pravinbhai Bhikhabhai Bagda, at Ardoi village.
A boy aged about 7-yrs-old due to any reason climbed on the tree from where 11kv Ardoi ADOM feeder is passing nearing to it. Accidentally, victim came in contact with 11 KV line live conductor and got electrical shock and met with non-fatal human electrical accident. There were two eyewitness named, (1)Dineshbhai Devabhai Bagda, (2)Ramjibhai Desha Bhai Bagda of ardoi village who were present at opposite location of accident site.
For further treatment victim was transferred at Government hospital Rajkot. On site, there were black spot found on the conductor of 11kv Ardoi ADOM feeder. A statement of eyewitness was taken and site Rojkam was done and also local police station was informed for above incident. 
       
44 RRC Navagadh & Babubhai Bhikhabhai  15.09.14 FA Victim Buffalo was passing near Rachna vadi valu TC,Dt No-20, 100 KVA ,Village-Navagadh and at that time leakage current was flowing through earth wire and buffalo came in contact with earth wire of transformer center, according it got electric shock and electrocute, resulting into animal fatal accident.        
45 RRC Dhoraji  AG Area & Sh. Hemantbhai Jentibhai Parmar 27.09.14 NFHOS Jentibhai Gangabhai Parmar was given the Work order for fail TC replacement wide W.O.No. DD/T-1/7054 Dt. 25.09.14. Victim Shri Hemnatbhai Jentibhai Parmar ( Contractor’s Labour)  was gone to replace failed T/C at Location No: DRJ/DRJ/082/R002,DT No.27 in 11 Kv Dhoraji AG feeder. Victim has taken line clear permit of 11 KV Datarwadi AG feeder instead of 11 KV Dhoraji AG feeder through Line Inspector Shri V.A.Muchhadiya. Power supply of 11 KV Dhoraji AG feeder is continue in single phase duration. Victim has started activity of T/C replacement without confirm power supply was off or not? Victim has not taken any kind of safety precaution and climb on T/C Structure and touched to left side DO fuse. Due to continuity of power supply victim got electric shock. Also no any supervisor was present at the time of TC replacement work. Hence Non fatal accident occurred. The detail investigation follows.
 
       
46 RRC Nani Marad & Sh . Gobarbhai Alabhai Kodiyatar 29.09.14 FA A Fatal Accident occurred to a buffalo owner Shri Gobar Ala Kodiyatar at village :- Nani Marad. From Site Visit it was found that  Water logged surrounding said transformer due to near pond. At that time Buffalo was passed near transformer center and came in contact with wet place and same time died due to any reason. During investigation switching " ON " the power supply of said T/C. No any leakage current found on whole T/C. The Said accident  may be happened due to minor leakage current of  T/C but actual reason for accident is to be known after receiving P.M. report. Detail Investigation follows.        
47 Morbi GHUNTU
Buffalo of
 Nareshbhai Gangarambhai Soriya
21.04.2014 FA A conductor of 11KV Ghuntu JGY feeder detached from pin point of location# GHU/GHU/070 & fell on ground. Given the conductor was live & the victim buffalo while passing by it came in contact, the victim animal electrocuted. The evening before the accident day there being extreme wind & storm like weather which may have resulted into detachment of the conductor from pinpoint.  Report yet not received NA NA Span has been restrung & guarding has been provided.
48 Morbi SARTANPAR
Vijaybhai Vashrambhai Bahukiya 
25.04.2014 FHD The victim had been attending jumper of 11KV Motto Ind feeder. The feeder’s LC was duly permitted. The victim was restoring jumper of the feeder by climbing over the DP structure location# SRP/MOT/005/R-05. In mean time one of the HT connections in the feeder namely M/S Ador ceramic pvt LTD with consumer# 25789 was in the process of changing over to DG set. The malfunction/ fault in one of the changeover mechanism led to reverse flow of supply of DG set into feeder. Although this may be momentary but was intense enough to cause fatal accident to the victim. Report yet not received NA NA NOTICE ISSUED TO ALL HT CONSUMERS REGARDING PERIODICAL MAINTENANCE & INSPECTION OF DG SET. Further, FIR# 0037/2014 against the directors of ADORE ceramics has been registered which should set deterrent example among consumer fraternity using DG set without effective  protective devices to guard reverse power phenemenon. Also supervisors namely H.K.Chauhan (L.I.) & G.K.Goswami (L.M) have been meted out disciplinary action in transfer & suspension. In addition to disciplinary action, an inquiry is pending against Chargsheet# EE/Wanka/Confidential/HR/DA/HKC/87 & EE/Wanka/Confidential/HR/DA/HKC/88 on 07.06.2014 issued to H.K.Chauhan (L.I.)  & G.K.Goswami (L.M) respectively. Also inquiry panel has been established. A reminder letter# EE/Wanka/Tech/2/5511 on 19.09.2014 has been sent to the concerned Police Sub Inspector inquiring about status quo of registered FIR against the directors of ADORE ceramics. Further, through the letter we have asked whether the concerned accused have been arrested .
49 Morbi DALDI
Gajendrasingh Dausingh
26.05.2014 NFHOS The victim is hired as a labourer by contractor undertaking PGVCL line work. The victim was into line maintenance work of 11KV Kashipar AG feeder emanating from 66KV Daldi S/S. The line clearance permit of the concerned feeder was duly taken by line inspector before commencing the maintenance work of this feeder. Further as a safety/ protective compliance, all 3 phases had been shorted & earthed before commencement of the aforesaid work. However, technician of the 66KV Daldi S/S switched ON the 11KV Kashipar feeder even though line clear permit was not returned. Hence, the victim suffered electric shock and fell down on the ground from the TC center & met with non-fatal electrical accident.  Report yet not received NA NA The personnel who by mistake powered on the feeder depite its LC was not returned had been terminated with immediate effect. The SIMS engineering agency had been awarded the contract to maintan concerned substation on behalf of GETCO. Therefore the Wankaner- EE has wrote letter# EE/WKR/TECH2/5557 on 20.9.2014 to EE (TR) GETCO, 132KVSS insisting to black list the SIMS engineering agency.
50 Morbi BHAVANIGADH
Buffalo
Ghusabhai Sondabhai Koli
03.06.2014 FA The earth wire of the village T/C was cut. The victim buffalo while passing by
came in contact with this earth wire & electrocuted.
Report yet not received NA NA As pasrt  of maintanance the earth wire has been replaced, PVC pipe provided & earthing has been reactivised
51 Morbi MATHAK
Cow of
Jayvantsinh Gumansinh Zala
18.07.2014 FA The live conductor of 3 phase 4 wire LT line snapped & touched the victim cow passing by & thus the cow electrocuted. Report yet not received NA NA The conductor has been replaced. Code Meaning
52 Morbi MORBI
Cow of
Sh Kalu Viha Toriya
25.07.2014 FA The LT Line (Aerial bunch LT) Girder pole# SCY/DT002/C2/016 bearing street light fixture became live as the street light fixture was shorted. The two victim cows passing by this pole electrocuted & accident occurred. Report yet not received NA NA The notice has been issued to the Chief Officer of Nagarpalika to regularly carry out maintenance of all street light fixtures to avoid such accidents in future. FHD Fatal Human Departmental
53 Morbi MORBI
Cow of
 Sh Bhala Kadva
25.07.2014 FA The LT Line (Aerial bunch LT) Girder pole# SCY/DT002/C2/016 bearing street light fixture became live as the street light fixture was shorted. The two victim cows passing by this pole electrocuted & accident occurred. Report yet not received NA NA The notice has been issued to the Chief Officer of Nagarpalika to regularly carry out maintenance of all street light fixtures to avoid such accidents in future. NFHD Non Fatal Human Departmental
54 Morbi Rafaleshwar
Shubhash Manganbhai Bariya
28.07.2014 NFHOS The victims were working on the JGY feeder, when the said feeder was powered on. Report yet not received NA NA The stern notice has been issued to the contractor because his hired men did not follow instructions of PGVCL's supervisor. The contractor has been reprimended that if this is repeated ever then his contract shall be terminated. A show cause notice has been issued to the contractor by concerned EE about why he should not be blacklisted. FHOS Fatal Human Outsider
55 Morbi Rafaleshwar
Rajeshbhai Chhaganbhai Bariya
28.07.2014 NFHOS The victims were working on the JGY feeder, when the said feeder was powered on. Report yet not received NA NA The stern notice has been issued to the contractor because his hired men did not follow instructions of PGVCL's supervisor. The contractor has been reprimended that if this is repeated ever then his contract shall be terminated. A show cause notice has been issued to the contractor by concerned EE about why he should not be blacklisted. FA Fatal Animal
56 Morbi Rafaleshwar
Kapasibhai Sonabhai Bariya
28.07.2014 NFHOS The victims were working on the JGY feeder, when the said feeder was powered on. Report yet not received NA NA The stern notice has been issued to the contractor because his hired men did not follow instructions of PGVCL's supervisor. The contractor has been reprimended that if this is repeated ever then his contract shall be terminated. A show cause notice has been issued to the contractor by concerned EE about why he should not be blacklisted. NFHOS Non Fatal Human Outsider
57 Morbi KHAMPALIYA
Buffalo of
Vasubhai Khimabhai Rabari
30.07.2014 FA The Khampaliya village TC had leakage current flowing into earth. Since it was raining while the accident took place, the induction zone enhanced in & around TC structure. The buffalo while passing near this TC must have come into induction zone created by leakage current & thus electrocuted. Report yet not received NA NA LT AB cable has been replaced by 16mm cable; TC earthing reactivised.
58 Morbi UNCHI MANDAL
Buffalo of
Ajitsinh Gandubhai Mori
16.08.2014 FA The victim buffalo somehow tangled his horn with the guy wire of DP structure of Madhuvan AG feeder bearing Location# 14. The victim buffalo in its struggle to free its horns from the guy wire seems to have broken the guy wire near the ground & this broken loose guy wire then contacted the jumper of AB switch on the DP structure. Thus the buffalo electrocuted. Another buffalo standing by & touching the victim buffalo was also electrocuted.  Report yet not received NA NA The snapped Guy wire has been removed.
59 Morbi UNCHI MANDAL
Buffalo of
Ajitsinh Gandubhai Mori
16.08.2014 FA The victim buffalo somehow tangled his horn with the guy wire of DP structure of Madhuvan AG feeder bearing Location# 14. The victim buffalo in its struggle to free its horns from the guy wire seems to have broken the guy wire near the ground & this broken loose guy wire then contacted the jumper of AB switch on the DP structure. Thus the buffalo electrocuted. Another buffalo standing by & touching the victim buffalo was also electrocuted.  Report yet not received NA NA The snapped Guy wire has been removed.
60 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
61 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
62 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
63 Morbi MESARIYA
Buffalo of
Vajubhai Keshabhai Bhaliya
24.08.2014 FA One of 11KV poles of Bhalgam AG feeder has been surrounded by water logging. The victim buffaloes were drinking water from this water logged area. Meantime, a pigeon sitting on the pin insulator of the said pole touched metallic point & there by phase to earth fault resulted into passing of current to water logged area. Thereby the victim buffaloes electrocuted.  Report yet not received NA NA The pole has been shifted from water logged land to dry area.
64 Morbi PANCHASAR
Buffalo of
Thobhanbhai Butabhai Bharvad
10.09.2014 FA LT conductor having slipped/ detached from shackle insulator, touched “C” clamp & thereby leakage current was passing into LT pole’s GI earth wire. The victim buffalo coming in its contact & thereby electrocuted.  Report yet not received NA NA LT Line Maintenance carried out, which included removal of earth wire from LT pole as it is surrounded by water currently. Further TC maintenance too has been carried out.
65 Morbi TANKARA
Buffalo of
 Daudbhai Jumabhai Ghanchi
21.09.2014 FA One of the three victim buffaloes was scratching itself to guy wire of 3-phase 4 wire LT pole. Due to scratching intensity of the buffalo onto the guy wire, the tension was built over pole which resulted into snapping of one of 3 phases’ bare conductor of this LT line. The snapped conductor fell down on the victim buffaloes & thereby the buffaloes electrocuted.  Report yet not received NA NA The conductor has been replaced.
66 Morbi TANKARA
Buffaloes of
Rasul Mamad Chaudhari 
21.09.2014 FA One of the three victim buffaloes was scratching itself to guy wire of 3-phase 4 wire LT pole. Due to scratching intensity of the buffalo onto the guy wire, the tension was built over pole which resulted into snapping of one of 3 phases’ bare conductor of this LT line. The snapped conductor fell down on the victim buffaloes & thereby the buffaloes electrocuted.  Report yet not received NA NA The conductor has been replaced.
67 Morbi TANKARA
 Buffalo of
Hanif Rahim Sherashiya
21.09.2014 FA One of the three victim buffaloes was scratching itself to guy wire of 3-phase 4 wire LT pole. Due to scratching intensity of the buffalo onto the guy wire, the tension was built over pole which resulted into snapping of one of 3 phases’ bare conductor of this LT line. The snapped conductor fell down on the victim buffaloes & thereby the buffaloes electrocuted.  Report yet not received NA NA The conductor has been replaced.
68 Morbi Sapakda
Adarsh Vasudevbhai Makwana
28.09.2014 FHOS Few children were playing on tractor trolley parked under the feeder. While playing, the victim must have touched the live bare conductor of the feeder & thus electrocuted.  Report yet not received NA NA New PSC pole has been erected for 11KV line & the span has been restrung. Show cause notice issued to the SDO for lach of timely periodic maintenance.
69 Morbi RAVAPAR
Kamlesh Dharamshibhai Sonagra
28.09.2014 FHOS Illicit construction structure was being built by the owner of the premises. This construction was not only encroaching outside his privately owned plot but was also immediately under 11KV Bahumali Urban feeder. The structure being built seems to be of security office. The victims were hired for building this structure. However while working at height over the roof of this structure to build trolley lift, some metal portion used for building this trolley lift touched overhead live bare conductor of the said feeder. Thus, the accident occurred.  Report yet not received NA NA FIR# 181/12 has been lodged against Mavji Premji Kanjariya, the party responsible for constructing illegal structure below 11KV line.
70 Morbi RAVAPAR
Rakesh Gumansing Adivasi
28.09.2014 FHOS Illicit construction structure was being built by the owner of the premises. This construction was not only encroaching outside his privately owned plot but was also immediately under 11KV Bahumali Urban feeder. The structure being built seems to be of security office. The victims were hired for building this structure. However while working at height over the roof of this structure to build trolley lift, some metal portion used for building this trolley lift touched overhead live bare conductor of the said feeder. Thus, the accident occurred.  Report yet not received NA NA FIR# 181/12 has been lodged against Mavji Premji Kanjariya, the party responsible for constructing illegal structure below 11KV line.
71 Morbi RAVAPAR
Kumsing Meghaji Adivasi
28.09.2014 NFHOS Illicit construction structure was being built by the owner of the premises. This construction was not only encroaching outside his privately owned plot but was also immediately under 11KV Bahumali Urban feeder. The structure being built seems to be of security office. The victims were hired for building this structure. However while working at height over the roof of this structure to build trolley lift, some metal portion used for building this trolley lift touched overhead live bare conductor of the said feeder. Thus, the accident occurred.  Report yet not received NA NA FIR# 181/12 has been lodged against Mavji Premji Kanjariya, the party responsible for constructing illegal structure below 11KV line.
72 PBR PADODAR AND
DILIPBHAI KANABHAI SANJVA
01.04.14 FHOS Drop out fuse was blown of Transformer centre known as Jagmal Naran Sanjva valu TC.
Vill. Padodar. Sh. Dilipbhai Kanabhai Sanjva was trying to fix it with help of wooden bamboo. The bamboo was wet, when it came in live contact of 11KV supply, he got shocked. The above information is received by eye witness Sh. Punjabhai Jagmalbhai Sanjva. 
Report yet not received NA NA Public Awareness
73 PBR SHEPA AG
AREA AND VINUBHAI ARJANBHAI TANK
25.04.14 NFHD A  Non  Fatal  Human   Departmental   Accident  Occurred  to  Electrical  Assistant    
Sh. Vinubhai  Arjanbhai  Tank   Age 52  Years  On  Date  25.04.2014  at  10.40  A.M.   in 11  KV Satmarag  Ag  Feeder  Emanating  from 66  KV    bhudhecha   S/S  Due  to  by  mistake  victim  climbed on  The T/C D.P.  Of   Live Line  of  11  KV   Satmarag  Ag Feeder.  Line  Clear  was  Taken  of  11  KV  Chakivav  Ag  Feeder  Instead  of  11  KV  Satmarag  Ag Feeder.
Report yet not received NA NA Necessary instruction given to all line staff & K B Desai was transferred & Chargesheet issue vide MGRL/HR/SHOWCAUSE/KBD/281,DT-08.08.2014 and C V Chapadiya - DE(Tech)-
Keshod Div appointed as inquiry officer vide SEP/HR/3/Dept Inquiry/570,05.09.14.
74 PBR BARVANESS AND KISHORBHAI DASABHAI KODIYATER 10.05.14 FHOS
Accident is occurred due to 1 phase service wire hitted by truck owner( truck no.GJ 25 T 9998) and service wire entangled on matel cage made of MS Angle and G.I. Pipe at the top of the truck which is parked in the open land.insulation of 1 phase service wire broken and removed due to tension on both the ends of service wire. Thus due to open phase wire came in contact with metal cage of truck and truck body charged. victim came in contact with charged truck body and got shocked and electrocuted
Report yet not received NA NA Proper Maintanace Done
75 PBR KHODADA AND BULLOCK OF KANABHAI SUDABHAI GALCHAR 14.05.14 FA An animal bullock accident occurs at village- Khodada (Ness) and the owner of cattle is
Sh. Kanabhai Sudabhai Galchar due to fault of Lightning Arresters. The Lightning Arrester's top part fall down on land and lightning arrester's jumper touch the 11KV line channel so leakage current is there in the earth, at that time bullock passes nearer to the Transformer D.P. structure around the induction zone and bullock fall down on land and than after in few minutes bullock died.
Report yet not received NA NA Proper Maintanace Done
76 PBR NANDARKHI AND HANUFBHAI DAUDBHAI VARAM 01.06.14 FHOS  Accident occurs to shree. contractor yusuf  ismail jivan person
shree,hanifbhai  daudbhai varam resident,mangrol age-21 year approx work at nandarkhi village ag area for replacement of deteriorated psc pole for 11 kv farngta ag feeder .the line clear was taken of  11 kv   farngta ag feeder and 11 kv shill feeder eminating both feeder 66 kv shil substation . the contractor gang(team) work compled of dismantling and erection of new pole and fixed  v-crossm with pin  the victim  has complted  binding  of two numers of phases and  thred phase pin binding carrying out.he come across with electric shock at time he was failedand sticked with v-crossm and was lowerdown by coworkers with help of rope.
Report yet not received NA NA Proper Maintanace Done & MEMO issue to JE-MGRL/RSDN/HR/CONFI/120,DT-07.06.2014
FIR LODGED AT SHIL POLICE STATION AGAINST FARMER DAYABHAI LAKHABHAI BHARDA VIDE FIR NO-I/17/2014,DT-13/06/2014
H B Mori - DE - Show Cause Notice Issue vide SEP/HR-III/DA/HBM/221 Dt-07-07-2014 & Draft C
77 PBR AKHODAR AND JAYSHUKHBHAI MANJIBHAI KATHAD 04.06.14 NFHOS The victim was removing support of newly constructed slab of house and "head" of victim touched to the 11KV live wire of Khirasara JGY Feeder. Report yet not received NA NA Proper Maintanance Done & Public Awareness
78 PBR AGATRAI AND KANTILAL BHODABHAI BHARDA 11.06.14 NFHD Victim had completed maintenance work on HT Pole, while de climbing (getting down), his leg slipped and fall down on ground and got injured.  Report yet not received NA NA Necessary instruction given to all line staff & VICTIM WAS UNDER MEDICAL TREATMENT
& TILL ON LEAVE AFTER THE JOIN OF DUTY DEPARTMENTAL ACTION WILL BE INITIATED INFORMED BY CONCERNED DE VIDE LETTER KSD-2/ACCD/TECH/1711,DT-09.09.14
79 PBR PANKHAVA AND BULLOCK OF KHIMABHAI VIRAMBHAI RAVALIYA 11.06.14 FA Conductor of 11 kv Dudhada Ag feeder was snaped from top insulator  and was
lying on top fitting angle ,Through earthing leakage current flow in route of tree which was nearby pole,a buffallo was tied with stem of tree with iron chain,Thus fatal accident occured.
Report yet not received NA NA Proper Maintanace Done
80 PBR SHEPA AND FARUKHBHAI HUSENBHAI KALVAT 14.06.14 FHOS  It might not be due to snaping of conductor  but may be due to wet tools tackle utilize for repairing  ceiling of  room came  in contact with 11 kv langodra  ag feeder conductor.&   electrocuted. Report yet not received NA NA Public Awareness
81 PBR SHEPA AND DAUDBHAI HUSENBHAI KALVAT 14.06.14 NFHOS  It might not be due to snaping of conductor  but may be due to wet tools tackle utilize for repairing  ceiling of  room came  in contact with 11 kv langodra  ag feeder conductor.&   electrocuted. Report yet not received NA NA Proper Maintanance Done 
82 PBR BHOGSAR AND BUFFALO SHE OF GOGANBHAI MANDABHAI MORI 16.06.14 FA DUE TO HEAVY RAIN & WIND LEAKAGE CURRENT PASSES THROUGH EARTH WIRE
OF LT LINE POLE & DUE TO WATER LOGGING NEAR THAT POLE & SHE-BUFFALO OF SH GOGAN MANDA MORI COMES IN CONTACT WITH THAT LEAKAGE CURRENT AND GOT ELECTROCULATED.
Report yet not received NA NA Proper Maintanace Done
83 PBR KHORASA AND RAGHAVBHAI PAVANBHAI KODIYATAR 03.07.14 FHOS A   fatal  accident occurred to a boy in survoyday hostel at khorasa village. By preliminary investigation,
it is found that a boy - shri rahav pavan kodiyatar has mischievously or by intestinally touch 11kv conductor through wooden road passing nearby tares of said hostel and came in contact with live 11kv gayatri jgy feeder & got electrocuted.
Report yet not received NA NA Proper Maintanace Done & Publice awareness
84 PBR KHAMIDHANA AND BUFFALO SHE OF KANTILAL THAKARSHIBHAI GAJERA 18.07.14 FA The buffalo came in live contact of leakage power in earthing of transformer centre known
as water works valu TC. vill. Khamidana and got electric shock.
Report yet not received NA NA Proper Maintanace Done
85 PBR RANAVAV AND BUFFALO-SHE OF KHIMABHAI POLABHAI GARCHAR 21.07.14 FA BUFFALO-SHE WAS PASSING NEAR TRANSFORMER
CENTRE AND LIGHT RAIN WAS COIMING AT THAT TIME AND METAL ROD WAS FULL OF LIGHT WATER. SO IT MAY BE EARTH LEACKAGE FROM TRANSFORMER CENTRE AND BUFFALO-SHE MIGHT BE COME IN ZONE AND GOT ELECTROCULATED DUE TO WET SPACE.
Report yet not received NA NA Proper Maintanace Done
86 PBR KADAYA AND GORDHANBHAI BHIKHABHAI RATHOD 25.07.14 NFHOS When a labour of contractor working on Dhanej Ag Fdr during line erection work
11 kv shackle pole was broken from top and below  guy clamp thats cause labour of contractor falled down on earth the and injured his legs, hands and body parts.
Report yet not received NA NA NOTICE ISSUED TO CONTRACOTR & NECESSARY INSTRUCTION GIVEN TO ALL LINE STAFF & CONTRACTORS.
87 PBR KESHOD AND BUFFALO SHE OF VANPARIYA JENTIBHAI NANJIBHAI 05.08.14 FA At the  visit of accident site due to heavy rain and wind an ab cable phase wire touches
to tail end  moistured pole,leackage current passes through pole to wet soil at that time buffello passes near by area of electrocuted pole and got shocked.
Report yet not received NA NA Proper Maintanace Done
88 PBR LAMBHORA AND BUFFALO SHE OF JADAV ARSHIBHAI VALABHAI 10.08.14 FA Due to service wire one phase  open &open phase touch guy clamp which is 
supported   to pole  so phase curent  pass through guy calmp to earth  there is lot of water arond they pole due to rain so cureent  pass thorogh water and then   buffalo  come nearr and  contact with the phase lekage  current  an around the induction zone and  buffalo fall down to land and then after few minutes buffalo  died age 7 year as per  partiis.      
Report yet not received NA NA Proper Maintanace Done
89 PBR KATRASA AND VATSALKUMAR SAILESHBHAI DODIYA 11.08.14 NFHOS  Accident occured due to coconut tree leave(pan) touched and burnt with conductor of 11 kv Ambalgadh jgy line beetween location no.97 and 98 due to thats cause 11 kv conductor broken and victim came in contact and his grand father sh.meramanbhai tries to save his grandson and both got electric shock . Report yet not received NA NA Proper Maintanance Done & Public Awareness
90 PBR KATRASA AND BABUBHAI MERAMANBHAI DODIYA 11.08.14 NFHOS  Accident occured due to coconut tree leave(pan) touched and burnt with conductor of 11 kv Ambalgadh jgy line beetween location no.97 and 98 due to thats cause 11 kv conductor broken and victim came in contact and his grand father sh.meramanbhai tries to save his grandson and both got electric shock . Report yet not received NA NA Proper Maintanance Done & Public Awareness
91 PBR KUTIYANA AND BUFFALO SHE OF BADHA BHAVAN RAIGA 15.08.14 FA Due to heavy wind leakage current passes through  support wire inside of lt line pole &
due to water logging near that pole & she buffalo of shree Badha Bavan Raiga comes in contact with that leakage current and got electrocuted. 
Report yet not received NA NA Proper Maintanace Done
92 PBR BARULA AND BUFFALO SHE OF KARSHANBHAI PARBATBHAI JOHRA 30.08.14 FA A   fatal  accident occurred to buffalo passing near by LT line and LT conductor
broken from joint and came in contact with live LT Wire & buffalo got electrocuted.
Report yet not received NA NA Proper Maintanace Done
93 PBR CHORWAD AND UMESHBHAI MULJIBHAI SEVRA 02.09.14 FHOS A   fatal  accident occurred to a boy in jarari vistar nr. Bandar road at chorwad village.
By preliminary investigation, it is found that a boy - shri umesh mulji sevra has mischievously or by intestinally touch 11kv conductor through wooden road / iron raod while getting thread of kite passing nearby tares of Shri dinesh ramji pandit and came in contact with live 11kv chorwad jgy feeder & got electrocuted.
Report yet not received NA NA Proper Maintanace Done & Publice awareness
94 PBR AGATRAI AND BUFFALO SHE OF HIRABHAI ALABHAI KHAMBHALA 03.09.14 FA A fatal electrical accident occurred to a buffalo of Sh. Hirabhai Alabhai Khambhala
due to breakage of LT schakle insulator and leakage current passes through GI wire (earthing wire) and buffalo came in contact and got electrical shock and died.
Report yet not received NA NA Proper Maintanace Done
95 PBR VADLA AND BULLOCK OF DAYABHAI RAJABHAI KODIYATAR 07.09.14 FA The person was going with his bullock at that time the live LT conductor was broken and laying down on earth and this bullock come in contact with this live wire and get electric shock and dies at site. Report yet not received NA NA Proper Maintanace Done
96 JAMNAGAR Hansthal,Shyam Arjan Chavada 25-4-14 NFHOS while boy was catching almond from tree with an iron rod,somehow iron rod touched to line jumper of transformer center and got electric shock PENDING N.A NO AWARENESS IN PUBLIC FOR KEEP SAFE DISTANCE FROM LINE
97 JAMNAGAR Govana,Lalsang Harisang Chauhan 15-5-14 FHOS Contractor asked for Line Clear Permit of 11 kv Govana Ag feeder for providing Jumper of newly erected SPA sanctioned work but actually the existing feeder was 11 kv Valor ag feeder After taking LCP of 11 KV Govana Ag feeder instead of 11 kv Valor Ag Feed CEI REPORT AWAITED N.A N.A Strict instructions passed on to all concerns to be very vigilant while taking LCP 
98 JAMNAGAR Nandana,Somat Natha Gojiya 30-5-14 FHOS Victim has gone to seen the new construction room at his brothers premises on the roof of the newly constructed room on which 11 kv bhalara-JGY line passes above as well as across the roof of the newly consructed room vertical distance between roof of roo CEI REPORT AWAITED N.A N.A Frequent public meeting for awarness about the hazards of construction beneath the lines are being arranged at filed level.
99 JAMNAGAR Meghpar Jashapar,Pramod Parshotambhai Sonagara 4-6-14  NFHD Pin Insulator faulat occurred during night in 11 kv Balambha feeder but due to some how breaker of that feeder at 66 kv keshiya s/s was not triped hence PIN was fired & brusted so conductor was fall down on V-cross arm. This PSC pole was burnt due to cont AWAITED AWAITED NA GETCO authority is informed to solve above technical problem by a letter to D.E. 132 KV S/S Dhrol
100 JAMNAGAR Jamnagar,A Cow of Razakbhai Ismailbhai Khafi 16-6-14  FA Live phase of 1Ph sevrive wire was teared off and got damged and due to rain and heavy wind.There for it came in contact with GI wire of service line it self. This GI wire along with service line was touched with nearby existing telephone tabular pole due N.A N.A N.A Nacessary maintenance is carried out new psc pole erract to reduce lenth of service wire and replace faulty service wire.
101 JAMNAGAR chokhanda,Arvindbhai Naranbhai Dhokiya 18-6-14 FHOS The victim was working unauthorisely on last L.T line pole of Lakha Allarakha ag connection of 63 KVA Hamir Markhi AG group at village chokhnada for restringing of conductor by isolating 11 KV DO fuse from TC The Jumper of AG feeder was under shutdown for CEI REPORT AWAITED N.A N.A People are being educated to avoid unauthorized operation of lines by arranging safety meetings at various villages.
102 JAMNAGAR Dhrol,Prakash R Consumara 23-6-14  NFHD During maintance of TC at village area our LM fall down form TC due to Giddines and his left leg got injured after taking primary treatment at dhrol Government hospital he  is transffered to Jamnagar AWAITED AWAITED NA No any remedial action is required to be taken.
103 JAMNAGAR hanjarapar,Mulji Devshi Kanzaria 24-6-14 FHOS Fatal Accident occurred to an outsider man at LT line of Tc at mathuranagar village on 11 kv dhandhusar JGY feeder of vadatra s.dn due to snapping of conductor  PENDING N.A NO DETAIL JINVESTIGATION UNDER PROCESS.
104 JAMNAGAR Gadhaka,Jiviben Devarajbhai Parmar 6-7-14 NFHOS Woman Was cleaning ground around LT line ,accidently conductor of LT line brokedown and touched her body and got electric shock PENDING N.A NO L.T.AB CABLE WORK COMPLETED IN WHOLE VILLAGE NETWORK.
105 JAMNAGAR Kota ag,A Camel of Shree Jesha sura Gangar 8-7-14  FA A Camel came in contact with live electircal wire of 11 kv dharampur ag dom to pile of soil and got electrocuted PENDING N.A NO NECESSRY MAINT. WORK CARRIED OUT BY S/DN.
106 JAMNAGAR Jamnagar,A cow of Jadeja Yashrajshinh Vanraj sinh(Unknown Brown Cow) 13-7-14  FA Due to hevay wind pressure and rain service wire insulation in the LT pole became weak and came in contact with its GI support wire.in turn the pole angle became shorted and the leakage current passed through the earthing wire of that pole Meanwhile a cow N.A N.A N.A Nacessary maintenance is carried out providing bus bar at pole. 
107 JAMNAGAR Jamnagar,A cow of Bhojabhai Nagshibhai Gadhave 13-7-14  FA Due to hevay wind pressure and rain service wire insulation in the LT pole became weak and came in contact with its GI support wire.in turn the pole angle became shorted and the leakage current passed through the earthing wire of that pole Meanwhile a cow N.A N.A N.A Nacessary maintenance is carried out providing bus bar at pole. 
108 JAMNAGAR Laloi ,Manjuben Vithalbhai Bhalara  24-7-14 NFHOS Victim growing bee in own farm.at that time fault occurred in 11 kv pin of laloi AG feeder on pole no 126 one phase conductor of line was broken at pin point conductor of line was nbot fall down on land but hangiing at tatpping  and loose down the span at CEI REPORT AWAITED N.A N.A All concerns are instructed to carry out periodical qualitative maintenance activity so as to avoid such incidents in future.
109 JAMNAGAR Jamnagar,Manishaben Hasmukhbhai Bhatt 26-7-14 NFHOS The victim who is belived to be mentally retarted jumped from the second floor of her house for any reason and while falling the victim came in contact with the 3-phase 5 wire LT Line passing near by to the house and then felldown on the ground and was se N.A N.A N.A Not Reported.
110 JAMNAGAR Khambhalia,A bullock(5Yrs) of shree Anupsinh Nagubha Sodha  and one chile bullock(2 yrs)  of shree Natubha Jitubha Jadeja 26-7-14  FA as par statement of eye witness & owners of animals fatal accident occurred due to street light cable phase got shocked &leakage current flow in wet psc pole at that time both animals came in contact & got electrocuted. PENDING N.A NO NECESSRY MAINT. WORK CARRIED OUT BY S/DN.
111 JAMNAGAR Nagarsim,Buffalow of Jusab Juma Safiya 5-8-14  FA Due to snapping of LT line conductor and came in contact with neck and right leg of buffalow and fatal accident occurred NO NO NO Next day on (N.A6/N.A8/2N.A14) Rama Sina’s T/C group all LT line &  connection maintenance work carried out and detoriated conductor replaced.
112 JAMNAGAR Badanpar,A she Buffalo of pababhai Sondabhai Zapada 5-8-14  FA Leakage current passing through GI wire which comes from LV side Neutral of Transformer animals are more sensitive with minor leakage current and as a buffalo came in contact with GI wire and it met with an electrical accident AWAITED AWAITED NA Periodically maintenance work carried out by SDO at regular interval.
113 JAMNAGAR Jasapar,A Bufflaow Hemashibhai Polabhai Malani 7-8-14  FA Victim got electroculated at about 9.00 A.M on 07.08.14 while grassing nearby substation she buffalo has inserted right horne in the distribution box of existing kanabhai Vadi Group AWAITED AWAITED NA Proper re-earthing with PVC pipe was done of this TC and proper maintenance of that dist. Box is done by the deputy engineer ofr non occurance of such type accident.
114 JAMNAGAR Jamnagar,A male Got of Sarifaben W/O Adam Muniya 8-8-14  FA Leakage current occurred by return power occurance from near by existing LT pole of the transformer centre a fatal accidnet occurred to A mele Goat near by TC due to earth leakage current ,exact cause of leakage current is not found  N.A N.A N.A Continuous instalation & cheking work done. And Nacessary Lt Line maintenance is carried out.
115 JAMNAGAR Bhinda,Sankar S Pargi 9-8-14  NFHD As per fault center complaint for break down of 11 KV jumper on TC above DO fuse while victim climbed on TC todo jumper fault after taking LCP from 66 kV Bhadthar SS but by mistake Mr. B.L, Gosai (LM) taken LC of Bhinda AG feeder and other crossing feeder PENDING N.A NO CHARGE SHEET ISSUESD TO CONCER LINEMAN AND DEPTT INQUIRY UNDER PROCESS. ALSO STRICT INSTRUCTION GIVEN FOR USE OF SAFETY GADGETS .
116 JAMNAGAR Jamnagar,A cow Unclaimed 10-8-14  FA As per the the telephonic  messg the site was visited were water logging nearby TC ,primary reason is not found However due to any other unknown source leakage current is suspected at water logging near TC due to water logiing earth leakage current passin NO NO NO On very next day i.e  on 11/N.A8/2N.A14 that transformer shifted at safe place and new earthling connection provided and also all LT bare conductor replaced by AB cable.
117 JAMNAGAR Jamnagar,A cow of Tinabhai Khimabhai Aambaliya 11-8-14  FA As per the the telephonic  messg the site was visited were water logging nearby TC ,primary reason is not found However due to any other unknown source leakage current is suspected at water logging near TC due to water logiing earth leakage current passin NO NO NO On very same day i.e on Dt (11/N.A8/2N.A14) that transformer shifted at safe place and new earthling connection provided and also all LT bare conductor replaced by AB cable
118 JAMNAGAR Jamnagar,A male got of Ismail Kadar Manek 15-8-14  FA Due to arrangement of meter by pass at consumer premises named babulal Madhavji bedi gam con no 32202016325 main service wire insulation was broken by the consumer near the meter box and extra wire was connected to the main service for to By pass the mete N.A N.A N.A Continuous instalation & cheking work done
119 JAMNAGAR Gorakhdi,A Buffalo of Trikam Gangdas Vasoya 17-8-14  FA The buffalo came in contact of the broken LT Conductor (Main Side)and leakage current flew in bufllow body and got electric shock and died CEI REPORT AWAITED N.A N.A All field offices are instructed to replace old deteriorated conductor and to carry out maintenance of lines by resagging loose span, tightening of loose guys, etc.
120 JAMNAGAR Dared,A Buffalow of Hahabhai Jungabhai Gujariya 24-8-14  FA Due to the PIN fault occurred on location no BSS/CHELA/58/R025 hence conductor was snapped and touched to the lower part of Buffalow and fatal accident occurred NO NO NO Same day on (24/N.A8/2N.A14) maintenance carried out and replace the faulty pin departmentaly
121 JAMNAGAR Jamnagar,A buffalow of Lilabhai Malde abha Keshavala 26-8-14  FA Due to unauthorised live electic  fencing of iron wire to  cover ag land of shree vijay Rambhai Keshavala for keeping animal away and protect the agriculture land. with same fencing the buffalo while passing near the fencing its tail came in contact with  NO NO NO FIR is launched in local police station against Shree Vijaybhai Rambhai Keshavala vide letter no. RSD/TECH/2698/3N.A.8.14 and also his AG connection Consumer No. 32557/N.AN.A461/8 had disconnected.
122 JAMNAGAR Amara,Jayesh Lalitbhai  Parekh  27-8-14  NFHD As per the telephonic information given by line staff on Dt. 27.08.2014 to undersigned   has visited accident site on next day i.e on 28.8.2014 and he has found that victim Shri J L Parekh was working on Ag Transformer center and  suddenly victim came in  NO NO NO Necessary maintenance work had been taken up and against this accident all line staff has got aware has to not repeat such type of incidence in future.

123 JAMNAGAR Khandhera,Two Buffalo ofNathabhai Shivabhai Vaghela 1-9-14 NFHOS The accident occurred at the time of snapping of LT conductor from LT Pole of Jethabhai L Hirpara in Laxmipur AG feeder while buffalo came in contact with the live wire and met with accident .this LT Conductor was snap due to rain. The above matter is dis AWAITED AWAITED NA Public awaareness campaign is carried out during fairs and in news papers for accident prevention
124 JAMNAGAR Rangpar,2 Buffalo of Kara Paba Gagiya 2-9-14  FA 2 buffalo got electric shock due to hevay wind pressure amd rain snapping of LT line conductor which fall on two buffalo both came in contact with live conductor and got a electric shock and died NO NO NO The maintenance of the location was carried out On Dt. N.A1.1N.A.2N.A14 properly after the accident done through Department.
125 JAMNAGAR Jamnagar,Kishor Ramji  Kanzaria 5-9-14  NFHD On the Staggering Day Various kind of maintanance works were arranged along with noted carried out temporary works during the week long period at GIDC-III and GIDC-II Dared So shree C L Parmar and K R Kanjaria E.A had to attend the maintanace works of 63  NO NO NO           Notice will be issue to the kishor Kanzariya for very sensitive mistake.
126 JAMNAGAR madhapar,Ranjanben Kumarbhai Vikani 9-9-14 NFHOS Victim was taking  soaked clothes on terrace one corner of this teraace is built under 11 KV Bodaka JGY feeder and the victim s right hand burned and finger got demaged  AWAITED AWAITED NA Public awaareness campaign is carried out during fairs and in news papers for accident prevention
127 JAMNAGAR Jamnagar,Piyush Sureshbhai Rathod 12-9-14 FHOS Victim was moving on terrace may extended his body parts towards 11 KV line Passing near the parafit of thos terrace, This was the extended body part of the victim may come in contect of this live 11 kv line which leads the path of current through victims N.A N.A N.A Notice sent to house owner smt. Salmaben samabhai to remove un authorised extension of terrace towards the 11kv overhead line & keep & maint. The horizontal clearnace from this projected over head 11kv line.
128 BHUJ Siracha, 1 Buffalo, Bhavubha Bhurubha CHAUHAN 3.7.14 FA CONDUCTOR OF 11 KV SHIRACHA AG FDR SNAP DOWN TO EARTH. WHILE PASSING THROUGH EMPTY RIVER BODY OF 3NOS BUFFALO COME IN CONTACT WITH CONDUCTOR & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
129 BHUJ Two  Goat of no owner 22.4.14 FA While investigatation it is found in the preliminary stage, the accident occurred near DHROBANA village. The Two GOAT was moving underneath the 11 KV DHARAMSHALA JGY feeder in DHROBANA VILLAGE Due to pin fault, the top (groove) of the pin broken and the conductor snapped and while falling on ground the TWO GOAT underneath came in contact with live conductor resulted into fatal accident. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
130 BHUJ Two  Goat of no owner 22.4.14 FA While investigatation it is found in the preliminary stage, the accident occurred near DHROBANA village. The Two GOAT was moving underneath the 11 KV DHARAMSHALA JGY feeder in DHROBANA VILLAGE Due to pin fault, the top (groove) of the pin broken and the conductor snapped and while falling on ground the TWO GOAT underneath came in contact with live conductor resulted into fatal accident. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
131 BHUJ Cow of  Devshi Manji Pindoriya 24.4.14 FA A cow passing through the sim area behind sukhpar(roha) village might have came in direct contact of (load side) snapped conductor of 11kv Khirasara ag and got electrocuted.There was no tripping observed during the time period at ss end.                                                                                                                      Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
132 BHUJ 1 BUFFALO  OWNER NAME SHRI RANABHAI REVABHAI BHARAVAD  23.5.14 FA as per telephonic compalin launched by shree butabhai merabhai bharavad to the line office PGVCL adipur s/dn regarding snapping of conductor and line wire fall down on earth near to the to container yard, ioc road side machunagar area village khari rohar and at the same time the one . Buffalo passsing near the snapped conductor and came to this she got electrocatal and resulting in to fatul accident.     note No any tripping occured on 11 kv  11 KV ioc feeder after snapped down the conductor ands came in contace with the earth till acciednert occured  Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
133 BHUJ COW FEMALE AND BUFFALLOW 11.5.14 FA DUE TO HEAVY WIND AND RAIN LT LINE CONDUCTOR IS BROCKEN AT  LATE NIGHT &NO TRIPPING TRIPPING IS OBSERVED AT NIGHT .AT EARLY MORNING ,COW & BUFFALLOW  PASSED THROUH THIS  LOCATATION & COME IN CONTACT WITH BROCKEN CONDUCTOR AND GET ELECROCUTED AND DIED Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
134 BHUJ COW FEMALE AND BUFFALLOW 11.5.14 FA DUE TO HEAVY WIND AND RAIN LT LINE CONDUCTOR IS BROCKEN AT  LATE NIGHT &NO TRIPPING TRIPPING IS OBSERVED AT NIGHT .AT EARLY MORNING ,COW & BUFFALLOW  PASSED THROUH THIS  LOCATATION & COME IN CONTACT WITH BROCKEN CONDUCTOR AND GET ELECROCUTED AND DIED Report yet not received NA NA  
135 BHUJ Siracha, 1 Buffalo, Bhavubha Bhurubha CHAUHAN 3.7.14 FA CONDUCTOR OF 11 KV SHIRACHA AG FDR SNAP DOWN TO EARTH. WHILE PASSING THROUGH EMPTY RIVER BODY OF 3NOS BUFFALO COME IN CONTACT WITH CONDUCTOR & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
136 BHUJ Siracha, 1 Buffalo, Bhavubha Bhurubha CHAUHAN 3.7.14 FA CONDUCTOR OF 11 KV SHIRACHA AG FDR SNAP DOWN TO EARTH. WHILE PASSING THROUGH EMPTY RIVER BODY OF 3NOS BUFFALO COME IN CONTACT WITH CONDUCTOR & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
137 BHUJ Jangi,  Navnit S. Baranda 13.7.14 FHD ON DATED: 13.07.2014 THE 11KV JANGI FDR WAS IN FAULT AND VICTIM HAD GONE WITH LINE STAFF FOR ATTENDING WORK.AFTER COMPLETION OF FDER ATTENDING WORK VICTIM WENT TO JANGI SALT WORKS FOR ATTENDING TELEPHONIC COMPLAINT OF NOT GETTING THREE PHASE POWER OF SALT WORKS. AT TC OF SHRI KANJI VASAN MATA SALT WORK ONE JUMPER WAS FOUND FUSED SO LIMBACHIYA HAD GIVEN INSTUCTION TO A D VANKAR TO OPEN SWITCH. AFTER ISOLATION OF 11 KV SWITCH SHRI VANKAR HAD INFORMED TO SHRI LIMBHACHIYA THERE IS ONE JUMPER DIRECT OF SWITCH BUT CONCERN NOT TAKE IT SERIOUS . VICTIM CLIMED ON TC HAVING LIVE ONECONDUCTOR OF 11 KV JANGI FDR. AND SUDDENLY HE CAME IN CONECT WITH LIVE CONDUCTOR AND GOT SHOCKED AND FELL DOWN AND WAS DECLARED EAD. THUS FATAL HUMAN CCIDENT OCCURED. Report yet not received NA NA All are instructed to utilize safety gadgets.
138 BHUJ  Bhuj,Cow , MAHESHBHAI MARAJ 17.7.14 FA COW WAS PASSING THROUGH THE HOUSE AND DUE TO WIRING PROBLEM IN THE CONSUMER PREMISES THE POWER COMES TO THE WALL OUT SIDE OF THE HOUSE THE COW CAME IN CONTACT TO THE WALL AND GOT ELECTROCUTED AND DIED. Report yet not received NA NA in consumer premises, after verification and test report power supply given. 
139 BHUJ Kanpar, 1 Goat , GOVIND LADHA CHARANIYA 18.7.14 FA 3 NOS OF GOATS PASSING THORUGH THE KANPAR SIM AREA NEAR KANPAR VILLAGE CAME IN CONTACT OF SNAPPING OF CONDUCOTOR OF 11KV ANANDSAR AG DUE TO PIN FAULT AND GOT ELECTROCUTED . Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
140 BHUJ Kanpar, 1 Goat , GOVIND LADHA CHARANIYA 18.7.14 FA 3 NOS OF GOATS PASSING THORUGH THE KANPAR SIM AREA NEAR KANPAR VILLAGE CAME IN CONTACT OF SNAPPING OF CONDUCOTOR OF 11KV ANANDSAR AG DUE TO PIN FAULT AND GOT ELECTROCUTED . Report yet not received NA NA  
141 BHUJ Kanpar, 1 Goat , GOVIND LADHA CHARANIYA 18.7.14 FA 3 NOS OF GOATS PASSING THORUGH THE KANPAR SIM AREA NEAR KANPAR VILLAGE CAME IN CONTACT OF SNAPPING OF CONDUCOTOR OF 11KV ANANDSAR AG DUE TO PIN FAULT AND GOT ELECTROCUTED . Report yet not received NA NA  
142 BHUJ Samagoga, Parmaben A. Seda 20.7.14 FHOS LT LINE CONDUCTOR OF RAJDE SUMAR (G6 ) TC GRUP SNAP DOWN TO FENCING OF FARM.VICTIM CAME IN CONTACT WITH FENCING LINE & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA All conductor & Fabrication of the LT line of the X’mer centre are  replaced .
143 BHUJ Gandhidham,1 ox 18.7.14 FA 2 ox and 1 ox child were standing under the LT line, LT-shakle at LT pole was broken, due tio which LT  conductors from its both side snapped down while snapping conductor came into contact with three ox and fatal animal acciden occurred . Report yet not received NA NA Arial bunch cable provided at accident palace.
144 BHUJ Gandhidham,1 ox 18.7.14 FA 2 ox and 1 ox child were standing under the LT line, LT-shakle at LT pole was broken, due tio which LT  conductors from its both side snapped down while snapping conductor came into contact with three ox and fatal animal acciden occurred . Report yet not received NA NA Arial bunch cable provided at accident palace.
145 BHUJ Gandhidham,1 Calf 18.7.14 FA 2 ox and 1 ox child were standing under the LT line, LT-shakle at LT pole was broken, due tio which LT  conductors from its both side snapped down while snapping conductor came into contact with three ox and fatal animal acciden occurred . Report yet not received NA NA Arial bunch cable provided at accident palace.
146 BHUJ Moti Undoth, Goat , ISMAIL IBRAHIM MANGALA 21.7.14 FA WHENEVER 11 KV POWER PASSING IN PADAMPUR AG FDR ON THAT TIME PIN WAS PUNCHERED AND CONDUCTOER WAS SNAPPED FROM UPPER SIDE OF PIN.ON THA TIME GOAT WAS PASSED FROM THERE AND GOAT TOUCHED WITH LIVE  SNAPPED CONDUCTOR.SO,ACCIDENT WAS OCCURRED. Report yet not received NA NA Maintenance done of this pole with faulty pin replacement and conductor restringing.
147 BHUJ Adersar,Sanava, Pratapsinh A. Baraiya 24.7.14 FHOS AFTER REPLACEMENT OF FAIL TRANSFORMER , THE VICTIM HAD CLIMD ON THE TC STRUCTURE FOR RELEASING THE CHAIN CAMPO SEALING , DURING THE WORK CCIDENTLY HE HAD FELT DOWN ON THE GROUND FROM THE TOP OF THE TC STRUCTURE. AFTER FELLING HE HAS GOT SERIOUS ON HIS HEAD AND MOUTH AND DIED AT SITE.THERE WAS NO ANY EVIDENCE  FOUND  OF CURRENT FLOW AND GOT ELECTOCUTED.  Report yet not received NA NA All vendors have instructed to all workors must be use safety gadgets.
148 BHUJ Anjar,  1 cow 24.7.14 FA DUE TO PUNCTURE IN LT SHACKLE INSULATOR, LEAKAGE CURRENT CAME INTO GURDER POLE AND COW AND OX NEAR TO THE GURDER POLE GETS ELECTROLUTED AND DIED. Report yet not received NA NA By replacement of shackle insulator.   
149 BHUJ Anjar, 1 ox,  24.7.14 FA DUE TO PUNCTURE IN LT SHACKLE INSULATOR, LEAKAGE CURRENT CAME INTO GURDER POLE AND COW AND OX NEAR TO THE GURDER POLE GETS ELECTROLUTED AND DIED. Report yet not received NA NA By replacement of shackle insulator.   
150 BHUJ Vayor, 1 Buffalo , DILUBHA JETHUBHA JADEJA 25.7.14 FA Durinng passing on road side buffalo touched the guy wire which was live as AB cable insulation was broken due to frictoin and died. Report yet not received NA NA detoriated ABC cable replaced and maintanance work carried out.
151 BHUJ Dhrobana,  1 cow 29.7.14 FA   Report yet not received NA NA After the accident took place on Dt 29/7/14 the faulty 11Kv pin insulator was replaced and snap conductor also replaced on same day and power supply was restored. Then on 30/7/2014 the maintenance of 11kv Dharamsala JGY feeder was arranged and restring of all the loose spans was done & at three location pole under line was also erected 7 no. of disc insulators were also replace while maintenance
152 BHUJ Dhrobana, 1 cow 29.7.14 FA   Report yet not received NA NA After the accident took place on Dt 29/7/14 the faulty 11Kv pin insulator was replaced and snap conductor also replaced on same day and power supply was restored. Then on 30/7/2014 the maintenance of 11kv Dharamsala JGY feeder was arranged and restring of all the loose spans was done & at three location pole under line was also erected 7 no. of disc insulators were also replace while maintenance
153 BHUJ Sayra, 1 Cow, MAHESHWARI DADU PACHAN 31.7.14 FA AT village sayara, Due to rain the surface ground is wet & water is filled near the PSC pole. A LT line conductor binding was snapped
due to heavy wind and rain and touch with LT cross arm. The leakage current flow through LT cross arm to GI wire of pole earthing and create potential near PSC pole. At that time cow passing near pole came in contact with GI wire and got electric shock and died.
Report yet not received NA NA maintanace cariied out to this place.
154 BHUJ Samagoga, Omkarsing Mansing 5.8.14 FHOS TRAILER LOADED WITH PIPES IS PARK UNDER 11 KV KAPAYA JGY LINE.VICTIM THROW THE CHAIN FROM ONE SIDE TO ANOTHER SIDE OF TRAILER TO BIND THE PIPES.CHAIN TOUCH THE LIVE CONDUCTOR WHICH PASSES ABOVE THE TRAILER .HENCE  CONDUCTOR ONE PHASE BROKEN & FALL ON VICTIM.SO VICTIM FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA Awarness to people for not Park the vehicle under 11 KV or LT network & don’t do such type of work. 
155 BHUJ Mandvi, Anil Yadav 5.8.14 NFHOS WHENEVER CONSTRUCTION WORK WAS CARRIED OUT BY VICTIM UNDER 11 KV CITY FEEDER.DURING CONSTRUCTION WORK VICTIM WAS SITTING ON WOODEN SUPPORT.ON THAT TIME HIS LEFT HAND TOUCHED 11 LINE CONDUCTOR R-PHASE.SO NON FATAL ACCIDENT OCCURRED. Report yet not received NA NA Issue notice for stop construction work.
156 BHUJ hareshbhai khimabhai koli 9.6.14 NFHOS on the 9.06.14 during morning approcimetely 7:30 hrs victim shri hareshbhai khimabhai koli aged 12 year come in contect witrh lie wire of 11 kv GIDC feeder. due to technical fault the wire hed brocken from the shakle pole near the pin and wire connected to the jumper hence conductor sug has increaed and conductor was about 7 ft from the ground level. The victim went there along with his parterner shri dilidp valjibhai rathod for collecting iron srcrap from the brokenpole lying benecth the line. the victim unawre that he will get shock he tried to cutch the wire with his right hand and got electric shock ( as per the statement of the victim) on investigation it is faund that the line clearence from the ground noremal wire broken and hanging with the jumper the clearenc with the grond was appere 7 ft ( as per the statement of the line staff who attend the line was attend looking to the burnes in the hand of the victim he might have technical the live wire either with iron rod or jumper and tried to pull the wire and leakege current hence had passed from hand to the ground  CONNECTED TO THE SUMPLE, HENCE THE CONDUCTOR SUG HAS INCREASED AND CONDUCTOR WAS ABOUT 7 FT FROM THE  Report yet not received NA NA maintanace cariied out to this place.AND diffective parts was removed to avoid acccident in future.
157 BHUJ M.M.Khombhal 19.4.14 NFHD Shri M.M.Khombhal climb up the LT pole for attending the service line complain. During this  by mistake  his hand came in contact with live part of sercive wire and got electric  shock .  He  fall down on land & got minor injury. Report yet not received NA NA Show cause notice issed to avoid utilize of safety gadgets
158 BHUJ Sinugra, Hasmukh J. Solanki 8.8.14 NFHD IN 11 KV RAMCO JGY FEEDER, WHILE DOING BURNT JUMPER WORK, CONDUCTOR OF SINUGRA AG FDR( CROSSING) TOUCH TO IT & DUE TO SHOCK, VICTIM FALL DOWN Report yet not received NA NA By using AB Cable specially near crossing and keeping proper clearance between
two feeders  are prevents  this type of accident.
159 BHUJ Bayath,  A. C. Kasta
A. G. Matang
10.8.14 NFHD WHENEVER PADAMPUR AG FEDDER CONDUCTOR WAS BROKEN ON THAT TIME ONE ELE.ASI WAS WORKED ON SHACKLE POINT POLE AND REPAIR CONDUCTOR AND ANOTHER ELE.ASSI.WAS WORKED AT LST TC STRUCTURE ON,DO JOINT CONDUCTOR AT DISC.ANY HOW CURRENT BOTH SIDE.SO NON FATAL HUMAN ACCIDENT OCCURRED BOTH EMPLOYEE. Report yet not received NA NA Maintenance done of this pole with old conductor replacement and conductor restringing of padampur Ag feeder at point of LST TC structure of shackle point.
160 BHUJ Bayath, 
A. G. Matang
10.8.14 NFHD WHENEVER PADAMPUR AG FEDDER CONDUCTOR WAS BROKEN ON THAT TIME ONE ELE.ASI WAS WORKED ON SHACKLE POINT POLE AND REPAIR CONDUCTOR AND ANOTHER ELE.ASSI.WAS WORKED AT LST TC STRUCTURE ON,DO JOINT CONDUCTOR AT DISC.ANY HOW CURRENT BOTH SIDE.SO NON FATAL HUMAN ACCIDENT OCCURRED BOTH EMPLOYEE. Report yet not received NA NA  
161 BHUJ Ler, 1 Cow, Rabari Megha Kana 24.8.14 FA DUE TO RAIN , DISC INSULATOR PUCTURED AND BROKEN DOWN , FEEDER NOT TRIPPED , ONE COW COME WITH CONTACT WITH POLE AND GOT ELECTROLUTED. Report yet not received NA NA To avoid this type of accident disk insulator was replaced and JE GETCO was inform about nonworking of 11kv panel relay of 11KV Laheriya Ag Feeder, 66 KV Bhujodi S/S. On dtd 24/08/2014 at 19:00 hours. 
162 BHUJ Dayapar, Ranmalji M. Jadeja 27.8.14 FHOS A fatal accident occurred to shree Ranmalji Modji Jadeja human outsider of village Mudhan at location Mudhan ag vistar under 11 kv Ghaduli AG feeder dated 27/08/2014. During visit at site it is concluded that 11 kv conductor is broken at tc center. There may be chance of fatal accident due to snapping of conductor but there is no any spark at land where snapped conductor fall near by accident place and no any human body parts like skin etc found in broken conductor. Cause of death wiil be found after further investigation and P.M.report received. Report yet not received NA NA as per investigation and P.M report
163 BHUJ RAJDEEPSINH VIKRAMSINF JADEJA 20.6.14 FHOS WHILE PLANNING ON THE TERRACE OF UNDER CONSTRUCTION HOUSE VICTIM CAME IN CONTACT WITH LT LINE PASSING NEAR HUSE. Report yet not received NA NA STOP CONSTRUCTIONWORK AT THIS PLACE
164 BHUJ Nagalpar Moti, Virmaram Idamram 31.8.14 FHOS While Victim has parked hydraulic type truck ( Dumper) under 11 kv sinogra Ag fdr line and trolley of truck was lifted upper side by hydraulic and touch to live 11kv wire and direct current pass through metallic body and driver met with fatal accident on driver sheet. Report yet not received NA NA Awareness regarding safe use of electricity and safety rules are prevents  this type of accident
165 BHUJ Gandhidham, 1  Cow 1.9.14 FA Transformer centre located nr plot no 273 ward 10/A under 11kv gurukul feeder, it was raining interminently on  dt 1.9.2014. and leakage current of neutal via earth was observed on visit to site and as it was raining, fault current flowed through neutral earth wire near TC and one cow while passing near the pole & TC which was waterlogged at that time came into direct contact with earthwire which was having leakage current and this live contact led to electrocution of cow.  Report yet not received NA NA Maintanance and earthing work  carried out this location. 
166 BHUJ Maska,1   Cow (Hasan H. Sumra) 3.9.14 FA THERE WAS ONE COW WITH HER OWNER WAS PASSING FOR DRINKING THE WATER IN FORNT OF TRANSFORMER CENTER AND SHE WAS ABOUT 15 FEET FAR FROM T/C AS PER OWNER'S STATEMENT . THE PHASE WIRE OF 3 RD LT SPAN AFTER THE T/C WAS BROKEN AND IT WAS CAME IN CONTACT WITH NEUTRAL WIRE SO,RETURN POWER WAS CAME IN TRANSFORMER CENTER EARTHING.SO,WHEN THE COW WAS PASSING.SHE WAS ATTRACTED TOWARDS THE TRANSFORMER CENTER AND GET ELECTROCUTED AND DIED. Report yet not received NA NA Maintanance and earthing work  carried out this location. 
167 BHUJ Vandhiya,1  Cow,  LALJI RANCHHOD DEVDA 9.9.14 FA  On dated 9.9.14 .approx  at 06.00 hours due to heavy rain fall and heavy wind pressure the tree branch of Neem falls down to LT line conductor. So, the LT Iive conductor got snapped and falls on the cow passing through stree  under and came in
contact with the live conductor & got electric shock and the cow died on the spot.
Report yet not received NA NA LT Arial Bunch provided at both span restringing done, earthing pipe new jumper 
     done at this place. 

168 BHUJ Khedoi, 1 Cow , RAJENDRA SING GANUBHA JADEJA 22.9.14 FA while cow passes under 11 KV line at that time line conductor Brocken and fallen on cow and animal fatal accident occurred Report yet not received NA NA lt conductor restringing done and complete maintanance carried out.
169 Junagadh SHRI VASIMBHAI RAJUBHAI BLOACH  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH 41756 NFHOS VICTIM CLIMBED ON TRANSFORMER CENTRE TO CATCH HIS PET BIRD (PIGEON) AND DURING THIS HE SOME HOW CAME IN CONTACT WITH LIVE PART AND MET WITH NON FATAL ELECTRICAL ACCIDENT. Not yet received Not yet received Not yet received FIR done against the victim 
170 Junagadh SHRI BHAGAVAN RAMBHAI BABARIA / KAMLESH KARABHAI BABARIA  VILLAGAE: VERVA   TALUKA:MANAVADAR 41774 FHOS VICTIM WAS SITTING ON TRUCK WHICH WAS FULLY LOADED WITH COTTON AND OVER HEIGHT AND TOUCHED WITH LIVE 11 KV FEEDER LINE WHILE HE WAS REMOVING CABLE & SERVICE WIRE WHICH WAS OBSTACLES TO THE COTTON GOODS AND MET WITH THE FATAL ACCIDENT, DETAIL INVESTIGATION UNDER PROCESS.

Not yet received Not yet received Not yet received FIR done against the victim 
171 Junagadh SHRI ASFAK ALLIMAHMAD SORTHIA (RENTAL)  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH 41778 NFHOS VICTIM WHILE OPENING THE BALCONY OF HIS BUILDING SOME HOW CAME IN CONTACT WITH 11 KV LINE AND CAME IN EITHER DIRECT OR INDIRECT CONTACT WITH 11 KV LINE AND GOT ELECTROCUTED AND MET WITH NON FATAL ELECTRICAL ACCIDENT. THE BALCONY IS TOTALLY ILLEGAL.

Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
172 Junagadh SHE BUFFALO OF SHRI DEVAJIBHAI DAYABHAI RATHOD      VILLAGE: BARVALA   TALUKA: BHESAN 41790 FA BUFAALO WHILE GRASSING CAME IN CONTACT WITH FENCING OF MOBILE TOWER  AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT.  Not yet received Not yet received Not yet received Proper maintenance done in the same group.
173 Junagadh SHE BUFFALO OF SHRI ABUBHAI  MULADAD  BLOCH      VILLAGE: JAVANTRI   TALUKA: TALALA 41803 FA DUE TO CYCLONIC PRESSURE IN ARABIAN SEA, HEAVY WIND PRESSURE WAS THERE AND AS A RESULT SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS CONDUCTOR AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
174 Junagadh SHE BUFFALO OF SHRI GANDA BHAI RAMBHAI KANALA      VILLAGE: JAVANTRI   TALUKA: TALALA 41803 FA DUE TO CYCLONIC PRESSURE IN ARABIAN SEA, HEAVY WIND PRESSURE WAS THERE AND AS A RESULT SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS CONDUCTOR AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
175 Junagadh COW (INDIAN) OF SHRI SAMATBHAI RAMBHAI VANIYA      VILLAGE: JAVANTRI   TALUKA: TALALA 41803 FA DUE TO CYCLONIC PRESSURE IN ARABIAN SEA, HEAVY WIND PRESSURE WAS THERE AND AS A RESULT SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS CONDUCTOR AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
176 Junagadh KUMARI DIVYABEN JITENDRABHAI LALVANI  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH 41805 FHOS DURING HEAVY RAIN VICTIM CAME IN CONTACT WITH DETERIORATED LIVE PART OF INTERNAL HOUSE WIRING AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
177 Junagadh LEOPARD OF  FOREST DEPARTMENT        VILLAGE: UMERETHI   TALUKA: TALALA 41819 FA DUE TO FAILURE OF PIN INSULATOR CONDUCTOR SNAPPING TOOK PLACE AND DURING THIS NO TRIPPING WAS OBSERVED DUE TO SINGLE PHASING OF FEEDER. AT 7:15 THE FEEDER WAS CHARGED FOR GIVING THREE PHASE POWER AND AS IT WAS NOT GETTING CHARGED SO TRIES WERE GIVEN AS PER NORMS AND DURING THIS LEPORD MIGHT HAVE COME IN CONTACT WITH SNAPPED CONDUCTOR AND MIGHT HAVE MET WITH FATAL ACCIDENT. DETAIL INVESTIGATION UNDER PROCESS. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
178 Junagadh CALF OF  KANTILAL  MOHANBHAI PARMAR      VILLAGE: GANTHILA   TALUKA: VANTHALI 41806 FA A FATAL ACCIDENT OCCURRED TO A MALE CALF DUE TO LEAKAGE CURRENT FROM THE EARTHING AT TRANSFORMER. CALF CAME IN DIRECT CONTACT WITH LEAKAGE CURRENT OF EARTHING CURRENT AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
179 Junagadh SHRI RAMBHAI  JESINGBHAI MALIVAD  VILLAGAE: MENDERDA   TALUKA:MENDERDA 41830 NFHD A MECHANICAL ACCIDENT OCCURRED TO SHRI RAMBHAI JESHINGBHAI MALIVAD DUE TO SLIPPING DURING LT MAINTENANCE ACTIVITY.

Not yet received Not yet received Not yet received Action taken agaisnt the employee for careless ness in work.
180 Junagadh      VILLAGAE: DOLATPARA   TALUKA:JUNAGADH 41831 FA DUE TO RAIN AND WATER LOGGING NEAR TRANSFORMER CENTRE IN SPITE OF PROVIDING PVC RIGID PIPE TO THE EARTHING WIRE, COW GRASSING NEAR THE TRANSFORMER CAME IN CONTACT WITH LEAKAGE EARTHING CURRENT AND GOT ELECTROCUTED AND MET WITH FATAL ANIMAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
181 Junagadh SHRI KANTIBHAI RUDABHAI BAGDA  VILLAGAE: RAVANI(K)   TALUKA:VISAVADAR 41846 FHD VICTIM MAY CLIMBED ON 11 KV DP OF AG FEEDER HAVING GO SWITCH TO OBSERVE JUMPER DUE TO COMPLAIN OF DEEM VOLTAGE TO Ag. CONSUMERS, AT THAT TIME HE MIGHT BE SUDDENLY CLIMBED ON MORE HEIGHT AND HIS HANDS MAY GOT INDUCTION SHOCK AND  FALL DOWN FROM HEIGHT AND DUE TO MECHANICAL INJURY IN HIS BODY ACCIDENT IS CONVERTED INTO FATAL. THERE IS NO DIRECT EYEWITNESS OF THIS ACCIDENT. FURTHER INVESTIGATION IS UNDER PROCESS. P.M. REPORT IS AWAITING.THERE IS NO TRIPPING ON 11KV SUKHPUR AG FEEDER NEAR ABOUT THE TIME OF ACCIDENT PERIOD. Not yet received Not yet received Not yet received Shaw cause notice issued to Deputy Engineer.
182 Junagadh SHE BUFFALO OF SHRI MULUVALA RANAVALA VALA      VILLAGE: NAVAGAM   TALUKA: JUNAGADH 41848 FA IN LT LINE CONDUCTOR OF PRABHU NA PIPADA VALU GROUP OF 11 KV KHADIA AG FEEDER CONDUCTOR SNAPPED AND FALLING DOWN ON THE GROUND (RETURN CONDUCTOR)AND  BUFFELO GETTING LIVE CONTACT WITH CONDUCTOR. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
183 Junagadh SHE BUFFALO OF SHRI DEVABHAI  RAJABHAI  DODIYA      VILLAGE: ANANDPARA   TALUKA: SUTRAPADA 41850 FA DUE TO LEAKEAGE CURRENT NEAR WATER LOGGING AREA NEAR TRANSFORMER LEAKEAGE CURRENT FROM TRANSFOMER. DUE TO THIS LEAKEAGE CURRENT THE BUFFALO GOT ELECTROCUATED AND MET WITH FATAL ANIMAL ACCIDENT.DETAIL INVESTIGATION IS UNDER PROCESS. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
184 Junagadh GOAT OF SHRI JAGABHAI DEVSHIBHAI MEVADA      VILLAGE: GOVINDPUR   TALUKA: VISAVADAR 41850 FA FENCING OF FARM WAS DIRECTLY CONNECTED TO THE LT POLE EARTH WIRE. GOAT CAME IN DIRECT CONTACT WITH THE LEKEAGE CURRENT IN EARTH WIRE CAME IN CONTACT THROUGH THE FENCING AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
185 Junagadh SHE BUFFALO OF SHRI NIZAR KASAM SORATHIYA      VILLAGE: CHITRAVAD   TALUKA: TALALA 41853 FA DUE TO HEAVY WIND & RAIN TREE BRANCH FELL DOWN  ON THE LT LINE CONDUCTOR, DUE TO THIS SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS FALLEN LIVE WIRE AND  IT GOT ELECTROCUTED & MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
186 Junagadh COW (INDIAN) OF SHRI RAJSHI  HAMIR BHOLA      VILLAGE: LODHAVA   TALUKA: SUTRAPADA 41854 FA THERE WAS A MINOR LEAKEAGE CURRENT NEAR WATER LOGGING AREA NEAR  LT POLE OF TRANSFORMER CENTRE . THE COW CAME IN CONTACT WITH THIS LEAKEAGE CURRENT GOT ELECTROCUATED AND MET WITH FATAL ANIMAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
187 Junagadh SHE BUFFALO OF SHRI RAJSHI  HAMIR BHOLA      VILLAGE: LODHAVA   TALUKA: SUTRAPADA 41854 FA THERE WAS A MINOR LEAKEAGE CURRENT NEAR WATER LOGGING AREA NEAR  LT POLE OF TRANSFORMER CENTRE . THE BUFFALO CAME IN CONTACT WITH THIS LEAKEAGE CURRENT GOT ELECTROCUATED AND MET WITH FATAL ANIMAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
188 Junagadh COW (INDIAN) OF SHRI DEVABHAI JADAVBHAI VADHER      VILLAGE: PANDVA   TALUKA: VERAVAL 41864 FA DUE TO HEAVY WIND & RAIN, LT LINE CONDUCTOR SNAPPED FROM INSULATOR AND WAS HANGING ON "C" CLAMP WHICH RESULTED IN EARTH LEAKEAGE. ANIMAL GRASSING NEAR LT POLE CAME NEAR TO THIS AFFECTED POLE ANS GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
189 Junagadh SHE BUFFALO OF SHRI DEVABHAI JADAVBHAI VADHER      VILLAGE: PANDVA   TALUKA: VERAVAL 41864 FA DUE TO HEAVY WIND & RAIN, LT LINE CONDUCTOR SNAPPED FROM INSULATOR AND WAS HANGING ON "C" CLAMP WHICH RESULTED IN EARTH LEAKEAGE. ANIMAL GRASSING NEAR LT POLE CAME NEAR TO THIS AFFECTED POLE ANS GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
190 Junagadh SHE BUFFALO OF SHRI  SARMANBHAI   HIRABHAI  SINDHAL      VILLAGE: JUNAGADH   TALUKA: JUNAGADH 41866 FA DUE TO HEAVY WIND & RAIN, LT LINE CONDUCTOR SNAPPED FROM INSULATOR AND WAS HANGING ON "C" CLAMP WHICH RESULTED IN EARTH LEAKEAGE. ANIMAL GRASSING NEAR LT POLE CAME NEAR TO THIS AFFECTED POLE ANS GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
191 Junagadh LEOPARD OF SHRI FOREST DEPARTMENT        VILLAGE: MADHUPUR   TALUKA: TALALA 41873 FA LEOP[ORD CLIMBED ON AG DP OF TRANSFORMER APPROX 15 FEET ABOIVE THE GROUND LEVEL AND CAME IN CONTACT WITH DO WIRE/JUMPER AND GOR ELECTROCUATED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received No action taken as animals fault.
192 Junagadh SHRI DILIPBHAI PARBATBHAI JETHAVA  VILLAGAE: SANTALPUR   TALUKA:VANTHALI 41873 NFHOS A NON FATAL ACCIDENT OCURRED TO VICTIM WHILE HE WAS IN PROCESS OF CLEANING HIS TERRACE. DURING THE CLEANING PROCESS HE CAME IN CONTACT WITH NEAR BY LINE PASSING AND GOT ELECROCUTED AND MET WITH NON FATAL ELECRICAL ACCIDENT.  Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
193 Junagadh SHRI  BHAVESHBHAI  PRABHUDAS  AGRAVAT  VILLAGAE: TALALA   TALUKA:TALALA 41872 NFHOS BOTH VICTIMS WERE WORKING IN NAGAR PALIKA TALALA IN STREET LIGHT BRANCH AND WERE INVOLVED IN STREE TLIGHT REPAIRING WORK WITHOUT ANY LINE CLEAREANCE OR PERMISSION. AND WHILE REPARING THE STREET LIGHT THEY CAME IN CONTACT WITH JUMPER OF NEAR BY TRANSFORMER AND GOT ELECTROCUATED & MET WITH NON FATAL ACCIDENT. Not yet received Not yet received Not yet received Letter written to nagarpalika for the same.
194 Junagadh SHRI JUMABHAI  HASAN BHAI  DAL  VILLAGAE: TALALA   TALUKA:TALALA 41872 NFHOS BOTH VICTIMS WERE WORKING IN NAGAR PALIKA TALALA IN STREET LIGHT BRANCH AND WERE INVOLVED IN STREE TLIGHT REPAIRING WORK WITHOUT ANY LINE CLEAREANCE OR PERMISSION. AND WHILE REPARING THE STREET LIGHT THEY CAME IN CONTACT WITH JUMPER OF NEAR BY TRANSFORMER AND GOT ELECTROCUATED & MET WITH NON FATAL ACCIDENT. Not yet received Not yet received Not yet received Letter written to nagarpalika for the same.
195 Junagadh SMT  SHANTABEN  MADHABHAI  RATHOD  VILLAGAE: GOLADHAR   TALUKA:JUNAGADH 41879 NFHOS VICTIM ON TERRACE WAS INVOLVED IN PLUCKING OF VEGETABLE FROM STEMS. DURING THIS WORK AND DUE TO DEW A LIGHT ELECTRIC SHOCK FROM NEARBY 11 KV WAS FELT TO VICTIM AND WAS FALLEN DOWN AND MET WITH NON FATAL  ACCIDENT. THE ROOF HOUSE WAS BUILT UP ILLEGALLY.

Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
196 Junagadh SHE BUFFALO OF SHRI  KANABHAI  KHODABHAI   MAKWANA      VILLAGE: MAJEVADI   TALUKA: JUNAGADH 41880 FA DUE TO HEAVY WIND & RAIN THERE WAS A SHORT CIRCUIT ON THE LT LINE CONDUCTOR, DUE TO THIS SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS FALLEN LIVE WIRE AND  IT GOT ELECTROCUTED & MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
197 Junagadh SHE BUFFALO OF SHRI  SURESHBHAI   BHIKHABHAI  KHUMAN      VILLAGE: NAVI CHAVAND   TALUKA: VISAVADAR 41886 FA DUE TO HEAVY WIND & RAIN THERE WAS A SHORT CIRCUIT ON THE HT LINE CONDUCTOR, DUE TO THIS SNAPPING OF CONDUCTOR TOOK PLACE AND BUFFALO CAME IN CONTACT WITH THIS FALLEN LIVE WIRE AND  IT GOT ELECTROCUTED & MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
198 Junagadh SHRI  RAJESHBHAI   PITHABHAI  RANVA  VILLAGAE: SHAPUR   TALUKA:VANTHALI 41884 FHOS  VICTIM CAME IN DIRECT CONTACT WITH 11 KV VELNATH JGY LIVE WIRE. VICTIM ILLEGALLY CONSTRUCTED THE BUILDING WHICH WAS ILLEGAL IN NHAI AND PGVCL NORMS, AND WHILE STANDING ON THE ROOF/WALL VICTIM SOME HOW CAME IN DIRECT CONTACT WITH LIVE CONDUCTOR AND GOT ELECTROCUATED AND MET WITH FATAL HUMAN ACCIDENT. Not yet received Not yet received Not yet received Notice for illegal construction given to owner.
199 Junagadh SHRI LAKHMANBHAI SURABHAI BAMANIYA  VILLAGAE: KANAVADLA   TALUKA:VISAVADAR 41894 NFHD AFTER REPLACEMENT OF TRANSFORMER CENTRE OF WATER WORKS ,VICTIM WAS BINDING D.O FUSE WITH THE HELP OF PLIER AND THAT TIME LINE CLEAR WAS RETURNED.AS A RESULT HE GOT ELECTRIC JERK AND MET WITH NON FATAL ACCIDENT.  Not yet received Not yet received Not yet received Explaination asked from EE and DE for the same.
200 Junagadh SHRI  KIRITKUMAR   DHIRAJLAL  PANDYA  VILLAGAE: BHALGAM   TALUKA:VISAVADAR 41897 NFHD VICTIM WAS PERFORMING JUMPERING WORK WITH LINE CLEAR AND DURING THIS PERIOD POWER WAS FEED FROM UNKNOWN POWER SUPPLY AND HE GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT.  Not yet received Not yet received Not yet received Explaination asked from EE and DE for the same.
201 Junagadh SHRI  SATISHBHAI  RAMBHAI  JASVANI  VILLAGAE: VERAVAL   TALUKA:VERAVAL 41900 NFHOS ACCIDENT TOOK PLACE DUE TO BLASTING OF CTPT UNIT OF HT CONNECTION OF M/S GOPAL SEA FOODS. DUE TO BLAST OF CT PT UNIT VICTIM CAME IN CONTACT WITH HOT OIL OF THE UNIT AND MET WITH BURNT INJURIES. Not yet received Not yet received Not yet received As its an incident no action taken.
202 Junagadh SHRI  SURESHBHAI  PREMDAS  MESVANIA  VILLAGAE: VADLA   TALUKA:VANTHALI 26-09-14 NFHD VICTIM WAS PERFORMING JUMPERING WORK WITH LINE CLEAR AND DURING THIS PERIOD POWER WAS FEED FROM UNKNOWN POWER SUPPLY AND HE GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT.  Not yet received Not yet received Not yet received Explaination asked from EE and DE for the same.
203 Junagadh SHE BUFFALO OF SHRI BHAYABHAI GOVINDBHAI GAMARA      VILLAGE: BHESAN   TALUKA: BHESAN 18-08-14 FA LT LINE CONDUCTOR BROKEN FROM FAULTY SHACKLE INSULATOR,  BUFFALO CAME IN DIRECT CONTACT WITH SNAPPED CONDUCTOR AND GOT ELECTROCUTED AND MET WITH FATAL ACCIDENT. Not yet received Not yet received Not yet received Proper maintenance done in the same group.
204 Bhavnagar Royal  -  Buffalo &  Ghohabhai Savajibhai Parmar- ( Owner ) 21-04-14 FA Non-Fatal Human & Fatal Animal accident occured due to Cyclonic high Wind flow, LT Conductor snapped & fell on fencing wire of farm and Buffalo tied near the fencing wire & got electrocuted & same time Victim Smt. GG Parmar tried to save his animal ( buffalo ), so she also got the electric shock  Report yet not received NA NA lt conductor restringing done and treecutting with complete maintanance carried out.
205 Bhavnagar Royal  -  Gomatiben Ghoghabhai Parmar 21-04-14 NFHOS Non-Fatal Human & Fatal Animal accident occured due to Cyclonic high Wind flow, LT Conductor snapped & fell on fencing wire of farm and Buffalo tied near the fencing wire & got electrocuted & same time Victim Smt. GG Parmar tried to save his animal ( buffalo ), so she also got the electric shock  Report yet not received NA NA lt conductor restringing done and treecutting with complete maintanance carried out.
206 Bhavnagar Navagam  -  Rohitbhai Velabhai Rathod 01-05-14 FHOS Gross negligency & Violation of sefty measures  during Victim was  Standing  on compound Wall with Iron Rod approx 17.5 ft long  & at the time upper side of iron Rod came in contact with 11 KV line & got electric shock and met with Fatal accident. Report yet not received NA NA Gross negligency by victim & Public awarness
207 Bhavnagar Bhavnagar  -  Pravinbhai Devajibhai Maru -EA 08-06-14 FHD While Working on girder pole, the pole broke down from bottom & Victim along with girder fell on the ground & succumbed to head injuries. Report yet not received NA NA Done Survey of all Girder pole and replaced deteriorated pole from bottom,If required muffing done after fabrication,Support pole provided to tension pole,Reactivated Guy wire to avoid recuuence of such accident.
208 Bhavnagar Navagam  -  Gopalbhai Natavarbhai Umaraliya - I/c Sr.Tech 18-06-14 NFHD Departmental Non-Fatal accident ( electrical burnts ) occurred during CTPT Unit installed at Consumer Premises & suddenly blast and highly flame generated and both of employees got electrical flame & burnt. Report yet not received NA NA CTPT replaced & Now onward more Vigilant during works
209 Bhavnagar Navagam  -  Sanskarbhai Sondabhai Kojani-EA 18-06-14 NFHD Departmental Non-Fatal accident ( electrical burnts ) occurred during CTPT Unit installed at Consumer Premises & suddenly blast and highly flame generated and both of employees got electrical flame & burnt. Report yet not received NA NA CTPT replaced & Now onward more Vigilant during works
210 Bhavnagar Bhavnagar  -  Kaushikbhai Hareshbhai Makawana 09-07-14 FHOS Fatal Human accident occurred due to LT Leakage Current flow from Removed Cotton Tape Open Joint Service Wire to GI Earth Wire. Due to rain & Wind the Soil become muddy & Wet, so he got electric Shock Report yet not received NA NA Earthings are reactivated & rigid PVC pipe is provided.Removed service joints and provided new twin core service.
211 Bhavnagar Ukharala ( Mamsa GIDC)  -  Sanjaybhai Dhirubhai Jadav 10-07-14 FHOS Fatal & Non -Fatal Human accident occurred during both of Victims were tried to bring out under ground Water tank by tripoleStand ( Ghodi ), near / below the 11 KV line at the time,  the Iron Rod of tripole stand touche to 11 KV line & got electric Shock Report yet not received NA NA Ground level below 11 KV line lover down by factory owner 
212 Bhavnagar Ukharala ( Mamsa GIDC)  -  Roshniben Akbarbhai Saiyad 10-07-14 NFHOS Fatal & Non -Fatal Human accident occurred during both of Victims were tried to bring out under ground Water tank by tripoleStand ( Ghodi ), near / below the 11 KV line at the time,  the Iron Rod of tripole stand touche to 11 KV line & got electric Shock Report yet not received NA NA Ground level below 11 KV line lover down by factory owner 
213 Bhavnagar Bhikada  -  Himmatbhai Devajibhai Kansara 12-07-14 FHOS Fatal Human accident occurred during victim was trying to repaired D.O fuse by using wet bamboo in his hand, without taking any permission from PGVCL authority  Report yet not received NA NA Gross negligency by victim & Public awarness
214 Bhavnagar Shivamnagar  -  Uvesh Mustubhai Saiyad 12-07-14 NFHOS Non- Fatal accident occurred due to leakage current passed through TV Cable by Joint of illigal PVC Cable wire & TV Cable by consumer for theft of electricty.    The Deputy Engineer, Gariyadhar-1 Registered Police Complaints on  Illigally  Network Disturbance. Report yet not received NA NA such type cable tv wire remove and booked under theft.
215 Bhavnagar Shivamnagar  -  Mahek Mustubhai Saiyad 12-07-14 NFHOS Non- Fatal accident occurred due to leakage current passed through TV Cable by Joint of illigal PVC Cable wire & TV Cable by consumer for theft of electricty.    The Deputy Engineer, Gariyadhar-1 Registered Police Complaints on  Illigally  Network Disturbance. Report yet not received NA NA such type cable tv wire remove and booked under theft.
216 Bhavnagar Bhavnagar  -  Aryan Arvindbhai Jethava ( Dhobi ) 14-07-14 FHOS Fatal Human accident occurred during Victim was playing & Stand on bricks which are near the PSC Pole and Contact with GI earthing wire and GI wire was already energized with LT leakage current which flow from pole SMC due to insulated tape of red phase of 3-phase cable was damaged. Report yet not received NA NA PVC Cable replace by LT ABC 
217 Bhavnagar Ranparada    -  Buffalo-She & Pathubhai Golanbhai Kamaliya - Owner 18-07-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time buffalo may pass near by transformer centre at came in contact & got electric Shock Report yet not received NA NA TC maintanance done and new earthing provided with pvc rigid pipe
218 Bhavnagar Sanala ( NAVA )  -  Pravinsinh Bhikhubha Sarvaiya 26-07-14 FA Fatal Animal accident occurred due to LT leakage current flow from Transformer Nuetral to Earthing Wire and also due to Rain the leakage current spread near the Transformer Center, and Buffalo may be came in contact with this leakage current &  Potential difference and got electric shock  Report yet not received NA NA TC maintanance done and new earthing provided with pvc rigid pipe
219 Bhavnagar Ratol  -  Buffalo -She & Bachubhai Punabhai Bhaliya - Owner  01-08-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time buffalo may pass near by transformer centre at came in contact & got electric Shock Report yet not received NA NA TC maintanance done and new earthing provided with pvc rigid pipe
220 Bhavnagar lapadiya  -  Buffalo -She &  Pachabhai Bhagvanbhai Vaghela -Owner 02-08-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time buffalo may pass near by transformer centre at came in contact & got electric Shock Report yet not received NA NA transformer center maintanance done and new earthing and new fuse provided.
221 Bhavnagar Kumbhan  -  Cow ( Indian ) &  Anandbhai Rambhai Gamara - Owner 05-08-14 FA Due to Wheather effect Joint Opened between LT Line dropper & Consumer Service & it's touched to Guy wire which have no Guy insulator provided so leakage current flow  from Joint to Guy wire and when Cow passing nearby it, she got electric shock and met with Fatal accident Report yet not received NA NA new stay is provided , also guy insulator provided 
222 Bhavnagar Lilvan  -  Shantubha Kanubha Vala 06-08-14 NFHOS Non-Fatal Human accident occurred during Vicitm stand on tarrace with babared wire in his hand due to gross negligency, the babared wire came in 11 KV Line Induction Zone & got electrical Shock  Report yet not received NA NA required maintainanace carried out at site
223 Bhavnagar Valukad  -  Cow ( Indian ) & Dineshbhai Bijalbhai Baraiya -Owner 08-08-14 FA Fatal Animal accident occurred due to leakage current passed from Transformer neutral  earth wire & also due to rain, the leakage current spread near the transformer center , at that time Cow ( Indian )  passed near by transformer centre at came in contact with Wet Land and due to Potential difference, Cow got electric Shock & died Report yet not received NA NA transformer center maintanance done and new earthing and new fuse provided.
224 Bhavnagar Morchand  -  Bairajba Balvantsinh Gohil 16-08-14 FHOS Due to rain & Wind Pressure LT bare conductor broken and fall down on land and Vicitm may be contact with LIVE Conductor and got electric Shock and  met with Fatal accident Report yet not received NA NA LT line maintenance carried out
225 Bhavnagar Tantaniya  -  Buffalo -She & Vithalbhai Labhubhai Lakkad - Owner 25-08-14 FA Fatal animal accident occurred due to heavy wind & Rain, neutral Conductor of LT line was broken from middle of span & fell on ground at the time buffalo may came in contact with neutral conductor & got electric shock. Report yet not received NA NA AG group maintannce done , also deteriorated conductor replaced and new conductor provided
226 Bhavnagar Kalela  -  Buffalo - She & Babubhai Virabhai Aradu 01-09-14 FA Fatal animal accident occurred buffloes ( Minor & Major ) due to service line GI Wire was brokean & hanging from pole to earth and also it was contact to LT Conductor & Leakage Current flow through GI Wire to Earth. When both  are came in contact with this energised GI wire, they are got electric shock Report yet not received NA NA broken GI wire removed ,Necessory maintainance carried out
227 Bhavnagar Kalela  -  Buffalo - She & Babubhai Virabhai Aradu 01-09-14 FA Fatal animal accident occurred buffloes ( Minor & Major ) due to service line GI Wire was brokean & hanging from pole to earth and also it was contact to LT Conductor & Leakage Current flow through GI Wire to Earth. When both  are came in contact with this energised GI wire, they are got electric shock Report yet not received NA NA broken GI wire removed ,Necessory maintainance carried out
228 Bhavnagar Dihor  -  Lakabhai ( Laxmanbhai ) Bhimabhai Chosala 13-09-14 FHOS One Side guarding wire got snapped between TC  & Pin point , The One Side broken guarding wire was lying beside the river bed, which is not easily approachable From the both the side of river, but As per statement of victims relative ,who reached the site at  around about 5.30 PM, the victim was lying on  river bed, besides the broken guarding wire. The villagers inform village helper ,  he immediately reached at Site and found that no power was Flowing Through Guarding Wire , also there was least  possibility of touching the  live 11 KV line with Guarding Wire, As there is minimum clearance of two feet, so actual reason of this incidence is not found,  How the victim got electric shock. After P.M. report actual reason of this incidence can be known. Report yet not received NA NA re-guarding done properly and complete maintanance carried out of accident place.
229 Bhavnagar Bagadana  -  Lakhabhai Arjanbhai Chavada 26-09-14 NFHOS Non-Fatal Human accident occurred due to Binding of LT Conductor was re-Opened & Conductor was fall into C-Clamp and C-Clamp earthed through GI Wire, So its leakage current to earth but at the time Victim was stand on nearby LT pole in  flood irregation ( Water Canel - Dhoriya ) and contact with leakage current and got electrical Shock  Report yet not received NA NA LT maintannce with all shakal rebinding and new earthing to all poles provided with pvc rigid pipe
230 Bhavnagar Alang  -  Buffalo - She & Budhabhai Vithalbhai Solanki 28-09-14 FA LT Line conductor got damaged in middle part due to babool tree near to the line, & conductor snapped from the middle part, the buffalo when passes through that area where broken wire was lying & came in contact with wire & met with Fatal accident. Report yet not received NA NA lt conductor restringing done and treecutting with complete maintanance carried out.
231 BTD At Village Khopala  , COW OF Shree Devabhai Karshanbhai Bharwad 20.04.14 FA In Evenning 4:45 PM, mini cyclone and rain was falling. Unauthorized gram panchayat Khopala, loud speaker network’s co-axial cable supported by Iron wire was falten on earth and its supported wire touch fuse lead situated on PSC poles, about 6:30 PM owner of Deva bhai Karshanbhai Bharwad’s cow was came in contact with co-axial cable’s iron wire. Cow get the shock and fall down and died. Report Yet Not Received NA NA Required Instruction given to SDO.
232 BTD At village Derala, BUFFALLO OF Shri Vitthalbhai Vashrambhai Miyani 31.05.14 FA In morning 8:00 am,at premises of Shri Vithhalbhai Vashrambhai Miyani 1phase lighting connection,Main Service Twin Wire bind at Iron Hook of Beam situated above Main Iron Gate,the main service wire was break at this iron hook and phase was touched on this hook,leakage current was passed through this hook to beam and Main Iron Gate.Shri Vithhalbhai Vashrambhai Miyani’s Buffallow pass through that iron Main Gate and Came in contact & get the shock and fall down and died. Report Yet Not Received NA NA Rectification Done.
233 BTD At village Kariyani, Shree kantibhai Martabhai katara 18.05.14 NFHD Victim instructed to release new Ag connection of Shri Nagarbhai Gatorbhai of vill kariyani . Victim has installed the meter and to start the jumper work for release of new connection, victim has taken line clear for 11kv Samadhiyala -2 ag feeder instead of 11 KV vajeli ag feeder .due to such mistake of victim, he got electric shock during jumper work and fall down from pole. Report Yet Not Received NA NA (1) C.S. ISSUED TO K M KATARA VIDE NO: BTDN/HR/DA/213, DATED 28.08.14
(2) C.S. ISSUED TO J G MAKWANA (DE) VIDE NO: BZ/HR/DA/BTD/JGM/1303 DATED 31.07.2014 ---POINT 6(2) IN C.S.
(3) SHOW CAUSE NOTICE TO K H TRIVEDI (ALM). BTDN/HR/DISC/154, DATED 02.06.2014
234 BTD At village Haddad, Amit Sureshbhai Belani 20.06.14 NFHD Non-fatal accident occurred to Shri A S Belani, while working on DP structure (11 KV Haddad JGY), has met with electrical shock. The line clear was taken by Y H Multani (EA), and line was also earthed from incoming side, i.e. from is s/s end. Looking to the site position unknown power reflected to 11 KV Haddad JGY feeder at DP Structure. The investigation is going on and detail report submitted after scrutiny of MRI report of relevant AG crossing feeder. Report Yet Not Received NA NA Instructed to all Line staff, Earthing must be done both side of 11 KV Line before statrting of work on line.
235 BTD At village Raliyana, COW OF Shri Harjibhai Bhikhabhai Jogava 17.06.14 FA In afternoon 1:30 P.M., at Balmandir TC village: Raniyala, a cow of Shri Harjibhai Bhikhabhai Jogava’s was passing under TC. Due to wet ground and leakage current to transformer through TC earthing cow came in contact with earthing G.I. wire got shocked. Fall Down and died. Report Yet Not Received NA NA Earthing Reactiveted and Rectification done.
236 BTD At village Nana Paliyad, Buffallo of shri Mansukhbhai  Gordhanbhai 13.07.14 FA Due to heavy rain and wind village TC cable fired and live part of cable touch to guy wire below guy insulator thus current passes through guy wire and buffalo touch to guy wire and got electric shock. Report Yet Not Received NA NA TC Maintenance done.
237 BTD At village Viravadi, Buffallo of Madhabhai Arjanbhai Talvadiya 06.08.14 FA In After noon, mini cyclone and rain was falling. Due to heavy wind, LT Conductor was snapped out and falling down on earth, Buffalo of Shri Madhabhai Arjanbhai Talvadiya was passing nearby snapped conductor and his leg came in contact with live conductor, so, the buffalo got shocked and died. Report Yet Not Received NA NA LT Maintenance done.
238 BTD At village Dhola, Buffallo of shri Bhayabhai Ranabhai Galani 28.08.14 FA The buffalo was wandering to eat the grass and to drink the water near lack. After drinking water it climbs the boundary of lack. The boundary of the lack is at height of 8 feet.  The Langala JGY feeder is   passing over the boundary. The one pole of the feeder, was tilted due to guy was cut by the farmer. Due to height of boundary and tilted pole the distance between the line and the boundary is about 4 feet. The buffalo might have came in contact with conductor and it got shock and died Report Yet Not Received NA NA  
239 BTD At village Kumbhara, Shri Ghansyambhai  Govindbhai Saliya 27.09.14 FHOS When pole carting truck passing under 11 KV Paliyad JGY crossing of 55mm AB Conductor at that time, suddenly by unknown reason, conductor came in contact with pole lifting instrument and victim got electric shock and died.  Report Yet Not Received NA NA  
240 BTD At village Kumbhara, Shri Bharatbhai Mavubhai  Sarakadiya 27.09.14 NFHOS When pole carting truck passing under 11 KV Paliyad JGY crossing of 55mm AB Conductor at that time, suddenly by unknown reason, conductor came in contact with pole lifting instrument and victim got electric shock and died.  Report Yet Not Received NA NA  
241 AMRELI 1 NO OF UNKNOWN COW,RAJULA 14-04-14 FA WHILE REPAIRING WORK WAS DONE BY NAGARPALIKA FOR STREETLIGHT CONNECTION, ONE END (1/18 WIRE) WAS BROKEN AND AT THAT TIME ANIMAL CAME TOUCHED THIS LIVE WIRE AND GOT ELECTROCUTED.  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
242 AMRELI GIGABHAI VIHABHAI SOLANKI,TRAKUDA 16-04-14 FHOS THREE LINE STAFF OF PGVCL – KHAMBHA SUB DIVISION INCLUDING LINE INSPECTOR WERE WORKING ON FIRST D.P. OF 11KV TRAKUDA AG. FEEDER IN YARD OF SUBSTATION FOR REPAIRING ONE JUMPER ON D.P. THE FEEDER WAS MADE OFF AND BREAKER TROLLEY WAS TAKEN OUT BY S.B.O. AS PER INSTRUCTION OF LINE INSPECTOR. AT THE SAME TIME THE LINE INSPECTOR RECEIVED A CALL FROM CONTRACTOR PERSON REGARDING LINE CLEAR OF TRAKUDA AG. FEEDER FOR TAPPING OF AG CONNECTION. THE LINE INSPECTOR INFORMED HIM THAT FEEDER IS OFF & THEY ARE MAKING JUMPER WORK AT YARD & ALSO SAY TO CARRY OUT THEIR TAPPING WORK & INFORM TO HIM AFTER COMPLETION. IN BETWEEN DP JUMPER WORK COMPLETED LINE INSPECTOR FORGET ABOUT CONTRACTOR WORK & INSTRUCT SBO TO ON FEEDER RESULTING OCCURRENCE OF FATAL ACCIDENT.   SHORT CIRCUITING AND EARTHING THE LINE BEFORE EXECUTION OF WORK. THE CONTRACTOR PERSON GOT AN ELECTRIC SHOCK AND DECLARED DEAD AT CIVIL HOSPITAL KHAMBHA. PM REPORT AND DETAIL INVESTIGATION  FOLLOWS. THE CONTRACTOR DOES NOT MAKE LINE EARTH DURING WORK * LINE INSPECTOR HAS NOT TAKEN LINE CLEAR ALSO. -- -- -- LINE INSPECTOR FOUND RESPONSIBLE,HE WAS SUSPENDED AND EDUCATE ALL LINE STAFF DURING LINE WORK
243 AMRELI SHRI ATULBHAI BHIKHABHAI SIDHDHPURA(E.A.),MALAVIYA PIPALIYA 06-05-14 NFHD LIGHTENING STROCK OCCURED IN NEAR VICINITY AND DUE TO FEAR HANDS ARE OPENED AND FALLEN DOWN FROM THE POLE WHILE CLIMBING ON POLE AND MET TO NON FATAL ACCIDENT.  -- -- -- SAFETY AWARENESS AMONG STAFF MADE THROUGH TAINING.
244 AMRELI SHRI MANSUKHBHAI BHURABHAI DOBARIYA,VAVERA 09-05-14 NFHOS A. THE VICTIM CLIMBING ON 63 KVA T/C CENTER FOR REPAIRING OF D.O.FUSE AND TOUCH TO JUMPER LYING BETWEEN D.O.FUSE AND T/C , AND GOT ELECTROCUTED. THE VICTIM RELATIVE DOES NOT INFORM TO PGVCL EMPLOYEE OR OFFICE ABOUT SUCH ACCIDENT BUT SAME IS COME IN TO KNOWLEDGE IN DY.ENGINEER RAJULA RURAL VIDE  RAHULA POLICE STATION LETTE DT:-19.05.14.THE DY.ENGINEER RAJULA RURAL HAS ISSUE NOTICE TO VICTIM BROTHER FOR NON INFORMING PGVCL OFFICE ABOUT ACCIDENT. THE VICTIM BROTHER CONFESS IN HIS STATEMENT THAT VICTIM GOT ELECTROCUTED DUE TO HIS MISTAKE ONLY. THE ALL RELAVANT STATEMENT ATTACHED HERE WITH -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
245 AMRELI SHRI HARESHBHAI VALLABHBHAI VEGAD,LUNIDHAR 11-05-14 NFHOS THE ACCIDENT OCCURRED WHEN VICTIM TRY TO MAKE UNAUTHORIZED WORK ON TRANSFORMER AT HIS FIELD -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
246 AMRELI 1 BUFFALO OF SHRI KATHADBHAI BACHUBHAI GAVTARMOTA, MACHIYALA 11-05-14 FA THE BUFFALO TOUCH TO BROKEN LT LINE WIRE & GOT ELECTROCUTED  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
247 AMRELI B.J.SONDARAVA,UNA 17-05-14 NFHD DURING THE WORK OF  REPAIRING OF BURNT JUMPER OF 11 KV LINE , VICTIM LOOSE HIS BALANCE AND FALL DOWN FROM SHACKLE POLE . IN THIS MECHANICAL ACCIDENT  BOTH LEGS OF VICTIM HAS BEEN FACTURED.  -- -- -- VICTIM HIMSELF RESPONSIBLE AND STRICT DISCIPLINARY ACTION TAKEN FOR NEGLEGENCE OF SAFETY RULES AND REGULATION
248 AMRELI HASMUKHBHAI AMRUTLAL SAPARA,VADIA 22-05-14 FHOS THE ACCIDENT WAS OCCURRED WHEN  A MENTALLY RETIRED MAN CLIMB ON11 KV GIRDER POLE AT THAT TIME HE WAS SUDDENLY FALL DOWN ON GROUND  AND AFTER SOME TIME (APPROXIMATE 2 HRS) HE IS DIED.  -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
249 AMRELI SHRI RANJITBHAI BHARATBHAI KHUMAN(E.A.),ZANZARIYA 31-05-14 NFHD THE ACCIDENT WAS OCCURRED WHEN  VICTIM WAS ATTENDING 11 KV ADIPUR AG FEEDER WITH OTHER TWO LINE STAFF & LINE PETROLLING CARRIED OUT IN FAULTY SECTION OF 11 KV ADIPUR AG FEEDER IN AG AREA OF VILLAGE ZANZARIYA ON ROAD ZANZARIYA KAGADADI JUNA MARAG., NEAR TC OF MAGANBHAI KURJIBHAI SATASIYA THE CAUSE OF ACCIDENT IS SUSPECTED AS STATEMENT OF VICTIM & STATEMENT OF OTHER TWO LINE STAFF UNDER PROCESS. -- -- -- VICTIM HIMSELF RESPONSIBLE AND STRICT DISCIPLINARY ACTION TAKEN FOR NEGLEGENCE OF SAFETY RULES AND REGULATION
250 AMRELI 1 BULLOCK OF SHRI JATASHANKAR SHIVLAL CHAV,BABRA 05-06-14 FA WHEN BULLOCK WERE PASSING NEAR THE LT LINE OF MOTIBAPA VALU T/C OF 11 KV CHARAKHA AG FEEDER LINE,  AT THAT TIME  BROKEN LIVE WIRE WAS CONTACTED  WITH BULLOCK. HENCE ONE BULLOCK WAS DEAD ON THE SPOT. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
251 AMRELI SHRI DINESHBHAI BADHABHAI CHAUHAN(E.A.),JANBAI DERDI 12-06-14 NFHD VICTIM WAS WORKING OF 11 KV TAPPING LINE JUMPER. AT THAT TIME DUE TO BEARY WIND, 11 KV FEEDERS CROSSING TOUCH WITH NEARBY WIRE FOR INSTANT AND VICTIM GOT SHOCK AND FALL DON'N FROM THE POLE. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
252 AMRELI 1 COW OF SHRI BAGHABHAI BHAGVANBHAI LAKHNOTRA,BARPATOLI 13-06-14 FA RAIN IS FALLING IN NIGHT AND IN MORNING ,A COW PASSED BETWEEN TWO PSC POLE OF VILLAGE TC. CAME IN CONTACT OF LEAKAGE CURRENT & GOT ELECTROCUTED -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
253 AMRELI 1 COW OF SHRI GHELABHAI NATHABHAI,NABAPARA 15-06-14 FA ACCIDENT OCCURE  LAND IS WET AROUND THE TC LOCATION CENTRE DUE TO RAINY SEASON ,THE COW PASSED NEAR FROM THE TC LOCATION CENTRE CAME IN CONTACT OF EARTH LEAKAGE & GOT ELECTROCUTED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
254 AMRELI 1 COW OF KANCHANBEN DAYABHAI GOHIL,SANAKHADA 15-06-14 FA RAIN IS FALLING IN MORNING AT DUE TO LEAKAGE CURRENT PASSES THROUGH EARTHING. AT THAT TIME COW WAS PASSING UNDER THIS T/C, COME IN CONTACT WITH EARTHING & GOT ELECTROCUTED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
255 AMRELI 1 COW OF SHRI JASUBHAI KESHUBHAI GOHIL,SAMTER 16-06-14 FA DUE TO LEAKAGE CURRENT PASSES THROUGH EARTHING.AT THAT TIME COW WAS PASSING UNDER THIS T/C,COME IN CONTACT WITH EARTHING & BECAUSE OF WET LAND GET ELECTROCUTED AND DIED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
256 AMRELI 1 COW OF SHRI ABHABHAI JETHABHAI BABARIYA,PALADI 16-06-14 FA RAIN IS FALLING IN MORNING , LEAKAGE CURRENT PASSES THROUGH EARTHING FROM JOINT OF OUTGOIN CABLE OF DISTRIBUTION BOX AND LT LINE.AT THAT TIME COW WAS PASSING UNDER THIS T/C,COME IN CONTACT WITH EARTHING & BECAUSE OF WET LAND GET ELECTROCUTED AND DIED.PVC PIPE IS ALREADY PROVIDED WITH EARTHING WIRE -- -- -- DETAILED TC MAINTENANCE CARRIED OUT & DETERIORATED CABLE REPLACED
257 AMRELI 1 BUFFALO OF SHRI CHHAGANBHAI MOHANBHAI DEVANI,SALVA 16-06-14 FA THE ACCIDENT OCCURRED DUE TO LEAKAGE CURRENT OF TC WHEN BUFFALO PASSING NEAR FROM TC.  -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
258 AMRELI VIRABHAI URFE HIRABHAI BECHARBHAI CHOPDA(FH),CHAMARADI
11-07-14 FHOS THE LEAKAGE CURRENT WAS PASSED THROUGH LT POLE EARTHING WIRE.WHEN VIRABHAI URFE HIRABHAI BECHARBHAI CHOPDA AND HIS GRANDSON SAGAR MANJIBHAI SONDARVA PASSING NEAR BY LT POLE OF VILLAGE TC AT THAT TIME SAGAR MANJIBHAI SONDARVA CONTACT WITH EARTHING WIRE OF LT POLE & GOT ELECTROCUTED.. HIRABHAI BECHARBHAI CHOPDA HAS THROWN SAGAR IMMIDIATELY FROM POLE BUT HE GOT ELECTROCUTED & DIED HOWEVER SAGAR MANJIBHAI SONDARVA WAS INJURED AT HAND.  -- -- -- DETAILED LT & TC MAINTENANCE CARRIED OUT
259 AMRELI SAGAR MANJIBHAI SONDARVA,CHAMARADI 11-07-14 NFHOS THE LEAKAGE CURRENT WAS PASSED THROUGH LT POLE EARTHING WIRE.WHEN VIRABHAI URFE HIRABHAI BECHARBHAI CHOPDA AND HIS GRANDSON SAGAR MANJIBHAI SONDARVA PASSING NEAR BY LT POLE OF VILLAGE TC AT THAT TIME SAGAR MANJIBHAI SONDARVA CONTACT WITH EARTHING WIRE OF LT POLE & GOT ELECTROCUTED.. HIRABHAI BECHARBHAI CHOPDA HAS THROWN SAGAR IMMIDIATELY FROM POLE BUT HE GOT ELECTROCUTED & DIED HOWEVER SAGAR MANJIBHAI SONDARVA WAS INJURED AT HAND.  -- -- -- DETAILED LT & TC MAINTENANCE CARRIED OUT
260 AMRELI ASLAMBHAI ABDULBHAI PATHAN,VIJAPADI 18-07-14 FHOS WHEN VICTIM CLIMB ON TRUCK& CAME IN CONTACT WITH LIVE WIRE -- -- -- DETAILED HT MAINTENANCE CARRIED OUT AND GROUND CLEARANCE MADE AS PER NORMS
261 AMRELI DHARMESHKUMAR VILASBHAI MAKVANA,VEKARIYAPARA 20-07-14 FHOS VICTIM WAS COLLECTING CLOTHES WITH HIS MOTHER FROM TERRACE WITH THE USE OF METAL ROAD WHICH COMES IN DIRECT CONTACT WITH LIVE 11 KV LINE ONE WIRE PASSING BEHIND HIS HOUSE AND OVER HIS TERRACE WALL. VERTICAL DISTANCE BETWEEN WIRE AND ROOF OF HOUSE IS ABOUT 7.5 FEET.  -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
262 AMRELI 1 BUFFALO OF SHRI BAGHABHAI DANABHAI CHAUHAN,DEVALIYA 26-07-14 FA DUE TO LEAKAGE CURRENT OF TC CENTER EARTHING ACCIDENT OCCURS -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
263 AMRELI 1 WILD ANIMAL LEOPARD FEMALE,GADHIYA 30-07-14 FA ON DATE 30.7.2014, FARMER SHRI KANUBHAI GHOHABHAI VALA GOESTO HIS FARM AT 08:00AM AND AROUND 12:00PM HE SAW AN DIEDFEMALE LEOPARD ON THE TRANSFORMER CENTER WHICH IS ERECTED ONPSC POLE IN HIS FARM FOR AGRICULTURE CONNECTION UNDER 11KV
MADHUPUR AG FEEDER. AN FEMALE LEOPARD GOES TO ON THETRANSFORMER CENTER ON PSC POLE FOR ANY REASON & CONTACT WITHJUMPER ON HT SIDE ABOVE TRANSFORMER CENTER & GET ELECTRICSHOCK & DIED ON THE SPOT.
-- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
264 AMRELI 1 COW OF KALUBHAI KANABHAI BERANI,LALAKA 31-07-14 FA WHEN COW OF MR. KALUBHAI KANABHAI BERANI PASSING FROM LT POLE OF LALKA VILLAGE TC AT THAT TIME LEAKAGE CURRENT PASSING TO EARTH AND COW GOT SHOCKED AND COW DIED AT SPOT AS PER INFORMED BY BHARATBHAI KALUBHAI BERANI( SON OF KALUBHAI BERANI). AFTER  PLACE VERIFICATION IT WAS FOUND THAT PVC EARTHING PIPE IS PROPERLY INSTALLED AND FOUND THERE IS NO MARKING OFELECTRIC SHOCK  ON COW. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
265 AMRELI SHRI MADHUBHAI BHIKHABHAI BHAYANI(LM),SARAMBHADA 05-08-14 NFHD A NON FATAL ELECTRICAL ACCIDENT ACCOUR TO M B BHAYANI – LINEMAN RURAL SDN – AMRELI. SARAMBHDA AG FEEDER WAS IN PERMANENT FAULT. VICTIME GONE TO REPAIR DODP NEAR TC OF CHATUR VALLABH NASIT OF VILLAGE : SARAMBHADA BELEIVING THAT HIS LINE IS IN SARAMBHADA AG FEEDER. BUT , ACTUALLY IT IS A NEW AG TC AND IS FED FROM : MEDI AG FEEDER. DUE TO UN AWARENESS OF POWER IN THIS GROUP, HE CLIMED ON 11 KV LINE OF MEDI AG FEEDER, AND ALSO, NOT UTILISED ANY SAFETY GADGETS AND NOT ACERTAINED ABOUT POWER OFF OR NOT. HENCE GOT ELECTRIC SHOCK FROM LIVE MEDI AG FEEDER. -- -- -- VICTIM HIMSELF RESPONSIBLE AND STRICT DISCIPLINARY ACTION TAKEN FOR NEGLEGENCE OF SAFETY RULES AND REGULATION
266 AMRELI 1 BUFFALLO OF SHRI ANIRUDHDHA DILUBHAI,DHOLAVA 08-08-14 FA THE ACCIDENT OCCURRED DUE TO BUFFALO CAME IN CONTACT OF LIVE LT LINE WIRE. THE LT LINE WIRE WAS BROKEN & FALL DOWN ON LAND & BUFFALO CAME IN CONTACT WITH BROKEN WIRE & GOT ELECTROCUTED -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
267 AMRELI 1 BUFFALLO OF SHRI ANIRUDHDHA DILUBHAI,DHOLAVA 08-08-14 FA THE ACCIDENT OCCURRED DUE TO BUFFALO CAME IN CONTACT OF LIVE LT LINE WIRE. THE LT LINE WIRE WAS BROKEN & FALL DOWN ON LAND & BUFFALO CAME IN CONTACT WITH BROKEN WIRE & GOT ELECTROCUTED -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
268 AMRELI RAJESHBHAI JAGUBHAI BAMBHANIYA,JAFRABAD
16-08-14 FHOS THE ACCIDENT IS OCCURRED DUE TO VICTIM CAME IN CONTACT OF LEAKAGE CURRENT. THE V CROSS ARM OF LOCATION NO:JFD/JFR/CITY/084/016 IS BROKEN & B PHASE CONDUCTOR  IS TOUCH TO PIN ROD OF Y PHASE RESULTING FLOW OF LEAKAGE POWER THROUGH TRANSFORMER GI WIRE.THE VICTIM GO TO POLE FOR URINAL PURPOSE GET ELECTROCUTED.  -- -- -- DETAILED HT MAINTENANCE CARRIED OUT AND GROUND CLEARANCE MADE AS PER NORMS AND STRICT DISCIPLINARY ACTION AGAINST DEFAULTER
269 AMRELI SAGARBHAI KISHANBHAI SOLANKI,JAFRABAD 16-08-14 FHOS THE ACCIDENT IS OCCURRED DUE TO VICTIM CAME IN CONTACT OF LEAKAGE CURRENT. THE V CROSS ARM OF LOCATION NO:JFD/JFR/CITY/084/016 IS BROKEN & B PHASE CONDUCTOR  IS TOUCH TO PIN ROD OF Y PHASE RESULTING FLOW OF LEAKAGE POWER THROUGH TRANSFORMER GI WIRE.THE VICTIM GO TO POLE FOR URINAL PURPOSE GET ELECTROCUTED.  -- -- -- DETAILED HT MAINTENANCE CARRIED OUT AND GROUND CLEARANCE MADE AS PER NORMS AND STRICT DISCIPLINARY ACTION AGAINST DEFAULTER
270 AMRELI 1 BULLOCK OF SHRI SAMATBHAI ARJANBHAI SOLANKI,SOKHADA 26-08-14 FA LT COUNDUCTOR BROKEN  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
271 AMRELI 1 BULLOCK OF SHRI SAMATBHAI ARJANBHAI SOLANKI,SOKHADA 26-08-14 FA LT COUNDUCTOR BROKEN  -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
272 AMRELI 1 BULLOCK OF SHRI ARJANBHAI KALABHAI MAKVANA,PALADI 31-08-14 FA ON DT.31.8.14, APP.3:00 PM ,A FATAL ACCIDENT OCCURRED TO 1 BULLOCK  OF SHRI ARAJANBHAI KALABHAI MAKAVANA AT VILLAGE PALADI  UNDER UNA.1S/DN.    A DTC FOR POWER TO VILLAGE AREA ON OLAVAN  TO PALADI ROAD IS EXIST ON 11 KV KESARIYA  JGY FEEDER. ACCIDENT OCCUR DUE TO RAIN FLOW WHEN LEAKAGE CURRENT FLOWS THROUGH  TRANSFORMER BODY EARTHLING WIRE  TO GROUND SAME TIME BULLOCK CAME IN CONTACT WITH VILLAGE TRANSFORMER BODY EARTHING WIRE HENCE CAUSE FETAL ANIMAL ACCIDENT OF BULLOCK WAS OCCURRED .  -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
273 AMRELI 1 BUFFALO OF SHRI VASHRAMBHAI BOGHABHAI BATADA,CHHATADIYA 31-08-14 FA ACCIDENT WAS OCCURRED IN HT POLE OF 11 KV CHHATADIYA AG LOCATED IN OWNER PRIMISES.DURING SITE INSPECTION V-CROSSARM,D-CLAMP,TOP CLAMP ,PIN INSULATER AND WIRING OF POLE WAS FOUND OK.EARTHING WIRE CONNECTED TO FABRICATION WAS RUNNING UPTO FIRST STEP OF POLE.POLE BOTTOM SIDE AND SURROUNDIG WAS CHECKED WHILE FEEDER IN  ON POSITION AND NO LEACKAGE CURRENT FOUND .ALSO THERE IS NO TRIPPING IN THIS FEEDER DURING ACCIDENT TIME PERIOD GIVEN BY OWNER .SO ACCIDENT IS NOT OCCURED DUE TO LEACKAGE CURRENT IN HT POLE OF 11 CHHATADIYA AG. -- -- -- DETAILED HT MAINTENANCE CARRIED OUT
274 AMRELI 1 COW OF SHRI DINESHBHAI HAMIRBHAI,JAGATIYA
03-08-14 FA WHEN 1 NOS. OF COW & 1 NOS OF CALF WERE PASSING NEAR THE GRAM PANCHAYAT WATER WORKS TRANSFORMER, THERE WAS TOO MUCH WATER SURROUNDING THE TRANSFORMER CENTRE LAND DUE TO THE HEAVY RAIN. ACCORDING TO EYE WITNESS THERE MIGHT BE LEAKAGE EARTHLING’S CURRENT FLOW THROUGH THE WATER, MEANWHILE THAT TIME TWO NOS. OF COWS CAME CONTACT WITH WATER NEAR TRANSFORMER CENTRE AND GOT SHOCKED. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
275 AMRELI 1 CALF OD SHRI KHATUBHAI VIRABHAI,JAGATIYA 03-08-14 FA WHEN 1 NOS. OF COW & 1 NOS OF CALF WERE PASSING NEAR THE GRAM PANCHAYAT WATER WORKS TRANSFORMER, THERE WAS TOO MUCH WATER SURROUNDING THE TRANSFORMER CENTRE LAND DUE TO THE HEAVY RAIN. ACCORDING TO EYE WITNESS THERE MIGHT BE LEAKAGE EARTHLING’S CURRENT FLOW THROUGH THE WATER, MEANWHILE THAT TIME TWO NOS. OF COWS CAME CONTACT WITH WATER NEAR TRANSFORMER CENTRE AND GOT SHOCKED & DIED AT SPOT. -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
276 AMRELI 1 COW OF SHRI RAMSINHBHAI SIDIBHAI JADAV,KODINAR 10-09-14 FA ACCIDENT OCCURE DUE TO SNAPPING OF 11 KV CONDUCTOR AT THAT TIME ONE COW CAME IN CONTACT WITH WIRE HENCE FATAL ANIMAL ACCIDENT OCCURE -- -- -- DETAILED HT MAINTENANCE CARRIED OUT
277 AMRELI 1 BULLOCK OF SONABEN VIRABHAI CHARANIYA,NALIYA MANDVA 10-09-14 FA THE LT LIVE CONDUCTOR WAS BROKEN & AT THE SAME TIME BULLOCK PASS ON CONDUCTOR RESULTING OCCURRENCE OF FATAL ANIMAL ACCIDENT. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
278 AMRELI 1 BUFFALO OF SHRI KADUBHAI URFE BHIKHUBHAI MALABHAI DODIYA,KODINAR 11-09-14 FA ACCIDENT OCCURE DUE TO LEAKAGE EARTH CURRENT OF  JALARAM VALU TC OF 11 KV KODINAR CT FEEDER HENCE FATAL ANIMAL ACCIDENT OCCURE -- -- -- DETAILED TC MAINTENANCE CARRIED OUT
279 AMRELI 1 BUFFALLO OD SHRI BAGHABHAI RAMBHAI KATARIYA,GHANDALA 11-09-14 FA ACCIDENT AT LT CONDUCTOR TOUCH WITH  C CLAMP THE LEAKAGE CURRENT FLOW IN WET SOIL NEAR THE PSC POLE AND WHEN THE BUFFELLO PASS NEAR THIS POLE DUE TO LEAKAGE CURRENT FATAL ANIMAL ACCIDENT OCCURE. -- -- -- DETAILED LT MAINTENANCE CARRIED OUT
280 AMRELI RAKESHBHAI JITUBHAI BALAR,SAKHPUR 15-09-14 FHOS THE VICTIM WAS WORKED AT VALJIBHAI BHATTUBHAI  HOUSE GALLERY & FITTING IRON PIPE AT GALLERY FOR PERSONAL USE .AT THE TIME OF WORK  THE PIPE TOUCH TO 11 KV LINE PASSES NEAR THROUGH GALLERY  HENCE VICTIM GOT ELECTROCUTED & FATAL ACCIDENT OCCURED  -- -- -- SAFETY AWARENESS AMONG GENERAL PUBLIC DURING VILLAGE VISIT
281 AMRELI JAYANTIBHAI BACHUBHAI THAVANI(ALM),SARASIYA 15-09-14 FHD THE AG SECTION OF 11 KV KHOKHARA FEEDER WAS IN FAULT HENCE VICTIM WAS CLIMB ON TRANSFORMER CENTER AFTER SECTIONALIZED THE D.O. FUSE TO CHECK WHETHER IT IS FAILED OR NOT? AFTER CHECKING OF TRANSFORMER, WHILE CLIMB DOWN HE FELL ON GROUND & FATAL ACCIDENT OCCURRED MIGHT BE DUE TO HEAD INJURY. AS NO EVIDENCE OF ELECTRICAL FATAL ACCIDENT FOUND FROM SITE. -- -- -- LETTER TO POLICE STATION TO LODGE FIR AGAINST FARM LABOUR BECAUSE OF UNAUTHORISE EXTENSIN OF NEUTRAL WIRE FROM ACCIDNET LOCATION
282 AMRELI 1 BUFFALO OF SHRI JAYSUKHBHAI SHAMBHUBHAI PANSURIYA,CHALALA 24-09-14 FA ON DATE 24.9.2014, AROUND 08:20AM A BUFFALO OF OWNER SHRI JAYSUKHBHAI SHAMBHUBHAI PANSURIYA PASS IN HIS FARM AT CHALALA & AT THAT TIME A BUFFALO TOUCH TO CABLE OF PRIVATE DIS-CABLE OPERATOR & AT THAT TIME THIS CABLE TOUCH TO LIVE 11KV LINE WIRE OF 11KV GAYATRI CITY URBAN FEEDER. SO THIS CABLE CHARGED & FIRED.
A BUFFALO CONTACT WITH THIS CABLE & GOT ELECTRIC SHOCK & DIED ON THE SPOT.
-- -- -- UN AUTHORISE HANGING OF TV CABLE,HENCE NOTICE ISUUED TO CABLE OPERATOR FOR UNAUTHORISE USE OF ELECTRIC POLE
283 SNRC Kum. Aartiben Jagdishbhai Thakor 26-04-14 NFHOS An electrical non fatal accident occur to above mention victim was contact with snapping of conductor due to pin insulator fired of 11 KV Dhama AG feeder emanating from 66 KV Dhama S/S Report yet not received NA NA Replaced Pin Insulator 
284 SNRC Shri Diwanbhai Humabhai 04-05-14 FHOS During construction work of bridge on road, victim came in direct contact with live conductor of 11 KV Ganjela JGY through an IRON ROD about 5 Mtr long in his hand and got electrocuted.  Report yet not received NA NA Victim Fault
285 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 05-06-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
286 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 05-06-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
287 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
288 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
289 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
290 SNRC Goat of Shri Ghanshyambhai Dharamshibhai 5-Jun-14 FA Fatal electrical Accident Occurred To 6 no of Goat of Shri Ghanshyambhai Dharamshibhai Koli due to a lunger Wire Hanging on LT pole & Live part of lunger wire  Touch with C-Clamp , by this C- Clamp leakage Current pass through  G.I Earthing Wire and at that time The Goats were passing there near LT pole From water logging area surrounding this LT pole leakage current pass through GI wire through water through Body of Goats and Electrocuted. Report yet not received NA NA Unauthorized work by unknown person. Removed lunger wire
291 SNRC Cow of Shri Janakbhai Ajani 18-Jun-14 FA Accident occurred to cow due to DTC meter cable cracked and might came in contact with DTC DP structure and due to raining leakage current flow through DP structure and cow might came in contact of DP structure and got electric shock Report yet not received NA NA Maint Done
292 SNRC Buffalo of Shri Chandu Thakarshi  19-Jun-14 FA Two nos. of HT pole & line Of 11 KV Fuleshwar feeder was broken by unknown person and this buffallow came in contact of live wire and get electrocuted. Report yet not received NA NA FIR Laundged & Rectification Done
293 SNRC  Buffalo of Shri Mavji Govind 19-Jun-14 FA Two nos. of HT pole & line Of 11 KV Fuleshwar feeder was broken by unknown person and this buffallow came in contact of live wire and get electrocuted. Report yet not received NA NA FIR Laundged & Rectification Done
294 SNRC  Buffalo of  Shri Ramnikbhai Himatbhai 19-Jun-14 FA Two nos. of HT pole & line Of 11 KV Fuleshwar feeder was broken by unknown person and this buffallow came in contact of live wire and get electrocuted. Report yet not received NA NA FIR Laundged & Rectification Done
295 SNRC Buffalo of Shri Popatbhai Saktabhai 1-Jul-14 FA An elctrical accident occurred to one buffalo due to DTC meter cable cracked & might came in contact with DTC DP Structure & due to raining leakage current flow through dp Strucutre & victim might came in contact with DP Strucutue and get electroculated.  Report yet not received NA NA Maint Done
296 SNRC Shri Maheshbhai Bolabhai 2-Jul-14 FHOS Accident occurred at 11KV Tavi JGY Feeder. Unauthorized construction was done by Gabhubhai Hirabhai sabhad and recently slab work was completed before @ 3 days. Victim was on the slab with other 2(Two) persons and he directly came in contact with the side phase of 11KV Tavi JGY feeder which was crossing at 5 Feet height from the slab and as a result accident occurred. As the construction is unauthorized below existing 11KV Tavi JGY, PGVCL is not guilty for the said accident. Report yet not received NA NA Victim Fault. As per party's application line shifting work done after payment
297 SNRC Cow of Shri Sureshbhai Khodabhai 10-Jul-14 FA LT conductor snapped of sejakpar village transformer and cow came in contact with this live snapped conductor and got electrocuted Report yet not received NA NA Maint Done
298 SNRC Shri Vinubhai M Baroliya 11-Jul-14 NFHD When victim called R M patel-ALM to take line clear of 11 KV Samadhiyala JGY feeder he sent SMS to 66 KV Vinchhiya SS for line clear at 14.36 Hrs. At 14.40 Hrs he orally talked with SBO and he informed him that the braker was reak out of 11 KV Samadhiyala JGy feeder so he informed to victim. When vicitm climbed on PSC pole of  11 KV Samadhiyala JGy feeder he experinced an electric shock and put down on ground.Meanwhile SBO has sent SMS for line clear taken to R M Patel-ALM mobile at 14.46 Hrs.  Report yet not received NA NA CS issued to Victim & Supervisor
299 SNRC Shri Manubhai Butabhai 15-Jul-14 FHOS As per information received from news paper Divya Bhaskar on dtd. 20.7.14, Victim was unauthorizedly built roof under 11 KV line of Somasar AG feeder meanwhile he throw iron wire on the roof and kept one side of il in his hand so it touched the live conductor of 11 KV Somasar AG feeder passing over the roof and live current may passed through this wire to the body of the victim and he experinced an electric shock. Report yet not received NA NA Victim Fault
300 SNRC Shri A G Solanki-EA 15-Jul-14 NFHD THE VICTIM SHREE  ARUNBHAI G SOLANKI WAS GOING TO ATTEND LTG COMPLAIN OF SHRI BHIMABHAI KEHABHAI VILL CHUDA AT MAFTIYAPARA WITH LINE INSPETOR SHRI KS PONDOR , WHILE ATTENDING THE SAID  LTG COMPLAIN VICTIM CLIMB ED  ON LT  PSC POLE BUT DUE TO RAINY ENVIRNMENT/CLIMATE HIS LEG WAS  SLIPPED  AND  HE WAS SLIPDOWN ON EARTH. DUE TO THIS REASON THIS MECH. ACCIDENT OCCURRED. NOTED THAT WHILE ATTENDING THE SAID COMPLAIN VICTIM WAS NOT USED SAFETY INSTRUMENT LIKE HELMET,GOOMBOOT,AND SAFETY BELT ETC….. Report yet not received NA NA CS issued to Supervisor & Warning issued to victim
301 SNRC A buffalo of Shri Bhagvanbhai Laxmanbhai 17-Jul-14 FA One jumper of LT line of village TC was loose and touched to the PSC pole earthing wire and leakage passes through GI earthing wire and current passed through body of buffalo. Accident message received from Sayla police station as on dtd.5.8.14. Report yet not received NA NA Maint Done
302 SNRC A HE Buffalo of Shri Vaghabhai Kamabhai 17-Jul-14 FA A HE buffalo touched to the GI earthing wire of village TC and leakage passed through GI earthing wire and got electric shock. Accident information received from Karadi Sarpanch. Report yet not received NA NA Maint Done
303 SNRC Cow of Shri Malabhai Hindubhai 17-Jul-14 FA Due to Heavy rain, poles of 11 KV Motabhadla Ag feeder  having Loc No. SUD/NAG/346-347-348 were broken and also other 3 Nos adjoining poles were broken and cow was at that time grazing under this location and came in contact with live wire and got electric shock. Report yet not received NA NA Maint Done
304 SNRC Shri Dineshbhai Bavalbhai 17-Jul-14 NFHOS 11 KV Tavi feeder was tripped at 18.25 PM. And at that time victim was climed on TC centre for binding of jumper of Ht line, meanwhile feeder charged at 18.35 PM and victim got shocked and fall down on the earth.  Report yet not received NA NA Victim Fault
305 SNRC Shri Kadvabhai Premjibhai 19-Jul-14 FA When buffalo was passing near guy wire of Kadva Premji AG TC, 11 KV DO broken and touched to angle and due to this return power from TC passing through PSC pole of TC centre and its guy and got electric shock on neck and died.   Report yet not received NA NA Maint Done
306 SNRC Shri Valjibhai Ranchhodbhai 24-Jul-14 FA Due to cyclone, street light fixture fixed on round pole got tilted and metal part of fixture came in contact of round pole. Report yet not received NA NA Municipality Fault. Notice Issued
307 SNRC Shri Bharatbhai Muljibhai  30-Jul-14 NFHD To attend 11 KV Vagadiya AG feeder which was in fault. During petrolling jumper of main line gang switch of Khakhrali village AG was found burnt. During rejumpering work on DP structure of gang switch he experinced  the momentary electric jerk on his hand. Shri B D Patel-ALM helped the victim to come down from DP structure   Report yet not received NA NA CS issued to Supervisor. Warning issued to DE & Victim
308 SNRC Shri Babubhai Raysangbhai 30-Jul-14 NFHOS A NFH accident occurred to outsider Shri BABUBHAI RAISANGBHAI SURELA ON DT15.07.14 00:05 HRS LOCATION UNDER SCSD-2,REASON OF THE ACCIDENT IS THAT HE HIMSELF CLIMB ON HT 4 POLE STRUCTURE  OF 11 KV JINTAN FEEDER & GOT ELECTRIC SHOCK Report yet not received NA NA Victim Fault
309 SNRC Smt Lilaben Rajubhai 30-Jul-14 NFHOS A non fatal electrical accident ocurred due to the connductor of 11kv Kankeshver Ag feeder slipped from shackle point, at that time victim came in contact with the live conductor and got electric shock. Report yet not received NA NA Manit Done. Overloaded Feeder. Load transferred to other feeder
310 SNRC Cow of Shri Vashrambhai Mayabhai 2-Aug-14 FA Due to strret light fixture choke short, aleakage current flow and cow passes near this pole nad got electric shock.  Report yet not received NA NA Municipality Fault. Notice Issued
311 SNRC Buffalo of Shri Kamabhai Vaghabhai 9-Aug-14 FA Buffalo was passing near manharpark society tc of 11 KV Jolly Urban feeder and there was a rain and wet atmosphere on dt.19.7.14, it came in contact of earthing wire and got electric shock.  Report yet not received NA NA SCN issued to SDO
312 SNRC Cow of Shri raiyabhai Masabhai 14-Aug-14 FA Fatal animal accident occurred due to short street light fixture Report yet not received NA NA Municipality Fault. Notice Issued
313 SNRC Buffalo of Shri Kamabhai Vaghabhai 30-Aug-14 FA Buffalo was passing near manharpark society tc of 11 KV Jolly Urban feeder and there was a rain and wet atmosphere on dt.30.7.14, it came in contact of earthing wire and got electric shock.  Report yet not received NA NA SCN issued to SDO
314 SNRC An OX of Shri Vajubhai Ranchhodbhai 2-Sep-14 FA Near TC DP leakage current passes through earth wire due to rain and current passed through OX body Report yet not received NA NA Maint Done
315 SNRC A buffalo of Shri Laghubhai Aalbhai 9-Sep-14 FA Near TC DP leakage current passes through earth wire due to rains and water logging near TC pole and at that time momentary leakage current passes through body of buffalo and got electrocuted. Report yet not received NA NA Maint Done
316 RCC Vijay Gordhanbhai Aghera 09.10.14 NFHD-Mechnical The Victim was given work to release temporary connection at shivdhara residency with lineman shri J.P.Vidja. They have cut power supply of  concern T/C by removing fuse from DB Box and after that victim climbed LT pole up to 4 to 5 meters with Helmet and safety belt. From Top side Chameleon (Kachido) was coming towards victim and in frustration he loose his cross leg balance and fell down and non fatal mechanical accident occured. Mechanical Mechanical NA During safety meeting all line staff were aware about prevention of such type of accident.
317 RCC Suresh Ramlal Suryavanshi 18.11.14 NFHOS Victim was change hording board at Kalavad Rd near Royal Palace at that time victim was touch to 11 kv Jalaram Fdr line which is passing above hording board and  get electric shock. So he was burned on ear & chest so non fatal accident occur. Report yet not received NA NA Informed to RMC to maintain safe Distance from electric line to advertisement board
318 RRC Jamtimbadi, fatal accident occurred
to Shri Kundan Mohan Bhut
12.3.15 FHOS As per telephonic message received of Sarpanch shri  Jamtimbadi, fatal accident occurred to Shri Kundan Mohan Bhut at  joint Ag.Land of Chhagan Ramji Bhut & Kundan Mohan Bhut, village. Jamtimbdi.  After site visit it is found that in AG Land  where one Transformer Centre (10 kva) exist named as Chagan ramaji valu victim climbed illegally on the same transformer center due to unknown reason and anyhow came in  contact with live part of the conductor and got electrocuted at that time. Hence fatal accident occurred. NOT YET RECEIVED NA NA village meeting done at village jam timbdi &aware the villageres about the safety &  not done illegal work on pgvcl network & also work done for any fault in private primises attented by wireman  not by self  
319 RRC Gomta, SH. GIRISHBHAI KURJIBHAI BAVARIYA 02.12.14 NFHD ON DT. 02.12.14 AT TIME APPROX 10:30 AM GOMTA VILLAGE ELE. ASST. SH. GIRISHBHAI KURJIBHAI BAVARIYA WENT TO ATTEND LT SERVICE LINE COMPLAINT OF JAGDISHBHAI NAROTTAMBHAI VACHANI , VILLAGE GOMTA & CONS. NO. 87718/00986/6. D.O FUSE OF SAID T.C WAS REMOVED BY VICTIM. AFTER THAT VICTIM WENT TO ATTEND COMPLAINT , AT THE TIME OF CLIMBING POLE VICTIM SUDDENLY FALLED DOWN & MET WITH MECHANICAL ACCIDENT. NOT YET RECEIVED NA NA WARNING MEMO ISSUED TO VICTIM EMPLOYEE & SHOWCAUSE NOTICE ISSUED TO SDO AND ISTRUCTED SDO TO ARRANGE SAFETY MEETING PER WEEK & MOCKDRILL PER MONTH TO TO AWARE STAFF TO AVOID SUCH ACCIDENTS.
320 RRC Jamkandorna,prafulbhai vamanrai joshi 04.10.2014 NFHOS A human outsider non fatal accident occurs to Shri Prafulbhai Vamanrai Joshi (Panchayat employee) at village jamkandorna on date 04.10.2014 time :11:00 am ,while he was working on pole for repairing of street light ,he fall down from pole and get injured and admitted into hospital, actual cause of reason is under investigation will be decided after statement of victim and medical report thereof NOT YET RECEIVED NA NA Letter return to gram panchayat  & panchayat helper should not work on PGVCL network without supervisor of PGVCL..Also carry out LT line maintenance periodically.
321 RRC Pedhla,1 sheeps Gopalbhai Samatbhai Aal 14.10.2014 FA On dated 17.10.14 approx 7:00 am ,At the place of Pedhla village Neutral wire of LT Line was snapped on ground of Rabari vas valu TC (Kerali JGY) Due to corrosion on shackle insulator. At that time shepherd Shri.Gopabhai Samatbhai Aal (Rabari) was passing with his sheep and two no’s of sheep are came in contact with this snapped  neutral wire and electric current passed through it and electrocuted resulting in to Animal fatal accident. The detail investigation follows. NOT YET RECEIVED NA NA Maintenance carried out.
322 RRC Pedhla,1 sheeps Gopalbhai Samatbhai Aal 14.10.2014 FA On dated 17.10.14 approx 7:00 am ,At the place of Pedhla village Neutral wire of LT Line was snapped on ground of Rabari vas valu TC (Kerali JGY) Due to corrosion on shackle insulator. At that time shepherd Shri.Gopabhai Samatbhai Aal (Rabari) was passing with his sheep and two no’s of sheep are came in contact with this snapped  neutral wire and electric current passed through it and electrocuted resulting in to Animal fatal accident. The detail investigation follows. NOT YET RECEIVED NA NA Maintenance carried out.
323 RRC Bavapiplya,Jitendra Govind Galoriya 01.03.2015 NFHD A non fatal Human departmental accident occurred at Bavapiliya village Timbadi JGY feeder ,to attend a pin fault in timbadi JGY. On 01.03.15 Shri Jitendrabhai G.Galoriya   Elect. Assistant  Jetpur rural S/Dn was assign work of 11 KV pin rebinding located near ag  land of Bavapilpliya of 11 KV Timbadi JGY fdr, for which he had isolated the section by operating AB switch. Then after he climbed up the PSC pole to rectify the work of pin rebinding. When  he reched to the  5th slot of PSC pole he suddenly from fall down on the ground, resulting in to non fatal mechanical accident.(DEPARTMENTAL) NOT YET RECEIVED NA NA Penalty  of 500rs.has been taken out.
324 RRC PARDI,Sh.Mohanbhai Parsottambhai Kandoliya 27.01.15 FHD As reported by the SDO Lodhika;On date: 26.01.15 the 11 KV Pardi AG feeder was in Fault at 14:00 Hrs which was attended by LM of Lodhika SDN Sh.L.G.Jotangiya with EA Sh.Jitubhai Khuman. While working for rejumper at Substation end Sh.Jotangiya observed that inspite of 11 KV Pardi AG Feeder in PF, the power felt when discharging the line with the discharge rod and after opening the GO switch located at “Pardi Vokala” the return power not felt. Consequently line patrolling carried out but no return power location found hence approx. 19:00 Hrs the Pardi AG feeder made ON in single phasing with the intimation to Line Inspector Sh.M.S.Bhoye to find out the reasons on the next day i.e. on 27.01.15 after the completion of scheduled 3 ph power of 11 KV Pardi AG feeder which is 04:00 to 12:00 Hrs.  On date:27.01.15 the Line clear of 11 KV Pardi AG DOM feeder has been taken by Sh. L.G.Jotangiya LM barring LC No:17173 time:12:30 Hrs. He and the other line staff viz. 1.Sh.Mohanbhai S Bhoye LI; 2.Sh.Gopalbhai L.Damor LM; 3.Victim Sh. M.P.Kandoliya ALM; 4.Sh.M.S.Miyatra EA; 5.Sh.R.J.Jadeja EA carried out the work of patrolling and to sectionalize the feeder for the detection of return power to 11 KV Pardi AG feeders. During the course of work Sh.Jotangiya and Sh.Miyatra isolated the Pardi Wokla wali switch and provided local earthing to one of the phase to guy wire but not short all three phase wires. They both stayed there and the other line staffs went for the sectionalization on the feeder. At the place of accident i.e. on the PSC Pole DP with the 11 KV Out door cable box near the Tejasavi Hanuman Mandir the victim Sh.M.P.Kandoliya;ALM and Sh.G.L.Damor;LM had climbed the PSC Pole DP from the opposite end while Sh. M.S Bhoye,LI and Sh.R.J.Jadeja EA were on ground for supervising and assist the work. The local earthing; short of all three barred wires and the discharge were not provided on either side of the DP. The victim while working with the safety gloves to remove the UG cable jumpers from line to isolate the section sitting on the DP angle; suddenly got the electric shock when LI Sh.Bhoye found that the victim on the DP got the electric shock; he started climbing the Pole for the help of the victim but the victim fell down from the DP. Immediately, they all together give him the preliminary treatment and called ‘108’ambulaence. During that time they shifted the victim in hired SDN vehicle and met with ‘108’ near 66 KV Vavdi SS took him to Civil Hospital-Rajkot where the doctor in charge declared him dead. After the accident occurred the under signed with DE Tech RRD immediately rushed to the accident place and with the Deputy Engineer, junior Engineers and the line staff of Lodhika sub division had worked to identify the cause of the return power to 11 KV Pardi AG feeder on which the victim working. As found the AG RL 1phase consumer Sh.Dineshbhai Hansrajbhai Mungpara Con No: 33421-66761-6 LS No:161p36 village: Pardi. The said connection is supplied by erecting the 1p2w line of LT AB cable from the 10 KVA transformer connected on 11 KV Pardi AG feeder erected for the AG connection of Sh.Vipul Popat Parsana Con No:33421-01950-9. Sh. Dineshbhai Hansrajbhai Mungpara had illegally taken the direct lungariya from the LT line pole of 100 KVA, Pardi village TC on 11 KV Velnath JGY feeder by lying approx.1000 MTR twin core wire. He had provided the arrangement of Kit kat fuses and change over switch in his house for the alternate supply. It is found that from the change over switch the live phase of velnath JGY feeder power returned on 11 KV Pardi AG DOM feeder through the 1ph meter and AG TC of 10 KVA Transformer. Immediately the said AG RL connection is disconnected and the meter, change over switch, MCB unit, wires and arrangement are seized. Necessary legal steps have initiated on the defaulter consumer. PM report and Police Panchanam awaited. NOT YET RECEIVED NA NA CHARGESHEET IS ISSUED TO SH. G.L.DAMOR(L.M) VIDE NO - 123/16.4.15 & TRANSFERRED TO RONKI S.DN ,  SH. BHOYE (L.I) -IS UNDER SUSPENSION & HQ AT JASDAN DN.VIDE C.S - 124/16.4.15 ,  AND INSTRUCTED SDO TO ARRANGE SAFETY MEETING PER WEEK & MOCKDRILL PER MONTH TO TO AWARE STAFF TO AVOID SUCH ACCIDENTS &CONTRACTOR MEETING ALSO ARRANGED. & FIR (304) LODGED VIDE - 07/2015/30.1.15 AGAINST THE DEFAULTER SH.DINESH HANSRAJ MUNGALPARA VILLAGE PARDI.
325 RRC VERAVAL Sh. Hardikbhai Gordhanbhai Paraliya 30.03.15 NFHOS As reported by the SDO-Shapar Veraval; at 19:15 Hrs Narmada IND feeder emanating from the 66 KV Veraval SS has been tripped. The message regarding the accident occurred at the Bright Metal Industries has been conveyed by the industrial consumer. During the investigation it is revealed that while dismantling the stand which used for the construction work, approximately at the distance of 1.5 Fts from the live 11 KV Wire of Narmada Ind Feeder, the victim came in contact with live wire by the wet Bamboo by the said stand, got  electrical  shock and fell down from the construction stand of Iron. DE is informed  to lodge FIR against defaulter. NOT YET RECEIVED NA NA VILLAGE MEETING IS ARRANGED FOR AWARENESS OF PUBLIC.& NECESSARY LETTER  WRITTEN TO LODGE FIR  AGAINST THE DEFAULTER SH.DIPAKBHAI SHAH (OWNER) & RAIYABHAI BHRVAD (CIVIL CONTRACTOR) VIDE - DE/SVSD/TECH/756/31.3.15
326 RRC DHORAPIPALIYA , SH. MAHESHBHAI BALABHAI MAKVANA 16.11.14 FHOS ON DATE 16.11.14 ACCIDENT OCCURRED AND REGARDING THIS ACCIDENT INFORMATION RECEIVED FROM 66KV KAMLAPUR S/S THAT A 11 KV WIRE IS BROKEN & HUMAN ACCIDENT OCCURRED DUE TO THIS.DURING SITE VISIT IT WAS FOUND THAT ONE CONDUCTOR OF 11KV DAHISARA AG FEEDER WAS SNAPPED ON THE GROUND AND IT CUT WITH SHARP METAL EQUIPMENT.BUT THERE WAS NO EVIDENCE OF SPARKING OR ANY BURNT MARK ON THE SURFACE OF CONDUCTOR.DETAIL CAUSE OF ACCIDENT UNDER INVESTIGATION & THERE IS NO ANY EYE WITNESS. NOT YET RECEIVED NA NA As per forensic report this accident not occurred that accident place, 
Also public awareness program done
327 RRC SAR , JAYABEN JASMATBHAI MAKVANA(FATAL) 27.11.14 FHOS As per the statement of victim Sh.Laxman Mohanbhai at bus stand chowk  A road crossing 1 phase LT AB Cable was snapped and fallen on both jayaben and Laxmanbhai and this accident occurred, further investigation is under process. NOT YET RECEIVED NA NA As per police investigation  this accident not occurred that accident place, 
Also public awareness program done
328 RRC SAR , LAXMAN MOHAN TALAVADIYA(NON-FATAL) 27.11.14 NFHOS As per the statement of victim Sh.Laxman Mohanbhai at bus stand chowk  A road crossing 1 phase LT AB Cable was snapped and fallen on both jayaben and Laxmanbhai and this accident occurred, further investigation is under process. NOT YET RECEIVED NA NA As per police investigation  this accident not occurred that accident place, 
Also public awareness program done
329 RRC JIVAPAR,  1 BUFFALO OF SH.Dinesh Vallabh Sathaliya 27.12.14 FA Information received regarding this accident from Sarpanch Jivapar Village & as per site visit & preliminary investigation 11KV Gaurav Ag feeder was "ON" in 1 Phase power at that time one top wire's 11KV pin insulator blast due to fault so conductor snapped from pin binding & fell on the buffalo & this accident occurred. 3 Nos. Buffalo was Fatal & 1 Buffalo is Non-Fatal. NOT YET RECEIVED NA NA Public aver regarding animals do not keep under over network or near TC. Also public awareness program done 
330 RRC JIVAPAR,  1 BUFFALO OF SH.Dinesh Vallabh Sathaliya 27.12.14 FA Information received regarding this accident from Sarpanch Jivapar Village & as per site visit & preliminary investigation 11KV Gaurav Ag feeder was "ON" in 1 Phase power at that time one top wire's 11KV pin insulator blast due to fault so conductor snapped from pin binding & fell on the buffalo & this accident occurred. 3 Nos. Buffalo was Fatal & 1 Buffalo is Non-Fatal. NOT YET RECEIVED NA NA Public aver regarding animals do not keep under over network or near TC. Also public awareness program done 
331 RRC JIVAPAR,  1 BUFFALO OF SH.Dinesh Vallabh Sathaliya 27.12.14 FA Information received regarding this accident from Sarpanch Jivapar Village & as per site visit & preliminary investigation 11KV Gaurav Ag feeder was "ON" in 1 Phase power at that time one top wire's 11KV pin insulator blast due to fault so conductor snapped from pin binding & fell on the buffalo & this accident occurred. 3 Nos. Buffalo was Fatal & 1 Buffalo is Non-Fatal. NOT YET RECEIVED NA NA Public aver regarding animals do not keep under over network or near TC. Also public awareness program done 
332 RRC JASAPAR , Vikram Bhavan Malival (CONTRACTOR PERSON) 27.1.15 NFHOS Victim Climbed on 11 KV pole for Restringing work of conductor. While working suddenly PSC Pole broken from middle and victim fall on the ground and got Mechanical injury and met with Mechanical Non Fatal Accident.  During site visit by EE quality of PSC pole is proper.(CONTRACTOR PERSON) NOT YET RECEIVED NA NA Contractor should Improve work menership, Also Meeting was arranged with Contractor and Labours 
333 RRC VERAVAL BHADLA ,     Naransing Balusing Gehlot  12.2.15 FHOS A contractor’s Gang of sh. D.U. Rabadiya was working at Veraval(Bhadala) Ag group at “Sarpanch valu TC” without informing anybody at S/dn office. No LCP was taken of  11 kv Virpar Ag feeder it is emitting from 66 kv Bhadala S/S. Only D.O. Fuse of AG TC removes So there is no power in LT line but 11 kv virpar  Ag feeder was live. On that particular location where this accident took place that place  HT line and LT lines are crossing. A Victim was climbed on end pole of LT line and cut the wire with plier & LT wire suddenly swing with jump due to tension and came in contact with Live 11 kv Virpar ag feeder’s wire and power came from 11 kv Line to LT line and this accident occurred. The actual reason May be concluded as per Post mortems Report (CONTRACTOR PERSON) NOT YET RECEIVED NA NA Do not work without take LCP of crossing feeder and don’t start work in over confidence,  Also Meeting was arranged with Contractor and Labours 
334 RRC HARIPAR , COW OF SH BHIKHABHAI CHHAGANBHAI BHUT 10.3.15 FA AS PER PRELIMINARY ACCIDENT REPORT OF DE SARDHAR THERE IS A SEPARATE 16KVA TC OF CONSUMER PRAVINBHAI LALJIBHAI SORATHIYA.THE 3 PH SERVICE WIRE OF AG CONNECTION IS COMING FROM TC LT BUSHING TO ELECTRIC METER. AS PER THE SITE SITUATION THIS SERVICE WIRE'S INSULATION IS DAMAGE & IT IS TOUCHED WITH FENCING WIRE.FENCING ISDONE AROUND THE FARM NEAR ANIMAL SHELTER . A BUFFAO & COW WAS IN ANIMAL SHELTER ROOM & BOTH ACCIDENTLY CAME IN CONTACT WIT FENCING WIRE & GOT ELECTRICSHOCK & ACCIDENT OCCURED.COWS AGE IS APPROX 6 YEAR  & BUFFALO S AGE IS APPROX 7 YEARS. NOT YET RECEIVED NA NA Always use GI wire, Egg insulator & Reel Insulator with Service wire at the time of connection release or meter and service wire replacement, Also Meeting was arranged with Contractor and Labours   
335 RRC HARIPAR , BUFFALO OF SH BHIKHABHAI CHHAGANBHAI BHUT 10.3.15 FA AS PER PRELIMINARY ACCIDENT REPORT OF DE SARDHAR THERE IS A SEPARATE 16KVA TC OF CONSUMER PRAVINBHAI LALJIBHAI SORATHIYA.THE 3 PH SERVICE WIRE OF AG CONNECTION IS COMING FROM TC LT BUSHING TO ELECTRIC METER. AS PER THE SITE SITUATION THIS SERVICE WIRE'S INSULATION IS DAMAGE & IT IS TOUCHED WITH FENCING WIRE.FENCING ISDONE AROUND THE FARM NEAR ANIMAL SHELTER . A BUFFAO & COW WAS IN ANIMAL SHELTER ROOM & BOTH ACCIDENTLY CAME IN CONTACT WIT FENCING WIRE & GOT ELECTRICSHOCK & ACCIDENT OCCURED.COWS AGE IS APPROX 6 YEAR  & BUFFALO S AGE IS APPROX 7 YEARS. NOT YET RECEIVED NA NA Always use GI wire, Egg insulator & Reel Insulator with Service wire at the time of connection release or meter and service wire replacement, Also Meeting was arranged with Contractor and Labours   
336 MRB At DHUVA
Laxmanbhai Rambhai Soren
07.10.2014 NFHOS The Victim was indulged in ground levelling work around PGVCL’s DO-DP of HT consumer M/s Glossy Tiles. In the process the guy became loose as the ground end of the guy wire detached. The victim with his bare hands then tried to push/ pull this detached loose guy wire & in the process the guy wire come in contact with live outgoing jumper of DO-DP. Thus the victim met with non- fatal electrical accident. The feeder did not trip but drop out fuse had been blown. Report yet not received NA NA The damaged Guy wire of DO/ DP structure has been removed & DP's Jumper has been rebound. Notice issued to  HT consumer M/s Glossy Tiles for conducting unauthotised work near & arround PGVCL network without intimation to & permission of the concerned PGVCL office.
337 MRB At VELALA
Rajubhai Aalabhai Lamka (Bharvad)
06.11.2014 FHOS The victim was under medical treatment since last few days for some mental disorder. Given he was mentally ill, he climbed over 11KV pole without realising the danger to his life & then came in contact with live phase & thereby electrocuted.  Report yet not received NA NA Since it was the vicitm's mental illness/ imbalance which resulted him climbing over the pole without undue reason, nothing much dould be done to prevent such accident.
338 MRB At MALIYA
Altaf Dilavar Chauhan
13.11.2014 NFHD When the victim would have climbed about 6mtr on LT line’s PSC pole to work on jumpers, the PSC pole begun bending over from & near the ground. The victim then out of fear of falling, tightly held the pole while it was fast bending over to the ground. Given the victim’s weight, the bent pole ultimately broke & fell to the ground while the victim was still over it. In the process, the victim sustained fracture on his hand. The victim did use helmet & safety belt.  Report yet not received NA NA Both The Executive Engineer of Morbi DO & the Deputy Engineer of Mota Dahisara has been served the Show cause notice in context with this accident. New pole has been erected in place of deteriorated broken pole.
339 MRB At PANCHDWARKA
Tarusing Nathusing Chauhan
18.11.2014 NFHOS The Victim is hired as a labourer by PGVCL line work contractor.The victim was into line maintenance work of 11 KV Tithva Ag feeder emanating from 66KV Jadeshwar S/S. The work supervisor was Sh P.K Khanma, Lineman. Since the feeder had LST arrangement for single phase power supply, the feeder’s one phase was live The Victim climbed on AG TC (Kusumben Yunushbhai valu ag TC) on which single phase power supply was ON and touched 11 KV jumper. Hence suffered electric shock and fell down on the ground from TC centre & met with non-fatal electric accident.  Report yet not received NA NA Showcause Notice issued to supervisor Sh. P.K. Khanma Lineman vide letter# EE/WKR/HR/252 dtd.20.11.14 for negligence in duty.
Notice issued to the line contractor Darshan Enterprise vide letter# EE/WKR/T-2/253 dtd.20.11.14 for carelessness & irresponsible behaviour exhibited by his labourers. Further EE- Wankaner division & DE- Wankaner Rural1 subdivision too have been served with the show cause notices in the context of this accident.
340 MRB At Morbi
Ranchhod Mohanbhai Rathwa
26.11.2014 FHOS The victims have been hired as construction labourers by the construction contractor undertaking Sankalp-2 complex construction. The complex is under construction. The victims while on second floor of this under construction building took about 10ft long iron rod for some reason & tried to move it when the said rod came in contact with nearby passing horizontally parallel 11KV line bare conductor. Horizontal clearance of the nearest conductor to this building structure is 6.5FT. Vertical clearance, although is irrelevant in this particular case, is 21.5FT.  Report yet not received NA NA SDO of Morbi Town1 has registered Police complain against defalter contractor. 
341 MRB At Morbi
Guman Dalsing Rathwa 
26.11.2014 NFHOS The victims have been hired as construction labourers by the construction contractor undertaking Sankalp-2 complex construction. The complex is under construction. The victims while on second floor of this under construction building took about 10ft long iron rod for some reason & tried to move it when the said rod came in contact with nearby passing horizontally parallel 11KV line bare conductor. Horizontal clearance of the nearest conductor to this building structure is 6.5FT. Vertical clearance, although is irrelevant in this particular case, is 21.5FT.  Report yet not received NA NA SDO of Morbi Town1 has registered Police complain against defalter contractor. 
342 PBR NANDARKHI AND BUFFALO-SHE OF UKABHAI MESURBHAI MUCHAL 09.10.14 FA An animal buffalo accident occurs at village-Nandarkhi Gam valu tc  and the owner of buffalo  is Sh.Ukabhai Mesurbhai Muchal  on date 08/10/2014 time 10.30 am approx at village Nandarkhi gam valu tc area  from 66 kv shill s/s under Mangrol rural subdivision  due to buffalo come the transformer D.P structure around the leakage current pass  induction zone near pass  and buffalo  fall down on land and than after in few minutes bu buffalo died. detail report follows. Report yet not received NA NA Proper Maintanace Done
343 PBR ITADI AND PRAKASHBHAI JESHABHAI SHINGAD 13.10.14 NFHOS The victimized person was invoved with HVDS work of Dudhala ag feeder & one more contractor gaung was also working for the same.line clear was issued to both for the same feeder. Victimised person confirmed that they have isolated the switch & they wiill work after the isolated switch i.e load side of switch though by mistake they were working ahead of isolated switch i.e main side of switch.as line clear of second contractor was on till that time there was no power in feeder  but as soon as second contractor also returned his LP, the line was charged & vitimised person working ahead of isolated switch got electrocued & met with a non fatal accident. Report yet not received NA NA CONTRACTOR BLACK LISTED & INSTRUCTION GIVEN TO ALL STAFF.
344 PBR KESHOD AND KESHUBHAI VARJANGBHAI GOHEL 24.11.14 NFHOS After carried out site visit of said accident, the illegal construction was carried out by Victim under HT line of 11KV Gangnath Urban Feeder. Victim was stood at first floor and carried out construction work at that time he was touched to live wire of HT line and got shocked. Report yet not received NA NA Notice Issued and Public Awareness
345 PBR MODHAWADA AND DUDABHAI SIDIBHAI MODHAVADIYA 03.12.14 FHOS Due to snapping of the conductor of 11 KV Lirbai AG Dom. Feeder emitting from 66 KV Ambarama S/S between location No. 103/104 (AB Switch DP) and location No. 105, near disc insulator of AB switch DP where jumper also found burnt and conductor fall down on agriculture land load side. Return path of the fault current of this break conductor causes the fatal accident when victim was came in contact anyway. No any tripping found on the 11 KV Lirbai AG Feeder as per 66 KV SS record. Various sparks observed on this snapped conductor. Report yet not received NA YES Proper Maintanace Done
346 PBR MANGROL AND PRAVINBHAI ARJANBHAI TANK 20.12.14 NFHD On dated 20.12.14 victim and his co worker Sh I I Kolad (E.A.) went for replacement LT fuse of distribution box of link bunglowvalu TC in 11kv Bandar urban feeder. For this work they demanded for hand trip of 11kv Bandar urban feeder for breaking of Madhav Icevali switch from LM Sh D M Alad, but R -phase jumper's female part of switch was not separated but came out from base and remained live. Due to other work replacement of LTAB cable in same TC after shorting LT side victim climbed on dp of link bunglowvalu TC for making earth at ht side when victim tried to earth/short R- phase due to imbalance his left hand touched to tc ht bushing and he fell down from dp then after he referred to govt.hospital Mangrol then at Junagadh. He got burnt in his left hand & both foot. Report yet not received NA YES Proper Maintanace Done
347 PBR DHARAMPUR AND BACHUBHAI VIKRAMBHAI RAM 15.01.15 FHOS Ram  Rajeshkumar Naranbhai con. No. 80619/00422/3 of village Dharmpur is having his ag conn. from ag TC of hvds Dharmpur ag fdr but he took illigal power supply from JGY Kaleswar feeder from Dharampur village TC  through extra  extended illigal cable & connected this power via a connector in such a way that this illgal JGY fdr power from LT bushing of his AG transformer step up & entered in Dharmpur ag fdr which was under line clear condition as Sri Bachubhai Vikrambhai Ram of Contractor Shri Meraman Hamir Solanki was working for new ag con of Varjang Meraman Solanki at vill Dharmpur got electrocuted because of this illigally connected  JGY power & met with a fatal accident.at the same time Kaleswar JGY feeder tripped heavily.necessary action agaist culprit are initiated. Report yet not received NA NA FIR Lodge against Defaulter Farmer and Public Awareness
348 PBR AJAK AG AREA AND DHANSUKHBHAI KARSHANBHAI KARGATHIYA 31.01.15 NFHD A NON FATAL DEPARTMENTAL HUMAN ACCIDENT OCCURED AT MADHAVPUR (GHED) S/DN.THE ACCIDENT OCCURRED DUE TO TAKE LC OF 11KV VADALA AG FEEDER INSTEAD OF 11KV MEHADI AG FEEDER AND DO EARTHING OF 11KV LIVE LINE TO 11KV POLE SUPPORT GUY AND THAT TIME VICTIME TOUTCHES HIS HAND TO POLE SUPPORT GUY AND ELECTROCUTED TO HIS HAND. Report yet not received NA NA NECESSARY INSTRUCTION GIVEN TO ALL LINE STAFF
349 PBR CHHAYA AND RAMESHBHAI SAMJIBHAI POSTARIYA 18.01.15 NFHD On 18- jan-2015 ,at about 09:30 AM, the  staff of emergency shift duty moved to release a new connection in chhaya vankarvas  area ,during the said work , one of employee of shift duty shri Rameshbhai Shamjibhai Postaria ,Electrical Assistant age app. 51 year, while standing in Balcony/ chhaja of new constructed house ,near parapet wall-pillar and watching junction box of nearby LT pole, leaning forward ,the some of stone of parapet wall dislodged from fixing and victim fall on ground-road side .Resulted in injury-facture in right hand wrinkle. Report yet not received NA NA NECESSARY INSTRUCTION GIVEN TO ALL LINE STAFF
350 PBR KANDORNA AND NAGABHAI CHANABHAI CHAVDA 21.02.15 NFHOS As per site inspection & victim's statement victim working with iron bar came in contact with 11kv line during unauthorized building construction first floor centing work near by existing 11kv line without permission and got electrical shock. Report yet not received NA NA Notice Issued
SCN Issued to Village Helper
Sh. H.B.Khira-E.A AND Public Awareness
351 PBR KERALA AND HARDIKBHAI DEVDANBHAI KAMALIYA 01.03.15 NFHOS A outsider non fatal human accident was occured to Sh.Hardik Devdan Kamaliya due to LT Leakage current pass throgh earth wire(G.I.Wire) of LT pole due to LT pvc cable burnt due to rain & wind & touch with earth wire   at  that time the  victim came in contact with earth wire and got electric shok and non fatal accident occured.  Report yet not received NA NA Proper Maintanace Done
352 PBR KUKASWADA AG AREA AND BHIKHABHAI NATHUBHAI PARBAT 27.03.15 FHOS A  fatal human accident occurred at Janjar No Pa. area Jadav Nathu AG T/c at  village Kukasvada Ag area residing at Khambhaliya village. By preliminary investigation, it is found that 11KV D.O Wire of B-Phase was already  blown and fallen on 11KV B-Phase jumper & directly touch to Transformer neutral earthing wire. This earthing wire are openly earth on land through both Pse Pole. One of the psc pole have wound thin copper wire & directly touch earthing wire. Victim might was try to touch said thin copper wire to rectify D.O & came in contact return power flows in thin copper wire & got electrocuted.    Report yet not received NA NA Proper Maintanace Done and Public Awareness
353 PBR SUPASI AND BHIMABHAI SAMJIBHAI SOLANKI 30.03.15 NFHOS A  Non - fatal human accident occurred at Supasi village Ta. Veraval under Supasi AG feeder emitting from Adri 66Kv S/s. By preliminary investigation, it is found that 11 Supasi ag feeder one of the side  conductor broken from pin binding  due to pin fault & jumper of same wire was blown from shackle point pole exactly before said pin fault pole. The victim was doing his natural process of latrine under 11kv said line & came in contact with return conductor of supasi ag feeder. There is no any tripping observe in Supasi ag feeder but line was tripped at 7.30Am by one of the person from supasi village. So victim might got came in contact with return power flows in said broken conductor  & got electrocuted. Report yet not received NA NA Public Awareness
354 JMN Rural ,A cow Unclaimed 10.08.2014  FA As per the the telephonic  messg the site was visited were water logging nearby TC ,primary reason is not found However due to any other unknown source leakage current is suspected at water logging near TC due to water logiing earth leakage current passing through the cow it came in contact with water part only due to return power from near by industrial connection and hence the accident occured Report Not Recived N.A  N.A  Nessary maintanace carried out
355 JMN Rural ,A cow of Tinabhai Khimabhai Aambaliya 11.08.2014  FA As per the the telephonic  messg the site was visited were water logging nearby TC ,primary reason is not found However due to any other unknown source leakage current is suspected at water logging near TC due to water logiing earth leakage current passing through the cow it came in contact with water part only due to return power from near by industrial connection and hence the accident occured Report Not Recived N.A  N.A  Nessary maintanace carried out
356 JMN Patel Colony,male got of Ismail Kadar Manek 15.08.2014  FA Due to arrangement of meter by pass at consumer premises named babulal Madhavji bedi gam con no 32202016325 main service wire insulation was broken by the consumer near the meter box and extra wire was connected to the main service for to By pass the meter for that joint was done by the consumer inside the GI service pipe which was wall maount as there was rain early morning the wall and premises and nearby area was watery on that day though GI pipe wall whole premises and nearby area got electrocuted there was a telehone and psc pole was near the premises was also became electorcuted meanwhile a male got passing nearby the pole and came in contact with the pole or premises and got electrocuted and met with fatal electrical accidet Report Not Recived N.A  N.A  Nessary maintanace carried out
357 JMN  horse of Valjibai Kadava Bhai Bhundiya 01.10.2014  FA HT conductor was snapped due to heavy wind and cylconic effect a about 8.30a.m on 01.10.14 victim came in contact with live wire and got electricuted and met with fatal accident Report Not Recived N.A  N.A  Nessary maintanace carried out
358 JMN  horse of Valjibai Kadava Bhai Bhundiya 01.10.2014  FA HT conductor was snapped due to heavy wind and cylconic effect a about 8.30a.m on 01.10.14 victim came in contact with live wire and got electricuted and met with fatal accident Report Not Recived N.A  N.A  Nessary maintanace carried out
359 JMN Beraja Bhalasan, Giga Bechar Mackwana 04.10.2014 NFHOS A message recived from office staff on dt 04.10.14 site was visited by undersigned on Dt 04.10.14 at a10.00 am and found that victim was reparing the top cover of tanker no GJ 12 Z 3887 owner of tanker clearance between 11 KV kaleshwar line is 14 ft which Report Not Recived N.A  N.A  Safety Awarness programme conducted at various leval
360 JMN Mota lakhiya, Nilesh Iswarlal Parmar 16.10.2014 NFHD At  the time of 11 KV feeder fault Victim was climbing on PSC pole for attending the fault accidently the victim slipped from the pole while trying to take support of V X Arm at meghpar ind Fdr no 2 & Line clear vide LC no 354/ dt 16.10.14 at 10.50 am.was Report Not Recived N.A  N.A  Safety Awarness programme conducted at various leval
361 JMN Timbadi,  Buffalo of Somabhai Momaiyabhai Mori 07.12.14 FA Snapping of HT line Conductor from PSC pole D P in load side at Timbadi Village Line passing through the field 2 No of Buffalo which were standing below the line conductor came in to contact with snaped HT conductor and got electrocuted and died. Report Not Recived N.A  N.A  1 inclide pole made straigh, 1 new pole erected,4 lt line span restringing done..
362 JMN Timbadi,  Buffalo of Somabhai Momaiyabhai Mori 07.12.14 FA Snapping of HT line Conductor from PSC pole D P in load side at Timbadi Village Line passing through the field 2 No of Buffalo which were standing below the line conductor came in to contact with snaped HT conductor and got electrocuted and died. Report Not Recived N.A  N.A  1 inclide pole made straigh, 1 new pole erected,4 lt line span restringing done..
363 JMN Kharedi, A Bullock of Panasara Sureshbhai Ramajibhai 28.12.14 FA While owner was going to his farm with his bullock at that time old LT Deteriorated conductor snapped on his bullock came incontact with live wire and got electric shock and met with fatal accident Report Not Recived N.A  N.A  Nessary maintanace carried out
364 JMN arabalu, Anil Rambhai Damor 07.01.15 FHOS Victim wnet for maintance work with team while he was rejumpering on pole lacoation no PIP-ARB-213,he got electric shock The L C NO 50748 was taken in the morning 10.05 hrs by supervisor D N Chatbar E A along with shre N C Hamal ,short dischage not done Report Not Recived N.A  N.A  Safety Awarness programme conducted at various leval
365 JMN Jamjodhpur, Toofan sardarbhai damor 15.01.15 NFHOS 11 kv vasantpur ag feeder emating form 66 kv jamjodhpur ss on dated 15.01.15 unfortunatly y phase conductor  wire was briken between pin point and jumper and has in hanging position and victim accidnetly came in contact with live wire and got electric sho Report Not Recived N.A  N.A  Detorative conductor replacecd of 4 span & 4 pin insulator, 4 jumper  & 2 disc also replaced of vasantpur ag fedeer & necessary maintanance done
366 JMN sutariya, Khimabhai Arshibhai Barad 05.02.15 NFHOS Victim came in contact with 11 kv HT line Report Not Recived N.A  N.A  proper maintance work carried out
367 JMN lalpur, Sanjaybhai Amrutlal Rathod 20.02.15 NFHD While victim carried out maintanace work on DP of 11 KV Godavari JGY feeder,Unfortunately anchor removed from Disc insulator which fall down in earth and non fatal mechanical accident occurred  Report Not Recived N.A  N.A  strict acction taken  by de tech, memo issued to victim self & also safety trainning,meeting,mockdril regularly conducted at s/dn level to avoid such  accident.
368 JMN Sapar, Buffalo of Pravinsh Dolubha Jadeja  01.03.15 FA 3 Nos of Buffalows were passing nerby Transformer Centere and rain water logging ,lekage current passing through transformer earthing ,Buffalo got electrocuted and fatal accident occurred Report Not Recived N.A  N.A  proper maintance work carried out
369 JMN Sapar, Buffalo of Pravinsh Dolubha Jadeja  01.03.15 FA 3 Nos of Buffalows were passing nerby Transformer Centere and rain water logging ,lekage current passing through transformer earthing ,Buffalo got electrocuted and fatal accident occurred Report Not Recived N.A  N.A  proper maintance work carried out
370 JMN Sapar, Buffalo of Ghelubha Jadeja 01.03.15 FA 3 Nos of Buffalows were passing nerby Transformer Centere and rain water logging ,lekage current passing through transformer earthing ,Buffalo got electrocuted and fatal accident occurred Report Not Recived N.A  N.A  proper maintance work carried out
371 JMN Khiri, Rajeshbhai Ratilal Teraiya 19.03.15 FHOS Accident occurred as victim was unauthorisedhanging /reparing of Dish tv cable on electric pole of 11 KV line of vadha AG dom feeder.The TV Cable came with live line HT conductor and he got electric shock and he got electric shock and met with fatal accid Report Not Recived N.A  N.A  public awarness programes arranged to avoid such accidnets in future
372 BHUJ Kakrva Sim,Latifkhan Firozkhan Baloch 5.10.14 NFHOS THE VICTIM WAS WORKED UNAUTHORISED JUMPERING ON T/C CENTER OF SHREE RAMJI KHIMA UNDARIYA IN KAKARVA AG FDR AND HE MAY GOT INDUCTION OR SHOCK AND FELL DOWN FROM THE STRUCTURE. Report yet not received NA NA NA
373 BHUJ Chobari Substation Yard,Pankajbhai H Prajapati 5.10.14 NFHD AT THE TIME OF REPLACEMENT OF LST T/C CONTACT OF KAKARVA AG FDR,THE VICTIM GOT ELECTRIC SHOCK OR ELECTRIC INDUCTION AND FELL DOWN FROM LST T/C STRUCTURE. Report yet not received NA NA ab cable provided on jgy and ag fdr crossing
374 BHUJ RAPAR,Bhbubhai Dhansukhbhai Bhabhor 9.10.14 NFHD VICTIM WAS WORKED ON PSC POLE SUDDENLY  THE TOP OF PSC POLE BROEN AND VICTIM FELLON DOWN WITH POLE AND GOT INJURY. Report yet not received NA NA old pole replaced by a new pole with all fabrication
375 BHUJ ZARPARA-MUNDRA,Irfan Kasam Manjothi 20.10.14 FHOS JOINT IN SERVICE WIRE OF TUBE LIGHT OF ROAD LIGHT ON THE LT POLE AT WHICH ACCIDENT OCCURRED AT THE EVENING TIME WHEN ROAD LIGHTE ARE ON PHASE OF SERVICE WIRE FROM JOINT TOUCH THE GI EARTH WIRE OF LT POLE.HENCE CURRENT PASSED THROUGH GI EARTH WIRE.WHILE PLAYING VICTIM CAMEIN CONTACT WITH THIS GI WIRE & FELT ELECTRIC SHOCK & DIED. Report yet not received NA NA INFORM TO GRAM PANCHAYAT FOR MAINTENANCE OF ROAD LIGHT & EARTHING PIPE IS PROVIDED AT SITE.
376 BHUJ Manglam Cross road , Bhuj,M U SAMEJA 17.7.14 NFHD SHRI M U SAMEJA (ALM) UNDER BHUJ CITY 1 WAS ATTENDING THE COUPLAINT IN MANGLAM CROSS ROAD AREA. HE WAS ON THE ROOF OF THE SHOP AND SUDDENLY HE SLIPPED FROM THE ROOF & FELL DOWN ON GROUND & GET FECTURE IN HIS LEG. IT IS A MICHNICAL ACCIDENT. Report yet not received NA NA NA
377 BHUJ Dhrobana, 1 cow owner(Amin Hothi Sama) 29.7.14 FA THE TWO COWS WERE GRAZING AND MOVING UNDERNEATH THE 11KV DHARAMSALA JGY FEEDER IN DHROBABA VILLAGE DUE TO PIN FAULT, THE TOP (GROOVE) OF THE PIN BROKEN AND THE CONDUCTER SNAPPED AND WHILE FALLING ON GROUND THE TWO COWS UNDERNEATH CAME IN CONTACT WITH LIVE CONDUCTOR RESULTED INTO FATAL ACCIDENT. Report yet not received NA NA 11 KV PIN INSULATOR WAS REPLACED AND SNAP CONDUCTOR WAS REPLACED ON SAME DAY AND POWER RESTORED.
378 BHUJ Dhrobana, 1 cow owner(Amin Hothi Sama) 29.7.14 FA THE TWO COWS WERE GRAZING AND MOVING UNDERNEATH THE 11KV DHARAMSALA JGY FEEDER IN DHROBABA VILLAGE DUE TO PIN FAULT, THE TOP (GROOVE) OF THE PIN BROKEN AND THE CONDUCTER SNAPPED AND WHILE FALLING ON GROUND THE TWO COWS UNDERNEATH CAME IN CONTACT WITH LIVE CONDUCTOR RESULTED INTO FATAL ACCIDENT. Report yet not received NA NA 11 KV PIN INSULATOR WAS REPLACED AND SNAP CONDUCTOR WAS REPLACED ON SAME DAY AND POWER RESTORED.
379 BHUJ Shivkrupa bagar , Bhuj,K D PARMAR 28.9.14 NFHD SHRI K D PARMAR WAS ATTANDING THE COMPLIAINT AT SHIVKRUPA NAGAR SUDDENLY HE SLIPPED FROM THE POLE TO GROUND DUE TO THIS HE GORT FRACTURED IN HIS LEG TI IS A MICHNICAL ACCIDENT. Report yet not received NA NA NA
380 BHUJ Nutan Tranbo,  BuffALO ,Premjibhai Devabhai Karani 18.9.14 FA At the location site due to snapping of guy wire  of transformer structure by the buffalow , guy insulator broken and current passed through guy wire and   got electrocuted and died
Report yet not received NA NA new guy set provided
381 BHUJ VONDH ,01. BuffALO (owner-PAMIBEN AMBA KAVATRA) 4.11.14 FA At the place of the accident street light was broken  was broken and open phase wire touched to guy wire of the LT pole, and the current passed through the guy wire. While passing from there the buffalo come in contact with guy wire of the LT pole and got electrocuted and died.  Report yet not received NA NA lt ab cable provided and space maintain between street light and guy set
382 BHUJ Patri ,01 Bullock ( Owner-Kanji Rupa Gangal) 5.11.14 FA fatal accident occur when bullock was crossing the way with bullock cart that time came in contact with broken  conductor  of 11kv kundroli feeder. and died same time Report yet not received NA NA CONDUCTOR REPLACEMENT & STRINGING OF CONDUCTOR AND POLE EARTHING WORK
383 BHUJ Patri , Sunil Kanji  Gangal 5.11.14 FHOS fatal accident occur when victim was crossing the way with his bullock cart that time came in contact with broken  conductor of 11kv kundroli feeder.  Report yet not received NA NA CONDUCTOR REPLACEMENT & STRINGING OF CONDUCTOR AND POLE EARTHING WORK
384 BHUJ Dahisara , LAXMIBEN THAKOR 29.11.14 NFHOS VICTIM WAS COLLECTING TREE BRANCHES WHILE CLIMBING ON TREE WITH A GI PIPE OF ABOUT 3 MTR LENGTH AND A IRON HOOK ON THE TOP OF THE GI PIPE.THE HT LINE OF 11 KV MEGHPAR AG FEEDER IS PASSING NEARBY THAT TREE ON WHICH LAXMIBEN WAS CLIMBED MISTAKENLY THE HOOK OF THE GI PIPESTUCK IN THE LINE WITH PHASE CONDUCTOR OF THE MEGHPAR AG FDR.AT THAT TIME THE 11KV MEGHPAR AG FDR WAS IN 3 PHASE POWER TIME AND AS THE GI PIPE WAS IN THE HAND OF LAXIMBEN.SHE GOT ELECTRIC SHOCK AND FELL DOWN FROM THE TREE. Report yet not received NA NA ARRANGED PUBLIC AWARENESS PROGRAM 
385 BHUJ Deshalpar , Mariyabai Sumar Koli 21.12.14 NFHOS on dtd:21.12.2014 at @ 14.10 hrs, due to bird fault , 11kv pin insulator broken  and power passing through earthing wire, which it is already binding with fencing wire at the time victim might  have came in contact  fencing wire. She got electric shock and resulting non fatal accident Report yet not received NA NA Faulty Pin replaced and instructed to owner to remove fencing from 11kv pole of feeder.
386 BHUJ HAJAPAR, HARSADKUMAR DAMJIBHAI JANGAM 3.1.15 FHD A complaint of AG consumer named Babulal Samji Bhanushali of village Hajapar was lodged on 3-1-2015. This connection was connected to 11KV Nanavada AG feeder from 66KV Hajapar S/S. Victim H.D. Jangam was Electrical Asistant (village helper) of Hajapar Village. So Shri H D Jangam had gone to attend the complaint where a LT conductor was broken.  A prearranged shut down was scheduled of 11 KV Nanavada ag feeder, from 66KV Hajapar S/S to carry out maintenance of the line. Line clear permit was taken by ALM–shree P.K. Gadhavi at 9:45 AM on 3-1-2015.

As victim shri H D Jangam had to carry out complaint attending work in same feeder for which line clear was taken by Shri P K Gadhavi, victim had telephonic communication with ALM shree P.K. Gadhavi and after confirming the fact with Shri Gadhvi that line clear was taken, the victim started work of repairing of snapped conductor of LT line of 63 KVA –Parvatiben Monji ag group transformer. The transformer was connected on 11 KV Nanavada AG feeder. The victim had competed conductor joining work from one side of broken LT line conductor. While repairing (Joining) of other side of conductor, power was restored from 66 KV Hajapar SS in 11KV Nanavada AG feeder, even though line clear permit was NOT RETURNED by ALM Shree P.K. Gadgavi. The sub station staff had energized said feeder without returning of Line clear by Shri Gadhvi and ultimately victim was electrocuted on the spot. 
       
As per detail investigation report, MRI data, Log book and statement of staff, it is clear that sub division staff had energized 11 KV Nanavada AG feeder without confirming or getting mandatory return of Line clear permit from Shri Gadhvi. Thus, Sub station staff is primarily responsible for this accident.
Report yet not received NA NA COnductor replaced, AB switch provided , Line staff were strictly instructed to utilised safety gadgets and isolate sections before starting the wotrk.
387 BHUJ sanghad,   1 nos of buffalo owner of this buffolo is chana ganga maytra 26.1.15 FA as per preliminary investigation, A buffalo came in contact with the broken conductor and got electrocuted and result into fatal accident. As there is no any tripping occurred in the 11 kv jogninar jgy feeder at 66kv kidana ss after snapping of conductor  Report yet not received NA NA PROVIDING NEW CONDUCTOR OF THAST SECTION AND ALSO RETRING 
388 BHUJ Narayan Sarovar, 1 cow, Owner: Umarbhai   Salebhai Bhadala 21.2.15 FA 11 KV conductor was snapped due to tree branches thrown on 11 KV live line by some illiterate and unsocial element.  The tree branch   was fixed between straight -cross arm and conductor. Due to moisture an electric path occured between straight-cross arm and conductor, thus continuous sparking occured at conductor result in to a conductor snapped and fall down on animals passing under the line and got electrocuted. Report yet not received NA NA NECESSARY MAINTENANCE WORK DONE LIKE OLD COND. REPLACEMENT, EARTHING ACTIVATION AT POLE & TRANSFORMER CENTER.
389 BHUJ Narayan Sarovar,  1 nos she buffalos, Owner: Umarbhai   Salebhai Bhadala 21.2.15 FA 11 KV conductor was snapped due to tree branches thrown on 11 KV live line by some illiterate and unsocial element.  The tree branch   was fixed between straight -cross arm and conductor. Due to moisture an electric path occured between straight-cross arm and conductor, thus continuous sparking occured at conductor result in to a conductor snapped and fall down on animals passing under the line and got electrocuted. Report yet not received NA NA NECESSARY MAINTENANCE WORK DONE LIKE OLD COND. REPLACEMENT, EARTHING ACTIVATION AT POLE & TRANSFORMER CENTER.
390 BHUJ Narayan Sarovar,  1 nos she buffalos, Owner: Umarbhai   Salebhai Bhadala 21.2.15 FA 11 KV conductor was snapped due to tree branches thrown on 11 KV live line by some illiterate and unsocial element.  The tree branch   was fixed between straight -cross arm and conductor. Due to moisture an electric path occured between straight-cross arm and conductor, thus continuous sparking occured at conductor result in to a conductor snapped and fall down on animals passing under the line and got electrocuted. Report yet not received NA NA NECESSARY MAINTENANCE WORK DONE LIKE OLD COND. REPLACEMENT, EARTHING ACTIVATION AT POLE & TRANSFORMER CENTER.
391 BHUJ Dhrobana,   Sheep ( 1 Nos.) Owner (Sama Amar Pathai) 4.2.15 FA While investigation it is found in Preliminary stage, the accident occurred at Dhrobana Kalodungar main road. The two sheep were grazing at farm near to road, which is near to the 11kv DHARAMSALA JGY FEEDER. At that time, all of sudden 11KV conductor Brocken near 11KV disc insulator and due to 11KV disc Insulator fault. Due to it conductor snapped and while falling on ground, the body parts of sheep came in contact with the Brocken conductor and got electrocuted and died on the spot at once. Brocken conductor has been found from this place and also noticed deep burnt injuries on both sheep at that place.
Report yet not received NA NA Conductor replaced.
392 BHUJ Dhrobana,   Sheep ( 1 Nos.) Owner (Sama Amar Pathai) 4.2.15 FA While investigation it is found in Preliminary stage, the accident occurred at Dhrobana Kalodungar main road. The two sheep were grazing at farm near to road, which is near to the 11kv DHARAMSALA JGY FEEDER. At that time, all of sudden 11KV conductor Brocken near 11KV disc insulator and due to 11KV disc Insulator fault. Due to it conductor snapped and while falling on ground, the body parts of sheep came in contact with the Brocken conductor and got electrocuted and died on the spot at once. Brocken conductor has been found from this place and also noticed deep burnt injuries on both sheep at that place.
Report yet not received NA NA Conductor replaced.
393 BHUJ Rapar,, DINESH MALSHI MAHESHWARI 24.2.2015 NFHOS The location of accident is situated in Odhadvadi society, court road Raparcity.  The victim was worked under 11kv Rapar city feeder. During the construction work might be came in contact with 11kv line and got electric shock at Oghadvadi, Rapar city. After accident the victim was taken to hospital and further treatment was done at Rajkot. Further report and detail investigation under process. Report yet not received NA NA Conductor re-stringing and PVC pipe provided in every phase of that span
394 BHUJ Kakarva SIm,   Rameshbhai Desalbhai Koli 14.3.2015 FHOS The location of accident is situated in kakarava village at Hajamvadi Vadi vistar/pankhadi vadi vistar,this accident  happened on 14.3.15 but no reported to this office. On 16.03.15 at 16:30 police Head constable,Bhachau came and inform by letter about accident . On Dt: 17.03.2015 our site visit statement recorded from eye witness shri Ramjibhai dhanabhai koli, the victim go to  on transformer D.P. for unauthorized electric work.  Due their fault victim may be got electric shock .The details of PM report and  Other documents  awaited . Report yet not received NA NA T/C CENTER AND T/C MAINTENANCE WORK DONE
395 BHUJ Bheraiya,   Jaymalsinh Pathubha Rathod 29.3.2015 FHOS A fatal accident to human outsider at village Bheraiya on dated 29.3.2015 . SDn came to know about the accident through newspaper report, so they visited the site. From the prilimnary information gathered, it is most likey the case of suicide in which the victim deliberately climbed on the line and electrocuted. Report yet not received NA NA  
396 JND SHRI RAMABHAI  RANABHAI CHUDASAMA  VILLAGAE: INDROI   TALUKA:VERAVAL 29-09-14 NFHOS DURING THE TRANSFORMER REPLACEMENT WORK UNAUTHORISED PERSON (VICTIM) CLIMBED ON THE POLE FOR JUMPER REPAIRING IN PRESENCE OF SUPERVISOR A. M. THAKOR(ELECT ASST). LINE CLEAR WAS TAKEN BY A . M THAKOR (ELECT ASST) FROM LINE MAN U.N. MURABIYA. BUT DURING THE RETURN OF LINE CLEARANCE WRONG RETURN WAS DONE FROM LINE MAN AND AS A RESULT. VICTIM DIRECTLY CAME IN CONTACT WITH LIVE POWER AND MET WITH NON FATAL ACCIDENT REPORT YET NOT RECEIVED NA NA Victim himself is repsonsible as he climbed or was performing unauthorised work.
397 JND SHRI JATINBHAI  LAXMANBHAI  VALODRA  VILLAGAE: BHALGAM   TALUKA:JUNAGADH, BILKHA Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 02-10-14 NFHD WHEN VICTIM WAS PERFORMING MAINTENANCE ACTIVITY ON AG TC WITH LINE CLEAR AND AND OTHER SAFETY PRECAUTIONS. DURING THIS ACTIVITY ON SAME FEEDER ONE FARMER WAS REMOVING VELAT CROSSING POINT OF JGY AND AG AND THE STRETCHED LT AG CONDUCTOR GOT TOUCHED WITH JGY AND REVERSE POWER CAME AND VICTIM GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT. REPORT YET NOT RECEIVED NA NA Action taken against Defaulter. And as per site verification no maintenance needed.
398 JND COW (INDIAN) OF SHRI  JAGDISHBHAI  GANDUBHAI  GAMARA      VILLAGE: NANI MONPARI   TALUKA: VISAVADAR, VISAVADAR-2 Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 02-10-14 FA DUE TO HEAVY RAIN & WIND PRESSURE LT LINE WIRE BROKEN & COW CAME CONTACT WITH LT LINE AND GOT ELECTROCTED AND MET WITH FATAL ACCIDENT REPORT YET NOT RECEIVED NA NA Re stringing along with whole iron part including C clamp and Shackle insulator replaced.
399 JND SHE BUFFALO OF SHRI BHIMABHAI  KANABHAI MUCHHAL      VILLAGE: TALALA   TALUKA: TALALA, TALALA Sub-division, VERAVAL Division, Junagah Circle 03-10-14 FA DUE TO HEAVY RAIN & WIND PRESSURE LT LINE WIRE BROKEN & BUFFALO CAME IN CONTACT WITH LT LINE AND GOT ELECTROCTED AND MET WITH FATAL ACCIDENT. REPORT YET NOT RECEIVED NA NA Re stringing along with whole iron part including C clamp and Shackle insulator replaced.
400 JND SHRI SHARDABEN KISHORBHAI  RIBDADIYA  VILLAGAE: SARSAI   TALUKA:VISAVADAR, VISAVADAR-2 Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 07-10-14 NFHOS LT LINE WIRE SNAPPED FROM LT SHACKLE INSULATOR AND CAME IN CONTACT WITH C CLAMP. AS A RESULT LEKEAGE CURRENT PASSED THROUGH EARTH WIRE WHICH CAME IN DIRECT CONTACT WITH VICTIM. AND VICTIM GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT. REPORT YET NOT RECEIVED NA NA Re stringing along with whole iron part including C clamp and Shackle insulator replaced.
401 JND SHRI  RAMESHBHAI  HIRABHAI  DAVERA  VILLAGAE: ZALANSAR   TALUKA:JUNAGADH, JND RURAL Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 14-10-14 FHOS VICTIM CLIMBED ON TRANSFORMER IN DRUNKED POSITION AND SOME HOW CAME IN CONTACT WITH LIVE PART AND GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. REPORT YET NOT RECEIVED NA NA N.A
402 JND SHRI  SURYAKANTBHAI  BHAVCHANDBHAI  SANGANI  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH, GANDHIGRAM Sub-division, JUNAGADH CITY Division, Junagah Circle 11-10-14 FHOS VICTIM IN PROCESS OF DISCONNECTING THE HALOGEN FROM HIS TERRACE, WHICH WAS HAVING A FLEXIBLE LONG WIRE AT ITS END FOR FIXING PURPOSE CAME IN CONTACT WITH NEAR BY 11 KV LIVE WIRE AND GOT A JERK AND VICTIM  FALL DOWN  FROM TERRACE AND MET WITH ACCIDENT. DETAIL INVESTIGATION IS UNDER PROCESS.  REPORT YET NOT RECEIVED NA NA N.A
403 JND SHRI RAMESHBHAI MAGANBHAI TANK  VILLAGAE: MOTIMONPARI   TALUKA:VISAVADAR, VISAVADAR-2 Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 29-10-14 NFHD VICTIM CLIMBED ON TC FOR MAINT WORK AND SOME HOW GOT ELECTROCUATED AND MET WITH NON FATAL HUMAN DEPARTMENTAL ACCIDENT.DETAIL INVESTIGATION IS UNDER PROCESS. REPORT YET NOT RECEIVED NA NA Action taken against Defaulter. And as per site verification no maintenance needed.
404 JND SHRI  AMRUTLAL  HIRABHAI  VALA  VILLAGAE: IVANAGAR   TALUKA:JUNAGADH, JND RURAL Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 06-11-14 NFHD VICTIM WAS INSPECTING SERVICE WIRE OF THE CONNECTION, WHICH WAS TIED WITH PARAPET TO GET A FAULT IF ANY. MEANWHILE PARAPET WAS BROKEN & FALLEN DOWN ALONG WITH VICTIM, HIS HELMET WAS BLOWN OUT &  HE GOT INJURIES. REPORT YET NOT RECEIVED NA NA N.A
405 JND SHRI  HITESHBHAI  DAYARAM  CHAUHAN  VILLAGAE: ANKOLWADI   TALUKA:TALALA, ANKOLVADI Sub-division, VERAVAL Division, Junagah Circle 18-11-14 FHD VICTIM WAS ATTENDING AG FAULT OF LT GROUP KNOWN AS PAGDHAR GROUP WITH ITS DO FUSE OPEN. AND THERE WAS A CROSSING OF 11 KV AG FEEDER VICTIM CARELESSLY HAD DISCONNECTED THE SECTION OF 11 KV OTHER THAN THE ONE CROSSING AND SOME HOW CAME IN DIRECT CONTACT WITH 11 KV AG CROSSING. WITHOUT USING ANY SAFETY GADGETS. NO SUPERVISOR WAS INVOLVED AS IT WAS AN AG CONSUMER FAULT. REPORT YET NOT RECEIVED NA NA No work needed as per site verification.
406 JND SHE BUFFALO OF SHRI YUSUFBHAI  HUSENBHAI  SIDA      VILLAGE: VIRPUR   TALUKA: JUNAGADH, JND RURAL Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 12-12-14 FA WHEN SDO VISITED THE SITE, NO LEAKAGE CURRENT FOUND AT T/C EARTHING, AS TC & LT WAS CHARGED COMPLETELY. INCIDENCE OCCURRED MIGHT BE DUE TO LEAKAGE CAUSED BY UNAUTHORIZED HOOKING. REPORT YET NOT RECEIVED NA NA N.A
407 JND SHRI  JITESHBHAI  GOVINDBHAI  CHAUHAN  VILLAGAE: JUNAGADH   TALUKA:JUNAGADH, JND RURAL Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 15-01-15 FHOS VICTIM (LABOUR) WAS IN PROCESS OF CONSTRUCTION ON TERRACE OF SHOP AND IN PROCESS CAME IN VICINITY OF NEARBY 11 KV LIVE WIRE AND CAME GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. AS NO TRIPPING WAS OCCURRED DETAIL INVESTIGATION IS UNDER PROCESS. REPORT YET NOT RECEIVED NA NA N.A
408 JND SHRI  BHAGVANBHAI  PARBATBHAI  BHOLA  VILLAGAE: LODHAVA   TALUKA:SUTRAPADA, PRANCHI Sub-division, VERAVAL Division, Junagah Circle 18-02-15 FHOS WHEN VICTIM WAS DOING UNAUTHORISE JUMPERING WORK ON VILLAGE TRANSFORMER CENTER WITHOUT ANY PERMISSION CAME INTO CONTACT WITH LIVE POWER OF 11KV LAXMI JGY FEEDER AND MET WITH FATAL ACCIDENT. REPORT YET NOT RECEIVED NA NA NA
409 JND SHRI ARJANBHAI MULUBHAI ZALA  VILLAGAE: UMBARI   TALUKA:SUTRAPADA, PRANCHI Sub-division, VERAVAL Division, Junagah Circle 25-02-15 NFHOS WHEN VICTIM WAS PASSING UNDER 11 KV LINE, CONDUCTOR SNAPPING TOOK PLACE AND FELL ON VICTIM. AS A RESULT VICTIM GOT ELECTROCUATED AND MET WITH NON FATAL ACCIDENT.DETAIL INVESTIGATION IS UNDER PROCESS. REPORT YET NOT RECEIVED NA NA Re stringing along with whole iron part including C clamp and Shackle insulator replaced.
410 JND SHRI RAMESHBHAI BAPUBHAI  DAMOR  VILLAGAE: MOTI MONPARI   TALUKA:VISAVADAR, VISAVADAR-2 Sub-division, JUNAGADH RURAL-1 Division, Junagah Circle 17-03-15 FHD VICTIM WAS INVOLVED WITH PROVIDING LT SINGLE PHASE SERVICE. VICTIM DID NOT TOOK LINE CLEAR BUT HE TOLD SBO OF 66 KV SS MOTIMONPARI TO PUT IN PF. THE FEEDER WAS PLACED IN PF MODE. HE HAS NOT ISOLATED BY REMOVING DO OF TC AND WITHOUT ANY PROPER EARTH. AFTER SOME TIME THE RACK OF BREAKER GOT FAILED AND A SHORT CKT TOOK PLACE AND DUE TO THIS ONE PHASE FOT ENERGIZED AND DUE TO THIS VICTIM GOT ELECTROCUATED AND MET WITH FATAL ACCIDENT. DETAIL INVESTIGATION IS UNDER PROCESS. REPORT YET NOT RECEIVED NA NA As SBO of GETCO was responsible DA taken on him.
411 BVN Bhavnagar-Puriben Bhupatbhai Aal 16-Nov-14 FHOS The Victim Was Doing Unauthorised Work By Putting Wet Clothes On G.I.Wire Binded With Psc Pole & Leakage Current Passed Through Broken Service Which Was Damaged at early Morning Due To Rain.  Report Not Received NA. NA. due to rain service wire is broken & replace it
412 BVN Thaliya-Rudiben Jivabhai Makawana 17-Nov-14 FHOS Fatal Human accident ouccred due to HT Conductor snapped from 11 KV Pin Insulator and fall on Victim Smt. Rudiben Jivabhai & Got heavy electric Shock While she was Cooking outside of her House ( Faliyu).  and at the time rain also falling. Report Not Received NA. NA. Replacemernt Conductor & providing  Gaurding and also periodically maintance carried out
413 BVN Dudhala-2-Babusing Sulehsing Chauhan 12-Dec-14 FHOS The victim was passing under HT Line of 11Kv Shardika AG Feeder with vehical (chotta haathi) With his co-ordinates in the farm of shri Jilubhai Hakabhai Bhukan, for digging of well, and the vehical came in contact with live HT Line conductor, the vehical stuck in the conductor and for removing obstruct of conductor the victim step out from vehical to ground level and during that victim get electric shock from electrically charged vehical and hence human fatal accident occured Report Not Received NA. NA. gross neglegency by Vicitm
414 BVN Habukavad-Mathurbhai Tapubhai Yaki ( Devipujak ) 9-Feb-15 FHOS At Manubhai Amarjitbhai Pandiya Valu TC, at sixth span of LT line Conductor of this Tc center, one conductor broken and first span two conductor broken and at first span one R phase conductor touch with fancing wire only and only due to the illligal activity at third pole from Tc center shri jayantibhai meghjibhai pandya make power theft direct lunger.  Due to and during this illegal power theft process two LT phase power come in contact with each other and heavy spark occur, due to this reason conductor snaping at sixth and first span. And first span r phase snapped conductor  touch farm fencing wire and current passing throught fancing wire at this time Mathurbhai Tapubhai Yaki which working at farm of danjibhai dalpat bhai pandya which is coming touch with fencing wire and current  passing through his body and met with fatal accident.  Report Not Received NA. NA. illigali activity done by Sh. Pandya & conductor snapped & periodically maintance should be done
415 BVN Manar-Atulbhai Maganbhai Parmar - EA 22-Feb-15 FHD Departmental Electrical Fatal & Non-Fatal Human  accident occured to Electrical Assistant While Jumpering Worked on DP Structure of Transformer Centre & at the time Suddenly 11KV Power Supply made ON by Line Inspector Sh. JT Dund Without any confermation  With  the Deputy Engineer. Now Matter is under Investigation & detailed cause of accident report will be Submitted Very Soon. Report Not Received NA. NA. gross neglegency by Vicitm
416 BVN Manar-Ranjeetbhai Ranabhai Bhil - EA 22-Feb-15 NFHD Departmental Electrical Fatal & Non-Fatal Human  accident occured to Electrical Assistant While Jumpering Worked on DP Structure of Transformer Centre & at the time Suddenly 11KV Power Supply made ON by Line Inspector Sh. JT Dund Without any confermation  With  the Deputy Engineer.  Report Not Received NA. NA. gross neglegency by Vicitm
417 BVN Pithalpur-Hareshbhai L Acharya - Contractor Person's 7-Mar-15 NFHOS Non-Fatal Contractor's Person accident occured during he was climbed on transformer DP Centre for  replacement of failed transformer & Suddenly he got electric shock. The statement is awaited of Vicitm and also  reason of Power Supply at Transformer DP is to be Investigate.  The detailed report will be submitted very soon as how accident occured & statement of Vicitm taken Report Not Received NA. NA. gross neglegency by Vicitm & Supervisory Staff
418 BVN Akhegadh-Bababhai Apabhai Vaghosi 20-Mar-15 FHOS Fatal Human accident occured due to unathorized worked done by Victim on 10 KVA Transformer centre & might be he came in contact with live  part of transformer & got electrical shock.  Report Not Received NA. NA. gross neglegency by Vicitm
419 BVN Mota-Charodiya Bullock- Manubhai Ravjibhai Zalavadiya 30-Jan-15 FA Fatal animal accident occurred due to LT shackle binding wire are re-opned & LT Conductor touched to C-Clamp due to Wind pressure & rainy season.currrent passing through Shackle to earth wire of PSC Pole and bullock came in contact with live earth wire and got electric Shock Report Not Received NA. NA. If proper maintenance done
420 BTD Location-Botad. Sh. SANKARBHAI SHANTIBHAI PANDOR 10.10.2014 NFHOS As on dated 10.10.2014 in evening victim was on advertisement hoarding tower & he try to up private iron wire which is connected with hoarding angle at a time iron wire touch with bottom wire of 11KV city feeder by mistake & he shocked & fall down on ground. NA NA NA NA
421 BTD Location-Alampar,Gadhada.Cow of Shri Arjanbhai Bijalbhai Khatana 21.10.2014 FA At village Alampar, near Bapa Sitaram Madhi, a DTC of 16 KVA is erected for W/w connection. There is sump near the w/w connection. Water supply of the sump is coming from the Kalatalav Water Head Pump. The wall of the sump is damaged and water is coming out of the sump. So there is a water clogging in surrounding area including the place of DTC.  Due to clogging of water and also earthing was deteriorated and the earhting of the DTC was joined with guy wire by someone else. Due to leakage current of the earthing the guy wire and surround water was electrocuted. The cow of Shri Arjanbhai Bijalbhai Khatana came near the DTC to drink the water. It might get shock and died.    NA NA NA NA
422 BTD Location-Nagalpar,Botad. Buffalo of Shri VELABHAI RATNABHAI HADGADA 18.11.2014 FA On above date & time the buffalo was shacking horns near transformer centre earthing, and its horns stuck with earthing wire and earthing wire was broken, hence return current passing through earthing, and buffalo got electrocuted and died.   NA NA NA NA
423 BTD Location-Dhankaniya Road,Botad. Buffalo of  Shri  JASABHAI BHIMABHAI  KHAMBHALIYA 07.02.2015 FA Due to unknown truck accident with streetlight pole & snapping of streetlight neutral conductor and conductor  fall down under river at a time one buffalo passing and contact with conductor thus electric Fatal Animal accident occurred.   NA NA NA NA
424 AMR DINESHBHAI DHIRUBHAI BAMBHANIYA(CONTRACTOR PERSON)JAMANVADAKODINAR 12-Oct-14 FHOS AT THE TIME OF  TAKING SHAPE OF CONDUCTOR OF NEW AG CONNECTION  WHILE HE WAS WALKING ON THE SAND DUNE WITH GRAVEL’S ,SUDDENLY HIS LAG SLIP AND HE  FALLS  DOWN ON THE SAND DUNE WITH GRAVEL’S AND HE GOT INJURY TO HIS BRAIN AND PROBABLY HE DIED DUE TO BRAIN HEMORRHAGE.   NOT YET RECEIVED N.A N.A Awareness among contractors regarding safety in every meeting
425 AMR MUKESHBHAI VAGHABHAI DABHISIMARUNA 25-Oct-14 FHOS MUKESH VAGHA DABHI, RES. SIMAR CLIMBED ON 11 KV LIVE LINE TO COMMIT SUICIDE.  THE VICTIM GOT ELECTROCUTED AFTER COME IN CONTACT WITH LIVE ELECTRIC LINE. NOT YET RECEIVED N.A N.A Public awareness for safety during village meeting and khedut shibir.
426 AMR SHRI JENTIBHAI JIVABHAI PARMAR(CONTRCTOR PERSON)
31-Oct-14 NFHOS THE ACCIDENT OCCURRED TO CONTRACTOR PERSON DURING NEW TRANSFORMER WORK EXECUTION AT VILLAGE:UMEJ. THE TRANSFORMER WAS PROPOSED TO RELEASE 10 HP FLOOR MILL CONNECTION OF DADU GIGA BAMBHANIYA, AS WELL AS TO RESOLVE LOW VOLTAGE PROBLEM OF TAIL END CONSUMER. THE HT LINE & TRANSFORMER CENTRE ERRECTION WORK WAS COMPLETED PREVIOUSLY. THE 8 SPAN LT CABLE PROVIDING WORK IS PLANNED TODAY BY VILLAGE HEPLER SH RATHOD HIMSELF WITHOUT INFORMING TO SDO OR ANY JUNIOR ENGINEER OF S/DN. SH.RATHOD HAS NEITHER TAKEN LINE CLEAR NOR SHORT OR EARTH HT LINE PASSING OVER THROUGH TRANSFORMER CENTRE, HENCE WHEN CONTRACTOR PERSON CLIMB ON TC CENTRE THE JUMPER PROVIDED BETWEEN DISC INSULATOR & DO FUSE TOUCH TO HIM, RESULTING OCCURRENCE OF ACCIDENT. APPROVAL FOR SUSPENSION OF HELPER WITH IMMEDIATE EFFECT IS ACCORDED TODAY NOT YET RECEIVED N.A N.A Awareness among contractors regarding safety in every meeting
427 AMR SHRI VIPULBHAI KANABHAI GOHIL(CONTRCTOR PERSON)UMEJUNA 31-Oct-14 NFHOS THE ACCIDENT OCCURRED TO CONTRACTOR PERSON DURING NEW TRANSFORMER WORK EXECUTION AT VILLAGE:UMEJ. THE TRANSFORMER WAS PROPOSED TO RELEASE 10 HP FLOOR MILL CONNECTION OF DADU GIGA BAMBHANIYA, AS WELL AS TO RESOLVE LOW VOLTAGE PROBLEM OF TAIL END CONSUMER. THE HT LINE & TRANSFORMER CENTRE ERRECTION WORK WAS COMPLETED PREVIOUSLY. THE 8 SPAN LT CABLE PROVIDING WORK IS PLANNED TODAY BY VILLAGE HEPLER SH RATHOD HIMSELF WITHOUT INFORMING TO SDO OR ANY JUNIOR ENGINEER OF S/DN. SH.RATHOD HAS NEITHER TAKEN LINE CLEAR NOR SHORT OR EARTH HT LINE PASSING OVER THROUGH TRANSFORMER CENTRE, HENCE WHEN CONTRACTOR PERSON CLIMB ON TC CENTRE THE JUMPER PROVIDED BETWEEN DISC INSULATOR & DO FUSE TOUCH TO HIM, RESULTING OCCURRENCE OF ACCIDENT. APPROVAL FOR SUSPENSION OF HELPER WITH IMMEDIATE EFFECT IS ACCORDED TODAY NOT YET RECEIVED N.A N.A Awareness among contractors regarding safety in every meeting
428 AMR ARVINDBHAI JASABHAI SOYA JARAKHIYA LATHI 4-Nov-14 FHOS WHILE VICTIM WAS LOADING RAW COTTON IN TEMPO(WHICH TOP IS EXTENDED) AT THAT TIME VICTIOM CAME IN CONTACT WITH 11 KV LINE PASSING OVER THE TEMPO AND GOT ELECTROCUTED. NOT YET RECEIVED N.A N.A GROUND CLEARANCE DONE AS PER REC NORMS BY INSERTION OF NEW PSC POLE
429 AMR 1 BUFFALO OF SHRI NATHABHAI DHANABHAI JINJALARAJULARAJULA 7-Nov-14 FA THE JUMPER OF LINE TOUCH TO GUY DUE TO WIND.. THE GUY INSULATOR WAS PROVIDED BUT  ABOVE JUMPER HEIGHT HENCE BUFFALO GOT ELECTROCUTED NOT YET RECEIVED N.A N.A DETAILED MAINTENANCE CARRIED OUT ON SHACKLE POLE
430 AMR LAXMANBHAI ATUBHAI SHIYAL(FATAL)
10-Nov-14 FHOS THE ACCIDENT HAVE BEEN OCCURRED DURING CONSTRUCTION WORK AT HOUSE OF  SURESHBHAI VALJIBHAI VAGHELA AT VILLAGE: HARNMADIA. THE 11 KV HARMADIA AG FEEDER PASSING NEAR THOUGH HOUSE OF SURESHBHAI BUT SURESHBHAI HAS EXTENDED 4 TO 5 FT. BALCONY  & DURING ELEVATION WORK OF WALL NEAR THE TERRACE, THE VICTIM TOUCH TO LINE, RESULTING OCCURRENCE OF FATAL & NON FATAL ACCIDENT . THUS THE ACCIDENT IS OCCURRED ONLY DUE TO UNAUTHORIZED WORK CARRIED OUT BY SURESHBHAI VALJIBHAI WITHOUT APPLYING FOR LINE SHIFTING. THE DEPUTY ENGINEER-KODINAR  2 S/DN.IS INSTRUCTED TO LODGE FIR AGAINST CULPRIT.  NOT YET RECEIVED N.A N.A Public awareness for safety during village meeting and khedut shibir.
431 AMR MOHANBHAI DEGANBHAI BAMBHANIYA(NON FATAL) HARAMADIYA KODINAR 10-Nov-14 NFHOS THE ACCIDENT HAVE BEEN OCCURRED DURING CONSTRUCTION WORK AT HOUSE OF  SURESHBHAI VALJIBHAI VAGHELA AT VILLAGE: HARNMADIA. THE 11 KV HARMADIA AG FEEDER PASSING NEAR THOUGH HOUSE OF SURESHBHAI BUT SURESHBHAI HAS EXTENDED 4 TO 5 FT. BALCONY  & DURING ELEVATION WORK OF WALL NEAR THE TERRACE, THE VICTIM TOUCH TO LINE, RESULTING OCCURRENCE OF FATAL & NON FATAL ACCIDENT . THUS THE ACCIDENT IS OCCURRED ONLY DUE TO UNAUTHORIZED WORK CARRIED OUT BY SURESHBHAI VALJIBHAI WITHOUT APPLYING FOR LINE SHIFTING. THE DEPUTY ENGINEER-KODINAR  2 S/DN.IS INSTRUCTED TO LODGE FIR AGAINST CULPRIT.  NOT YET RECEIVED N.A N.A Public awareness for safety during village meeting and khedut shibir.
432 AMR PURANBHAI NURABHAI(CONTRACTOR)BABRABABRA 14-Dec-14 FHOS LINE CONTRACTOR’S SUPERVISOR DEMANDED LINE CLEAR FOR    RAMAPIR  JGY FEEDER WHERE  AS WORK TO BE ON 11 KV GIDC     FEEDER. PURAN NURA   WAS CLIMBING ON GIDC FEEDER  POLE  AND HE WAS TOUCH TO THE 11 KV JUMPER LYING ON POLE AND HE WAS GOT ELECTRICAL SHOCKED AND AN ACCIDENT OCCURRED. THIS TYPE OF LACUNA CAUSE OF ACCIDENT. NOT YET RECEIVED N.A N.A Awareness among contractors regarding safety in every meeting
433 AMR WILD ANIMAL(LEOPARD)JUNA MALAKNESKHAMBHA 19-Dec-14 FA THE PRIMARY REASON OF AN ELECTRIC SHOCK WAS DUE TO DIRECT CONTACT OF LIVE THIN WIRE WHICH IS USED FOR BOUNDING OF STEEL WAS SPREAD IN THE FARM TO AVOID WILD ANIMALS FROM COMING IN TO SAVE THEIR CROPS. POWER SUPPLY WAS FED IN A THIN WIRE FOR THE SAID PURPOSE BY FARMER NAMED RUKHADBHAI NAZABHAI VAHELA OF VILL: JUNA MALAKNESH. A SHE LEOPARD GOT AN ELECTRIC SHOCK AND MET WITH FATAL ACCIDENT. PM REPORT AND DETAILED INVESTIGATION FOLLOWS. NOT YET RECEIVED N.A N.A DETAILED MAINTENANCE CARRIED OUT ON SHACKLE POLE
434 AMR SHRI SAVARBHAI PURANBHAI RAJPUT(CONTRACTOR)KAGDADIBAGASARA 12-Jan-15 NFHOS WHEN WICTIM WAS CARRIED OUT MAINTANCE WORK ON TAPPING POLE  OF 11 KV MAHESWER AG FEEDER EMANATING FROM 66 KV KAGDADI S/S NEAR NEAR JAYNTIBHAI RAVJIBHAI DHADUK NI VADI  FOR RESTRINGING OF LOOS SAPN AND GUY WIRE BREAK FROM BINDING WITH FEBRICATION ALSO POLE BREAK FROM BOTTOM LEVEL ABOUT 3 FEET FROM GROUND LEVEL AND VICTIM FELLDOWN FROM POLE ABOUT 6 FEET & GOT NON FATAL MECHENICAL ACCIDENT, ASLO GET INJURED ON LEFT HAND & LEG,  AFTER THAT HE HOSPITALISED AT GOVT. REFRAL HOSPITAL –BAGASARA THEN SHIFTED TO DR. KAMLIYA HOSPITAL-BAGASARA, THEN HE ADMIT IN AMRELI DAVE ORTHOPEDIC HOSPITAL FOR MORE TREATMENT. WHERE IT IS FOUND THAT VICTIM ALSO GOT INJURY IN SPAINAL CORE (L1). NOT YET RECEIVED N.A N.A Awareness among contractors regarding safety in every meeting
435 AMR SURESHBHAI KALYANBHAI RAVAL(CONTRACTOR)
20-Jan-15 FHOS ON DATED:20.01.15,AFTERNOON SEASON, CONTRACTOR B.B.RAMANI- LABORS DEPUTED FOR MAINTAINCE OF 11 KV BHESAWADI AG FEEDER AT PREMAJI KESHAV GROUP.LINE MAN SH.TADAVI HAS TAKEN LINE CLEAR OF BHESAVADI FEEDER & INSTRUCT CONTRACTOR PERSON TO MAKE LINE SHORT,EARTHED BUT HE HIMSELF NOT CHECKED BY MAKING LINE SHORT OR EARTHED. WHEN LABORS CLIMB ON POLE TO EARTH THE LINE & REMOVING OF JUMPER ON  2 DIFFERENT POLE ACCIDENT OCCURRED. DETAIL REPORT IS AVIATED NOT YET RECEIVED N.A N.A CROSSING OF 11 KV LINE AND LT LINE REMOVED BY PROVIDING LT AB CABLE
436 AMR JASVANTBHAI BABUBHAI RAVAL(CONTRACTOR)GODHAVADARLILIYA 20-Jan-15 FHOS ON DATED:20.01.15,AFTERNOON SEASON, CONTRACTOR B.B.RAMANI- LABORS DEPUTED FOR MAINTAINCE OF 11 KV BHESAWADI AG FEEDER AT PREMAJI KESHAV GROUP.LINE MAN SH.TADAVI HAS TAKEN LINE CLEAR OF BHESAVADI FEEDER & INSTRUCT CONTRACTOR PERSON TO MAKE LINE SHORT,EARTHED BUT HE HIMSELF NOT CHECKED BY MAKING LINE SHORT OR EARTHED. WHEN LABORS CLIMB ON POLE TO EARTH THE LINE & REMOVING OF JUMPER ON  2 DIFFERENT POLE ACCIDENT OCCURRED. DETAIL REPORT IS AVIATED NOT YET RECEIVED N.A N.A Awareness among contractors regarding safety in every meeting
437 AMR SAILESHBHAI LALJIBHAI PARMAR(EA)DEDANKHAMBHA 7-Feb-15 FHD FOUR LINE STAFF OF PGVCL- KHAMBHA SUB DIVISION
INCLUDING LINE INSPECTOR WERE WORKING ON GIDER POLE
OF 11KV DEDAN AG. FEEDER NEAR DEDAN- RANINGPARA
AG. AREA. WHILE ANCHORING OF BROKEN CONDUCTOR, A
13 PRIMARY REASON FOR ACCIDENT TAPPING ANGLE ON WHICH VICTIM WAS STANDING,
DETACHED FROM POLE DUE TO BREAKING OF BACK PIECE
RUSTED BOLTS. A VICTIM FELL DOWN AND MET WITH THE
-::~ FATAL MECHANICAL ACCIDENT. PM REPORT AND DETAIL
;I INVESTIGATION FOLLOWS.
NOT YET RECEIVED N.A N.A DETERIORATED FABRICATIONS REPLACED
438 AMR JADAVBHAI KANABHAI MAKWANADHOLARADIJAFRABAD 19-Nov-14 FHOS 19/11/2014, IT IS INFORM TO JAFARABAD S/DN BY  POLICE STATION NAGESHREE APPLICATION RECIVING ON DT 18/12/14 INWORD NO JFD/2365 IT IS POSSIBILITY TO ELECTROCUTED WITH VICTIM,WHEN VICTIM CAME IN CONTACT WITH LIVE WIRE OF TRANSFORMER  DO JUMPER WHEN HE SHOULD WORK  ON TRANSFORMER AFTER REMOVING DO WIRE WITHOUT PERMISSION OF  SUBDIVISION ANY LINE STAFF, BY MISTAKE OF THEIR OWN  ELECTROCUTED THOUGH 11 KV FEEDER.    NOT YET RECEIVED N.A N.A Public awareness for safety during village meeting and khedut shibir.
439 AMR SHRI BHANUPRASAD LALABHAI TAVIYAD(E.A.)AMBADAUNA 31-Mar-15 NFHD AFTER CUTTING OF TREE BRANCHES WHICH WERE OBSTACLE IN 11 KV MOHABATPARA AG FEEDER, SHRI BHANUPRASAD LALABHAI TAVIYAD (E.A.) (E-URJA EMPLOYEE NO: 16805) HAS BEEN FALL FROM TREE TO LAND AND GOT INJURED OF LEG AND BACK HEAD. NOT YET RECEIVED N.A N.A Awareness regarding safety during work exucution among line staff during every safety meeting.
440 SNR Shri Hasmukhbhai Tapubhai Solanki 1-10-14 FHOS When the victim was standing of top of the truck cabin under 11 kv line of kherva jgy feeder and trying to fold tarpaulin ( tadpatri ) at that time been contacted with line and got electrocuted. REPORT YET NOT RECEIVED NA NA Maint Done
441 SNR A buffalo of Shri Bhaichandbhai Bhavanbhai 8-10-14 FA Due to burnt  ht bushing jumper of  T/C   and hanging ,  casually coming contact  to body of t/c with angle at the same time  Buffalow     might came in contact to  D P structure with bottom angle( 4 feet ,support angle  of bottom) and  leakage current pass through the burnt ht jumper to body of t/c to angle  to body of buffalow  and electrocuted                                            REPORT YET NOT RECEIVED NA NA Maint Done
442 SNR A cow  of Shri Ghughabhai Popatbhai 8-10-14 FA FATAL ELECTRICAL ACCIDENT OCCURRED TO A COW & ITS CALF OF GHUGHABHA POPATBHAI MEVADA AT VILLAGE SURAI DUE TO SNAPPING OF CONDUCTOR OF 11KV LINE DUE TO OVER CURRENT & AT THAT TIME COW & ITS CALF WAS PASSING UNDER HT LINE OF 11KV SURAI AG FEEDER AND GOT ELECTRIC SHOCK & DIED ON SPOT  REPORT YET NOT RECEIVED NA NA Maint Done
443 SNR  A calf of Shri Ghughabhai Popatbhai 8-10-14 FA FATAL ELECTRICAL ACCIDENT OCCURRED TO A COW & ITS CALF OF GHUGHABHA POPATBHAI MEVADA AT VILLAGE SURAI DUE TO SNAPPING OF CONDUCTOR OF 11KV LINE DUE TO OVER CURRENT & AT THAT TIME COW & ITS CALF WAS PASSING UNDER HT LINE OF 11KV SURAI AG FEEDER AND GOT ELECTRIC SHOCK & DIED ON SPOT  REPORT YET NOT RECEIVED NA NA Maint Done
444 SNR Shri Karsanbhai Satabhai Savdhariya 12-12-14 FHOS An electrical human fatal accident occur on date 12/12/2014 at 17:30 approx to Karsanbhai Satabhai Savdhariya as victim was carrying iron bar with him and iron bar might  came in contact  with 11kv line and get electroculated also sparking occurred on 11kv line conductor & tripping occurred at this time on 11kv feeder. Clearance from ground to live conductor is approx.20 feet.  REPORT YET NOT RECEIVED NA NA Maint Done
445 SNR Shri Bhimsingbhai Somabhai Nayak 31/12/14 FHOS A human fatal accident occurred on date 31/12/2014 to Bhimsingbhai Somabhai Nayak, age approx 40 years, at village Kankavati during carrying out maintenance work of 11 KV Kankavati Ag feeder. Victim is labour of contractor Shri Naththubhai Karsanbhai.                                                            cause of accident:-The Lobours were working on 11 KV Kankavati ag feeder for maintenance work, the victim was climbed on 11 kv Satyam JGY Instead of 11 kv kankavati AG  by his own mistake & get arc of 11 KV & fall down to earth. REPORT YET NOT RECEIVED NA NA Maint Done
446 SNR Kumar Vishalbhai Ashokbhai Jarvaliya 11-2-15 FHOS An electrical fatal human accident occurred on dtd.11.2.15 at 1.30 PM as 100 KVA TC located on otta and fencing done surrounding otta. As DT meter cable was cracked and might came in contact of fencing angle of VTC and at the same time school recess is happened and victim would have passed from there and might came in contact of fencing and got electrocuted. REPORT YET NOT RECEIVED NA NA Maint Done
447 SNR Kum. Vaniben Nudhabhai Bharvad 21/2/15 NFHOS When victim was playing with lunger of shoes tied with string on terrace and it went in HT line of 11 KV Jadeshwar Urban feeder and she was trying to remove it from HT line by iron rod. The iron rod came in induction zone of HT line and current passed through iron rod to victim body's and got electric shock. REPORT YET NOT RECEIVED NA NA Maint Done
448 SNR Buffalo of Shri Juvansinh Kalubha Zala 7-3-15 FA A Fatal electrical accident occurred due to Snapping of HT Conductor between Location No CHO/CHO/CT/061/R001 & R002. PVC Coated Conductor found snapped between above two locations due to ageing effect and hanging conductor did not touched ground and hence Tripping not reflected on the protection system, Buffalo came in direct contact with the Live Wire and hence Accident occurred on date 07.03.2015 @ 08:15 AM REPORT YET NOT RECEIVED NA NA Maint Done
449 SNR 1 Nos of cow-(1) Kukabhai Hindubhai & (2) Ranabhai Jivanbhai 15/3/15 FA Due to heavy rain and wind, live part of wire dis connected from the street light fixture came in to the contact of LT girder pole of 11KV Ratanpar Feeder, Where two nos of cows came in the contact of girder pole  which resulted in to the fatal accident.  REPORT YET NOT RECEIVED NA NA Maint Done
450 SNR 1 Nos of cow-(1) Kukabhai Hindubhai & (2) Ranabhai Jivanbhai 15/3/15 FA Due to heavy rain and wind, live part of wire dis connected from the street light fixture came in to the contact of LT girder pole of 11KV Ratanpar Feeder, Where two nos of cows came in the contact of girder pole  which resulted in to the fatal accident.  REPORT YET NOT RECEIVED NA NA Maint Done